Puls Dimension C Series User manual

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/26
POWER SUPPLY
▪AC 100-240V Wide-range Input
▪Width only 32mm
▪NEC Class 2 compliant
▪Efficiency up to 89.8%
▪Full Power between -25°C and +60°C
▪3 Year Warranty
PRODUCT DESCRIPTION
The DIMENSION C-Line units are cost optimized power supplies
without compromising quality, reliability and performance. The
C-Line is part of the DIMENSION power supply family, existing
alongside the high featured Q-Line.
The CS3.241 includes all the essential basic functions but also
includes important features of small size, high efficiency, wide
temperature range and is NEC Class 2 compliant.
The wide range input makes worldwide installation and usage
very simple. Defects or system failures caused by wrongly set
switches cannot occur.
High immunity to transients and power surges as well as low
electromagnetic emission and a large international approval
package for a variety of applications makes this unit suitable for
nearly every situation.
SHORT-FORM DATA
Output voltage
DC 24V
Adjustment range
24 - 28V
Output current
3.3 –2.7A
below +60°C
ambient
2.5 –2.1A
at +70°C ambient
Derate between +60°C and +70°C
Output power
80W
Output ripple
max. 50mVpp
20Hz to 20MHz
AC Input voltage
AC 100-240V
±10%
Wide-range input
Mains frequency
50-60Hz
±6%
AC Input current
1.23 / 0.68A
at 120 / 230Vac
DC Input voltage
DC 110-300V
-20 / +25%
DC Input current
0.81 / 0.29A
at 110 / 300Vdc
Power factor
0.61 / 0.56
at 120 / 230Vac
AC Inrush current
23 / 45A peak
at 120 / 230Vac
Efficiency
88.0 / 89.8%
at 120 / 230Vac
Losses
11.1 / 9.1W
at 120 / 230Vac
Temperature range
-25°C to +70°C
operational
Hold-up time
29 / 120ms
at 120 / 230Vac
Dimensions
32x124x102mm
WxHxD
Weight
430g
ORDER NUMBERS
Power Supply CS3.241 24-28V Standard unit
Accessory ZM1.WALL Wall mount bracket
ZM11.SIDE Side mount bracket
YRM2.DIODE Redundancy module
MAIN APPROVALS
For details and the complete approval list, see chapter 18.
UL 508
UL 60950-1
Class I Div 2
Marine

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
2/26
INDEX
Page Page
1. Intended Use................................................................3
2. Installation Requirements............................................3
3. AC-Input .......................................................................5
4. DC-Input .......................................................................6
5. Input Inrush Current.....................................................7
6. Output..........................................................................8
7. Hold-up Time................................................................9
8. Efficiency and Power Losses.......................................10
9. Lifetime Expectancy and MTBF ..................................11
10. Functional Diagram ....................................................11
11. Terminals and Wiring .................................................12
12. Front Side and User Elements ....................................13
13. EMC............................................................................14
14. Environment...............................................................15
15. Protection Features....................................................16
16. Safety Features...........................................................16
17. Dielectric Strength......................................................17
18. Approved, Fulfilled or Tested Standards ....................18
19. Regulatory Product Compliance.................................19
20. Physical Dimensions and Weight ............................... 20
21. Accessories................................................................. 21
21.1. ZM1.WALL - Wall Mounting Bracket ................ 21
21.2. ZM11.SIDE - Side Mounting Bracket................. 21
21.3. Redundancy Modules....................................... 22
22. Application Notes....................................................... 23
22.1. Peak Current Capability.................................... 23
22.2. Back-feeding Loads .......................................... 23
22.3. External Input Protection................................. 24
22.4. Parallel Use to Increase Output Power ............ 24
22.5. Parallel Use for Redundancy ............................ 24
22.6. Charging of Batteries........................................ 24
22.7. Series Operation............................................... 25
22.8. Inductive and Capacitive Loads ........................ 25
22.9. Operation on Two Phases ................................ 25
22.10. Use in a Tightly Sealed Enclosure..................... 25
22.11. Mounting Orientations..................................... 26
The information presented in this document is believed to be accurate and reliable and may change without notice.
No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
TERMINOLOGY,ABREVIATIONS AND DEFINITIONS
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
t.b.d. To be defined, value or description will follow later.
AC 230V A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances
(usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
230Vac A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.
50Hz vs. 60Hz As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50Hz mains frequency. AC
120V parameters are valid for 60Hz mains frequency.
may A key word indicating flexibility of choice with no implied preference.
shall A key word indicating a mandatory requirement.
should A key word indicating flexibility of choice with a strongly preferred implementation.

