Pumps (UK) PUK Autopress 1LC User manual

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
O&M for models:
Autopress 1LC, Autopress 1HC, Autopress 1HHC,
Autopress 2LC, Autopress 2HC, Autopress 2HHC
FOR SERVICE AND MAINTENANCE
CALL: 01322 292415

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Operation & Maintenance Manual
EC Declaration of conformity
Pumps (UK) Ltd declare that the Presfix pressurisation set conforms to the requirements of the Machinery Safety Directive
2006/42/EC.
Electromagnetic compatibility (EMC) Directive 2014/30/EU Conforming to the UK Health & Safety
Requirements 2008 No.1597
Water supply (Water fittings) regulations 1999
Code of practice for heating and chilled water systems BS7074 (parts 1, 2 & 3)
Signed: Position: Engineering manager Date: 20-04-2016 Revision E
Clive Willmott
Introduction
This leaflet contains information to enable the safe installation and operation of the products mentioned above. The following instructions must be read and
understood by all persons responsible for the installation, operation and maintenance of this product.
Warning Symbols
Safety instructions where noncompliance would affect safety.
Safety instruction where electrical hazard is involved.
Safety instruction where noncompliance could cause damage to the equipment.
Instruction for safe use
This product has been designed for the pressurisation of sealed heating, chilled water and closed-condenser water systems to the operating
conditions shown.
This product should not be installed until this leaflet has been studied carefully.
Handling, transportation and installation of this equipment should only take place with the proper use of lifting equipment.
This product must be stored in a frost-free dry environment.
Noise Emissions
This equipment operates at a noise level lower than 70dBA. Protection degree
IP54
Ambient temperature 4-30°C
Maximum system operating pressure: 2.8 & 5.5 units (10 bar) 8.0 units (13 bar)
Installation
The Autopress unit is despatched mounted on a wooden pallet and covered in a protective film, it is recommended that the unit be retained in
the protective packaging until the product is to be installed. The unit will arrive pre-packaged and wired ready for installation.
This product has been fully run tested at our works under simulated site conditions. The unit should be thoroughly checked for physical damage
that may have been caused during transit.
If the unit is found to have damage it must be reported immediately and should not be installed. The unit must be sited in a dry clean well-
ventilated area with good all round access, mounting can be either wall or floor. The unit is despatched with bottom fixing brackets turned inward
suitable for wall mounting, for floor mounting turn brackets to face outward which will give access to mounting holes
Electrical connections
The cable used for the incoming supply must be of adequate size to carry the motor full load current. This is shown on the duty plate. All non
power caballing should be limited to 2.5mm². All connections must be made using the appropriate wiring drawings for the equipment being
installed, with particular attention being paid to the supply voltages.
The supply voltage is shown on the set duty plate.
Never operate this product with the control panel door in the open position. It is essential that this equipment
is earthed to the building earth system.
Pumps operate at 230v 50Hz

