
Corporate
800.882.8854
11
Interconnecting Piping- Critical to System Functionality
• The piping between the tanks/compartments will set the liquid level in each tank.
The elevation and downward elbow help prevent oating material and settled
solids from moving to the next tank.
• For the PW050/100 / 200 / 300 series, the interconnecting piping needs
to be a minimum of 4”. For PW350 / 400 / 700 series, the minimum is 6” to help
with ow through the tanks.
Sewer Overow
• The sewer overow connection is above the normal liquid level and will normally
overow while washing vehicles.
• The sewer connection should slope downward to the main sewer line.
• There must be a backow preventer installed between the reclaim tanks
and the main sewer line to prevent sewage from entering the reclaim tanks.
Low Level Float Switch
• PurWater will supply one “Normally Closed” two-wire (yellow oat) level switch,
(Float is not required in standard underground setups but highly recommended.)
• The oat should be wired into a water-tight junction box within the last reclaim tank
and wired through the 1” conduit to the PurWater unit in the equipment room.
• The oat should be installed a minimum of 12” above the bottom of the check
valve when the oat is in the down position.
Misc. Items - Reclaim Tank Plumbing
• Piping and conduit materials should be PVC. PurWater recommends using
schedule 80 pipe as it is more durable than schedule 40.
• All piping to/from the PurWater Unit should be accessible from a manway for
frequent maintenance and troubleshooting.
• A spare or “back-up” secondary suction line is shown on standard drawings. Do
not overlook installing a back up suction line.
• All oor drains emptying into the reclaim tanks should be piped to go below the
water level within the tanks. This prevents any gas from backing up through the
line into the bay or the equipment room. This is especially important for ozone
units.
• The following should not be piped into the reclaim system: Domestic sewer
lines (sinks/toilets), regeneration from softeners, blowdown from compressors or
boilers, drains from service/ detail bays / areas where tire shine is applied.
• If self serve bays are to be piped into the reclaim tanks, a separate reclaim tank
should be used. Contact PurWater for details.
Important Note: Vent pipes from reclaim tanking should not terminate in the
equipment room oor or in the wash bay. Vents (typically) are above the water
line in the reclaim tank(s) and odors or possibly Ozone will exit the vents.
Any venting in the equipment room or wash bay should terminate outside -
typically at roof level to outside air.
Tanking Details