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/26
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control,
monitoring, measurement equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without additional
appropriate safety devices, that are suited for the end-application.
If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.
2. INSTALLATION INSTRUCTIONS
WARNING
Risk of electrical shock, fire, personal injury or death.
- Turn power off before working on the device and protect against inadvertent re-powering.
- Do not open, modify or repair the device.
- Use caution to prevent any foreign objects from entering into the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Obey the following installation instructions:
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for
inspection.
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN rail according to EN 60715 with the input terminals on the bottom of the device. Other mounting
orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are designed for a
minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient temperatures up to +60°C and 90°C
for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the input terminals. Unused screw
terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed.
The enclosure of the device provides a degree of protection of IP20.The housing does not provide protection against spilled liquids.
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested for impulse withstand voltages up to
4kV, which corresponds to OVC III according to IEC 60664-1.
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use without a proper PE (Protective Earth)
connection.
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage between the input terminals and the PE
potential must not exceed 264Vac.
The input can also be powered from batteries or similar DC sources. The continuous voltage between the supply voltage and the
PE/ground potential must not exceed 375Vdc.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation
grid!
The device is designed for altitudes up to 5000m. Above 2000m a reduction in output current is required.

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/26
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase the 5mm to
15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, the 5mm can be reduced
to zero.
The device is designed, tested and approved for branch circuits up to 20A without additional protection device. If an external fuse is
utilized, do not use circuit breakers smaller than 10A B- or 6A C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C.
The operational temperature is the same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations.
Substitution of components may impair suitability for this environment.
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or the area is known to be non-
hazardous.

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/26
3. AC-INPUT
AC input
nom.
AC 100-240V
±10%, Wide-range input
Mains network systems
TN, TT or IT
AC input range
90-264Vac
85-90Vac
264-300Vac
short-term or with reduced output current
max. 500ms
Allowed voltage L or N to earth
max.
300Vac
continuous, IEC 62103
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
75Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ.
58Vac
steady-state value, see Fig. 3-1
External input protection
See recommendations in chapter 22.3.
AC 100V
AC 120V
AC 230V
Input current
typ.
1.48A
1.23A
0.68A
at 24V, 3.3A, see Fig. 3-3
Power factor*)
typ.
0.62
0.61
0.56
at 24V, 3.3A, see Fig. 3-4
Crest factor**)
typ.
3.1
3.2
4.0
at 24V, 3.3A
Start-up delay
typ.
95ms
95ms
95ms
see Fig. 3-2
Rise time
typ.
18ms
29ms
56ms
at 24V, 3.3A const. current load, 0mF
load capacitance, see Fig. 3-2
typ.
35ms
52ms
92ms
at 24V, 3.3A const. current load, 3.3mF
load capacitance
Turn-on overshoot
max.
400mV
400mV
400mV
see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage ranges
Fig. 3-2 Turn-on behavior, definitions
Turn-on
(85)90
max.
500ms
VIN
P
OUT
300Vac264
Shut-down
RatedInput
Range
Start-up
delay Rise
Time
Overshoot
-5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 24V
Fig. 3-4 Power factor vs. output load
0.5 1.51.0 2.0 2.5 3.0 3.5A
0
0.3
0.6
0.9
1.2
1.5
1.8A
Output Current
Input Current, typ.
(a)100Vac
(b)120Vac
(c)230Vac
(a)
(b)
(c)
Power Factor, typ.
0.5 1.0 1.5 2.0 3.5A
0.40
0.45
0.50
0.55
0.60
0.65
Output Current
2.5 3.0
(a)100Vac
(b)120Vac
(c) 230Vac
(a)
(b)
(c)