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
The base frame must be earth bonded directly to the building earth system.
All wiring should be arranged such that it enters the control section through the appropriate cable glands.
Water supply and system connection
Connect the Autopress set ½”BSP ball valve (left side of cabinet) to a suitable water supply, incorporating an approved stop cock.
If the pressure available at the ball valve is below 0.3 bar, a low pressure orifice must be obtained and fitted.
Extend the 22mm plastic overflow pipe from the Autopress break tank to a position where an overflow will be noticed and rectified. Ensure the
warning pipe is able to handle the incoming water volume, if this is not the case then a reducing valve should be fitted to the incoming water
supply. Connect the pressurisation port ½” BSP (right hand side of cabinet) to the expansion vessel pipeline which in turn should be connected
to the suction side of the system circulating pump. Quick fill and isolating valves must also be fitted to this line (see connection sketch Fig 1)
The Break tank is constructed to have a weir slot as required by the water bylaws to prevent back flow contamination, if the inlet ball valve or NRV
suffered a catastrophic failure the overflow may not be able to keep up with the inflow in which case excess water will be ejected through the weir slot
and onto the plant room floor, if this is not acceptable then consideration should be given to fitting the pressurisation set onto a try with overflow to
drain
Commissioning
1. Fill the system with water via the quick fill filling loop to the system fill pressure, this filling loop must comply with local water authority bylaws
and contain double check valves. The filling loop must be completely removed after the system has been filled.
The pressurisation unit must never be used to fill the system.
The maximum running time for pumps fitted to this product must not exceed 4 hours in any 24 hour period.
It is essential that all air is allowed to escape freely via air vents and radiator vents etc. All air must be evacuated from the system for this
product to operate correctly.
2. Turn on the water supply feeding the product break tank. Water treatment crystals/chemicals must never be introduced to the system via the break
tank.
3. Check that pumps have been fully evacuated of all air by removing the bleed screw of each pump where fitted and allow water to escape
until no air is present. Replace bleed screws.
4. Before the unit is opened up to the main system pressure check the pre-charge in the internal vessel. The pre-charge should be set to
approximately 0.35bar below the system fill pressure. Charge as necessary with Nitrogen or dry air. Open system valve to Presfix Beta unit.
System set points
System set points are entered via the front panel interface.
To stop unauthorised adjustment of set points a lock switch is positioned on the back of the display PCB this will need to be switched to the
unlocked position to enable set points to be changed.
Switch the selector switch to the appropriate set point and the display will show the value of that particular set point, if the value is blinking on/off the
value is able to be modified, if the value is not blinking it means that the lock is active and the value will not be able to be changed.
To increase or decrease the value press the up/down buttons. The longer you press the button the quicker the change rate.
Once you have selected the correct value move the selector switch to next set point that you wish to change, the values in the previous set point
will be automatically saved.
Once you have entered data into all relevant set point parameters the selector switch should be set to the Auto position. If the data is to be locked
then switch the lock switch on the rear of display PCB to the locked position.
Set point description
Delay Start
This set point is adjustable between 0-10 seconds and is used to delay starting the pressurisation pump for the set period. This can be useful especially on
chilled water system where it can be very difficult to remove all air.
Low pressure set point
This set point is typically set approximately 0.4 bar below the fill point.
High pressure set point
This set point is typically set approximately 0.2 bar above the final working pressure.

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Duty pump cut in
This should be set to the static height of the building + 0.35 bar. The standby set points are automatically set from the duty pump set points
Auto
This is the normal operating position for the set and will display system pressure.
Off
The off position performs two functions, if the main pump has failed and the duty standby pump has been activated, the duty pump will be locked out until the
system is reset by switching the selector to the off position and then back to auto. If the selector switch is left in the off position no pumps will be able to run
but the system will still be monitored for all other conditions I.E. low/high pressure.
P1/P2 hand positions
If either pump one or pump two is selected that pump will run continuously regardless of system pressure. This function is primarily intended to check pump
rotation and pumps should not be left to run excessively. If a pump is left to run in this position it will automatically be locked out after 18 minutes.
Exercise
This set point is adjustable between 0-30 days and is used to run the pumps for a short period after the set time has elapsed, running the pumps at regular
intervals helps prevent pumps from seizing due to inactivity.
V/Free contacts
See appropriate drawing for Volt free contact availability. Rating 1A 50v maximum.
Features
Hours Run
With the selector switch in the off position press the up button to view pump1 run time press up button again to enter reset mode, hold down both up & down
buttons for 8 seconds and the display will zero. Repeat for pump 2 using down button.
Commissioning valves
Commissioning valves have been provided to aid fault finding and checking that the system operates at the correct values. The internal system isolation valve
fitted on the unit discharge pipe can be turned off so the unit is isolated from the system pressure. The small isolation valve can then be used to manipulate the
pressure within the unit to check that the pump cuts in and out as required. This valves can also be used to dump water/pressure back to the break tank to
enable the internal vessel pre-charge to be checked.
Remote inhibit
If the remote inhibit contacts have been activated then the display will show set inhibited, during this condition no pumps are allowed to run irrespective of
system pressure, however the system will still be monitored for all conditions.
Run limit exceeded
If a pump is called to operate for periods in excess of 18 minutes or a combination of frequent starts both pumps will be locked out and prevented from further
operation. To reset the timer circuit switch the selector switch to the off position and back to Auto again.
Transducer failure
If the transducer fails the display will read Sensor error and prevent pump operation, the high low pressure contacts will simultaneously operate to indicate that
a failure has occurred and switch off the boiler circuit.
Break tank low water level
The break tank contains a low level float switch which will stop all pumps from operating whilst the water level is low. Once the water level rises to the reset
position the pumps will be released to operate as normal.
Boiler/chiller interlock
A volt free normally closed circuit is provided as a boiler/chiller interlock. The circuit has 1 high pressure contact and 1 low pressure contact either of which,
when operating, will open the boiler/chiller circuit. If the high pressure contact is not required with chiller applications it can be omitted. See product wiring
drawing