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/26
4. DC-INPUT
The power supply can be supplied with an AC or DC input voltage.
Instructions for DC-use:
a) Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not recommended and can
cause a malfunction or damage the unit.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the machine ground.
DC input
nom.
DC 110-300V
-20% / +25%
DC input range
88-375Vdc
observe reduced output current below 100Vdc,
see Fig. 4-2.
DC input current
typ.
0.81A / 0.29A
at 110Vdc / 300Vdc
Allowed Voltage L/N to Earth
max.
375Vdc
continuous, IEC 62103
Turn-on voltage
typ.
103Vdc
steady state value
Shut-down voltage
typ.
50Vdc
steady state value
Fig. 4-1 Wiring for DC Input
Fig. 4-2 Output current vs. input voltage
+
-
Load
L
PE
+
-
Power Supply
AC
DC
Battery
N
0
1.5
1.0
2.0
0.5
3.5A
88 110 375Vdc
DCInput Voltage
2.5
3.0
Output Current

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/26
5. INPUT INRUSH CURRENT
After turn-on of the input voltage, an active inrush limitation circuit limits the input inrush current. Virtually no input inrush current is
generated.
The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V
AC 120V
AC 230V
Inrush current
max.
24Apeak
28Apeak
54Apeak
at +40°C ambient, cold start
typ.
14Apeak
16Apeak
32Apeak
at +25°C ambient, cold start
typ.
20Apeak
23Apeak
45Apeak
at +40°C ambient, cold start
Inrush energy
max.
0.4A2s
0.5A2s
1.7A2s
at +40°C ambient, cold start
Fig. 5-1 Typical input inrush current behavior
Input Current
Input Voltage
Output Voltage
Input: 230Vac
Output: 24V, 3.3A
Ambient: 25°C
Upper curve: Input current (20A / DIV)
Medium curve: Input voltage (500V / DIV)
Lower curve: Output voltage (20V / DIV)
Time scale: 40ms / DIV

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/26
6. OUTPUT
Output voltage
nom.
24V
Adjustment range
24-28V
guaranteed
max.
30V**)
at clockwise end position of potentiometer
Factory settings
typ.
24.1V
±0.2%, at full load, cold unit,
Line regulation
max.
50mV
90-300Vac
Load regulation
max.
100mV
static value, 0A →3.3A; see Fig. 6-1
Ripple and noise voltage
max.
50mVpp
20Hz to 20MHz, 50Ohm
Output current
nom.
3.3A
at 24V, ambient temperature <60°C, see Fig. 6-1
nom.
2.5A
at 24V and 70°C ambient temperature
nom.
2.7A
at 28V, ambient temperature <60°C, see Fig. 6-1
nom.
2.1A
at 28V and 70°C ambient temperature
Reduce output current linearly between +60°C and +70°C
Output power
nom.
80W
continuously available
Overload behavior
continuous current
see Fig. 6-1
Short-circuit current
min.
4A*)
load impedance <250mOhm, see Fig. 6-1
max.
8A*)
load impedance <250mOhm, see Fig. 6-1
Output capacitance
typ.
1 450µF
included inside the power supply
*) Discharge current of output capacitors is not included.
**) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value
which can be achieved. The typical value is about 28.5V.
Fig. 6-1 Output voltage vs. output current, typ.
Output Voltage
00 4
4
8
12
28V
16
20
24
7A621 3 5
Adjustment
Range
Output Current
a)100Vac
b)120Vac
c)230Vac
abc

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/26
7. HOLD-UP TIME
AC 100V
AC 120V
AC 230V
Hold-up Time
typ.
38ms
60ms
244ms
at 24V, 1.65A, see Fig. 7-1
min.
29ms
45ms
200ms
at 24V, 1.65A, see Fig. 7-1
typ.
19ms
29ms
120ms
at 24V, 3.3A, see Fig. 7-1
min.
15ms
23ms
95ms
at 24V, 3.3A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
Fig. 7-2 Shut-down behavior, definitions
0
25
50
75
100
225ms
85 120 155 190 230Vac
Input Voltage
125
150
175
Hold-up
Time
200
24V,3.3A,min.
24V,3.3A,typ.
24V,1.65A,min.
24V,1.65A,typ.
-5%
Hold-up Time
ZeroTransition
Output
Voltage
Input
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK LED is on during this time.

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/26
8. EFFICIENCY AND POWER LOSSES
AC 100V
AC 120V
AC 230V
Efficiency
typ.
86.4%
88.0%
89.8%
at 24V, 3.3A
Average efficiency*)
typ.
87.4%
88.4%
87.7%
25% at 0.83A, 25% at 1.65A,
25% at 2.5A. 25% at 3.3A
Power losses
typ.
1.0W
1.1W
1.8W
at 24V, 0A
typ.
5.4W
4.9W
5.9W
at 24V, 1.65A
typ.
12.5W
11.1W
9.1W
at 24V, 3.3A
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of
the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the
time.
Fig. 8-1 Efficiency vs. output current at 24V, typ
Fig. 8-2 Losses vs. output current at 24V, typ.
Efficiency
0.5 1.0 3.5A
86
87
88
89
Output Current
90
91%
85 2.0 3.01.5 2.5
(a)
(b)
(c)
(a)100Vac
(b)120Vac
(c) 230Vac
Power Losses
0 0.5 3.5A
0
2
4
6
8
10
12W
1.0 1.5 2.0 2.5 3.0
Output Current
(a)
(b)
(c)
(a)100Vac
(b)120Vac
(c) 230Vac
Fig. 8-3 Efficiency vs. input voltage at 24V, 3.3A, typ.
Fig. 8-4 Losses vs. input voltage at 24V, 3.3A, typ.
Efficiency
85 120 155 190 225 260Vac
85
86
87
88
Input Voltage
89
90
91%
Power Losses
0
3
6
9
12
15
18W
85 120 155 190 225 260Vac
Input Voltage

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/26
9. LIFETIME EXPECTANCY AND MTBF
AC 100V
AC 120V
AC 230V
Lifetime expectancy*)
98 000h
106 000h
120 000h
at 24V, 1.65A and 40°C
277 000h*)
300 000h*)
338 000h*)
at 24V, 1.65A and 25°C
57 000h
64 000h
77 000h
at 24V, 3.3A and 40°C
160 000h*)
180 000h*)
218 000h*)
at 24V, 3.3A and 25°C
MTBF**) SN 29500, IEC 61709
1 788 000h
1 901 000h
2 243 000h
at 24V, 3.3A and 40°C
3 131 000h
3 287 000h
3 796 000h
at 24V, 3.3A and 25°C
MTBF**) MIL HDBK 217F
849 000h
854 000h
886 000h
at 24V, 3.3A and 40°C;
Ground Benign GB40
1 088 000h
1 095 000h
1 153 000h
at 24V, 3.3A and 25°C;
Ground Benign GB25
195 000h
196 000h
214 000h
at 24V, 3.3A and 40°C;
Ground Fixed GF40
246 000h
246 000h
272 000h
at 24V, 3.3A and 25°C;
Ground Fixed GF25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in
electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The
manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated
theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical
representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that statistically one unit will fail
every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit has been running for 50 000h or only for 100h.
10.FUNCTIONAL DIAGRAM
Fig. 10-1 Functional diagram
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
NTCInrush
Limiter

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/26
11.TERMINALS AND WIRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Type
Screw terminals
Solid wire
0.5-6mm2
Stranded wire
0.5-4mm2
American Wire Gauge
AWG20-10
Max. wire diameter
2.8mm (including ferrules)
Wire stripping length
7mm
Screwdriver
3.5mm slotted or cross-head No 2
Recommended tightening torque
1Nm
Pull-out force
according to UL 486E
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Do not use the unit without PE connection.
e) Unused terminal compartments should be securely tightened.
f) Ferrules are allowed.