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Operation
Ensure MCBs in the electrical section are at the on position, switch selector switch on front panel to Auto. Switch main isolator on front door
to the on position. The digital display will now go through the starting check sequence, after about 8 seconds the display will show system
pressure.
If the system pressure is lower than the fill pressure then a pump will run and start to raise the system pressure. Once the system pressure is
restored the pump will stop.
If the pressure in the system falls to the duty pump cut in point the duty pump will start, once the system pressure has been restored the duty
pump will stop. Each time the pressure falls the alternate pump (on two pump units) will start and restore system pressure. If the duty pump
after running for 2 seconds has not succeeded in raising the pressure and it continues to fall by 0.2 bar it will be deemed that the duty pump
has failed. The failed pump will then be locked out and the standby pump will run and take the place of the duty pump.
If a pump trips for any reason it will be locked out and the standby pump will operate in its place.
Once the reason for pump failure has been ascertained and rectified the selector switch can be switched to the off position and back to auto
to reset the controls.
Maintenance
Routine check (3 monthly intervals)
1. Check that the pump seal is not leaking.
2. Check the pump is not seized and develops the correct pressure.
3. Check that the pump operates without undue noise or vibration.
4. Check that the motor runs without overheating.
Routine check (6 monthly intervals)
1. Check the break tank is clean and that the correct water level has been maintained.
2. Check that all screws are tight on electrical components.
3. Check that the earth connections are tight and making good contact.
4. Check that the gas pre charge is at the correct pressure, this should be done by isolating the unit from the System and draining water back into the break
tank by opening one of the 4mm ball valves (see drawing for location) once the unit pressure has been discharged, a tyre gauge can be connected to the
precharge valve to display the vessel pre charge pressure. Recharge as necessary with Nitrogen or dry air. All other expansion vessels connected to the
system can be checked in the same manner

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Typical MTHW sealed system max. 120°C. Intermediate vessel only required on MTHW systems

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Fault finding guide
Fault
Possible Cause
Remedy
Pump fails to start
Power supply failure Control panel fuse blown,
MCB tripped
Remote inhibit active
Low water level
Reinstate incoming power supply
Replace power supply fuse
Reset MCB
Turn remote inhibit off
Reinstate water supply
Pump fails to stop
Set point set too high Manual operation selected
System pressure low due to large leak
Lower set point
Select Auto operation
Switch unit off until leak is repaired
Pump switches on and off quickly
Air in system Vessel pre-charge incorrect
Purge air from pumps and pipework Check vessel
pre-charge and Charge as necessary with
Nitrogen or dry air
Pump runs but will not make pressure
Pump air locked Commissioning valve left open
Incorrect rotation
Passing too much water
Open pump bleed screw and vent pump Check
commissioning valves are in correct position.
Check pump internal connections. Check system
for leaks
Pump overheating
Pump partially seized
Remove pump and check for sediment build up or
foreign objects
Pump set frequently starting. (pressure falls to cut
in point)
Newly installed system with large amount of air in
pipe work
Leaks in system pipe work Vessel pre-charge
incorrect in open position
Bleed system to remove air
Repair leaks
Isolate vessel and pre-charge with
Nitrogen as appropriate
Break tank overflowing
Leaking ball valve
Non-return valve letting by
Commissioning valve left in open position
Replace ball valve seal
Replace/clean non-return valve
Close commissioning valve
Pump stops and pressure drops immediately
Non-return valve letting by
Vessel pre-charge incorrect
Replace non-return valve
Check vessel pre-charge and Charge as
necessary with Nitrogen or dry air

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Single Pump Wiring Diagram

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Twin Pump Wiring Diagram

www.pumpsukltd.co.uk | info@pumpsukltd.co.uk
Units 3-4 Invicta Park, Sandpit Road, Dartford, Kent, DA1 5BU
Dual System Wiring Diagram
This manual suits for next models
5
Table of contents
Popular Water Pump manuals by other brands

KIRLOSKAR
KIRLOSKAR Non-Clog Submersible Series Instructions on Installation, Operation and Maintenance Manual

Wilo
Wilo SCPV Installation and operating instructions

AMT
AMT 3680 Series Specifications information and repair parts manual

EINHELL
EINHELL 41.802.83 operating instructions

EINHELL
EINHELL HWA 800K operating instructions

FMT Swiss AG
FMT Swiss AG PREMAxx operating instructions