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/26
12.FRONT SIDE AND USER ELEMENTS
Fig. 12-1 Front side
A Input Terminals (screw terminals)
N, L Line input
PE (Protective Earth) input
B Output Terminals (screw terminals, two pins per pole)
+ Positive output
–Negative (return) output
C Output voltage potentiometer
Open the flap to adjust the output voltage. Factory set: 24.1V
D DC-OK LED (green)
On, when the voltage on the output terminals is >21V

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/26
13.EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light industry
environment.
A detailed EMC report is available on request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
contact discharge
air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
input lines
output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L →N
L →PE, N →PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+ →-
+ / - →PE
500V
1kV
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
10V
Criterion A
Mains voltage dips
EN 61000-4-11
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion B *)
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11
5000ms
Criterion C
Powerful transients
VDE 0160
over entire load range
750V, 1.3ms
Criterion A
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
B: Temporary voltage dips possible. No change in operation mode.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply
will occur.
*): Criterion A is fulfilled below 2.8A output current
EMC Emission
According generic standards: EN 61000-6-3, EN 61000-6-4
Conducted emission
input lines
EN 55011, EN 55032, FCC Part 15, CISPR 11, CISPR 32
Class B
Conducted emission
output lines**)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power port according
EN 61000-6-3 not fulfilled
Radiated emission
EN 55011, EN 55032
Class B
Harmonic input current
EN 61000-3-2
fulfilled
Voltage fluctuations, flicker
EN 61000-3-3
fulfilled*)
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired operation.
*) tested with constant current loads, non pulsing
**) for information only, not mandatory for EN 61000-6-3
Switching frequency
50kHz to 450kHz
Main converter, input voltage and load dependent

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/26
14.ENVIRONMENT
Operational temperature*)
-25°C to +70°C
reduce output power according Fig. 14-1
Storage temperature
-40°C to +85°C
for storage and transportation
Output derating
1.8W/°C
60°C to 70°C
Humidity**)
5 to 95% r.h.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g***)
2 hours / axis***)
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 2000m
without any restrictions
2000 to 6000m
reduce output power or ambient temperature,
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
Altitude derating
5W/1000m or 5°C/1000m
> 2000m, see Fig. 14-2
Over-voltage category
III
IEC 62103, EN 50178, altitudes up to 2000m
II
altitudes from 2000m to 6000m
Degree of pollution
2
IEC 62103, EN 50178, not conductive
*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation.
Fig. 14-1 Output current vs. ambient temp.
Fig. 14-2 Output current vs. altitude
0-25 0 20 40 70°C
1
2
3
4A
60
Ambient Temperature
Allowable Output
Current at 24V
002000 4000 6000m
1
2
3
4A
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
C
A
B
Allowable Output
Current at 24V

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
16/26
15.PROTECTION FEATURES
Output protection
Electronically protected against overload, no-load and short-circuits*)
Output over-voltage protection
typ. 34Vdc
max. 39Vdc
In case of an internal power supply defect, a redundant circuit
limits the maximum output voltage. The output shuts down and
automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Caution: For use in a controlled environment according to CSA
22.2 No 107.1-01.
Penetration protection
> 3.5mm
e.g. screws, small parts
Over-temperature protection
no
Input transient protection
MOV (Metal Oxide Varistor)
Internal input fuse
included
not user replaceable
*) In case of a protection event, audible noise may occur.
16.SAFETY FEATURES
Input / output separation*)
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 5MOhm
input to output, 500Vdc
PE resistance
< 0.1Ohm
between housing and PE terminal
Touch current (leakage current)
typ. 0.16mA / 0.35mA
100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.24mA / 0.52mA
120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.41mA / 0.85mA
230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.22mA / 0.43mA
110Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.32mA / 0.63mA
132Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.57mA / 1.08mA
264Vac, 50Hz, TN-,TT-mains / IT-mains

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/26
17.DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer.
Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s
down). Connect all input-terminals together as well as all output poles before conducting the test. When testing, set the cut-off current
settings to the value in the table below.
Fig. 17-1 Dielectric strength
A
B
C
A
C
L
Input
Earth,PE
Output
+
-
NB
Type test
60s
2500Vac
3000Vac
500Vac
Factory test
5s
2500Vac
2500Vac
500Vac
Field test
5s
2000Vac
2000Vac
500Vac
Cut-off current setting
> 10mA
> 10mA
> 10mA
To fulfil the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the –pole or any other part of the
output circuit shall be connected to the protective earth system. This helps
to avoid situations in which a load starts unexpectedly or can not be
switched off when unnoticed earth faults occur.

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
18/26
18.APPROVED,FULFILLED OR TESTED STANDARDS
UL 508
UL Certificate
Listed equipment for category NMTR - Industrial Control Equipment
Applicable for US and Canada
E-File: E198865
IEC 61010-2-201
Manufacturer's Declaration
Electrical Equipment for Measurement, Control and Laboratory Use -
Particular requirements for control equipment
IEC 60950-1
CB Scheme Certificate
General safety requirements for Information Technology Equipment
(ITE)
UL 60950-1
UL Certificate
Recognized component for category QQGQ - Information Technology
Equipment (ITE)
Applicable for US and Canada
E-File: E137006
Class I Div 2
CSA Certificate
Power Supplies for Hazardous Location
Applicable for Canada and US
CSA Class: 5318-01 (Canada), 5318-81 (USA)
Temperature Code: T3
Groups: A, B, C and D
Marine (DNV)
DNV Certificate
DNV Type approved product
Certificate: TAA00001ST
Temperature: Class B
Humidity: Class B
Vibration: Class C
EMC: Class A
Enclosure: Class A
NEC Class 2
Manufacturer's Declaration
NEC Class 2 - Limited Power Source
Listed device according to NEC Handbook chapter 725-121
ISA-71.04 G3
Manufacturer's Declaration (Online Document)
Airborne Contaminants Corrosion Test
Severity Level: G3 Harsh
H2S: 100ppb
NOx: 1250ppb
Cl2: 20ppb
SO2: 300ppb
Test Duration: 3 weeks, which simulates a service life of at least 10
years.
VDMA 24364
Paint Wetting Impairment Substances Test (or LABS-Test)
Tested for Zone 2 and test class C1 according to VDMA 24364-C1-
L/W for solvents and water-based paints

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
19/26
19.REGULATORY PRODUCT COMPLIANCE
EU Declaration of Conformity
The CE mark indicates conformance with the
- EMC directive
- Low-voltage directive
- RoHS directive
REACH Regulation (EU)
Manufacturer's Declaration
EU regulation regarding the Registration, Evaluation, Authorisation and
Restriction of Chemicals (REACH) fulfilled.
EU Regulation (EC) 1907/2006.
WEEE Regulation
Manufacturer's Declaration
EU Regulation on Waste Electrical and Electronic Equipment
Registered as business to business (B2B) products.
EU Regulation 2012/19/EU
UKCA
UKCA Declaration of Conformity
Trade conformity assessment for England, Scotland and Wales
The UKCA mark indicates conformity with the UK Statutory
Instruments
2016 No.1101,
2016 No.1091,
2012 No.3032

CS3.241
C-Line
24V, 3.3A, SINGLE PHASE INPUT
Jun. 2023 / Rev. 2.1 DS-CS3.241-EN
All parameters are specified at 24V, 3.3A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
20/26
20.PHYSICAL DIMENSIONS AND WEIGHT
Width
32mm
Height
124mm
Depth
102mm
The DIN rail depth must be added to the unit depth to calculate the total required installation depth.
Weight
430g
DIN rail
Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
Housing material
Body: Aluminium alloy
Cover: Zinc-plated steel
Installation clearances
See chapter 2
Fig. 20-1 Front view
Fig. 20-2 Side view
Other manuals for Dimension C Series
6
This manual suits for next models
1
Table of contents
Other Puls I/O System manuals
Popular I/O System manuals by other brands

Weidmuller
Weidmuller WI-I/O 9-K user manual

Acard
Acard ARS-2160H Quick installation guide

Spectrum Controls
Spectrum Controls Micro800 2085-OB32-SC user manual

ICP DAS USA
ICP DAS USA I-7021 user manual

Andover Controls
Andover Controls Continuum UI-8-10 Technical manual

Acces I/O products
Acces I/O products M.2-AIO16-16F Series Hardware manual