Red Arrow HTLEDCM User manual

Ceiling Mount LED
Exit Sign
Installation Instructions p.1
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
T: 0800 195 0006 F: 0870 043 3946
For models: HTLEDCM
Specification
• Ceiling Mount LED Exit Sign
• 240V
• 2W
• 13pcs of SMD 2835 White LEDs
• 40-50 Lumen output
• 2.4V 900mAh Ni-Cd Battery
• 1 Year guarantee
• IP20
This installation must be carried out by an electrician.
Please read these instructions carefully before installation.
Leave a copy for the user/maintenance engineer for future reference.
Structure Diagram
1. Indication light for charging.
2. Indication light for main function and error.
3. Indication light for mains power.
4. Test switch.
Terminal Block Instruction
L. AC220V connect the live wire
E. Connect the earth wire
N. AC220V neutral wire
Brief Introduction
This product is suitable for use in buildings such as hotels,
restaurants, supermarkets and other public buildings with fire
protection systems. It can be used to indicate directions for an
exit or passage as well as to indicate storing locations of fire
safety products and dangerous materials. It can also be used
for emergency evacuation or fire protection.
Functions and Features
This product is made with high quality LEDs, which features
clear soft light, less power consumption and long working
life expectancy. As a result, it is regarded as an upgraded
replacement of normal exit lights with fluorescent tubes. It
is a continuous working emergency evacuation indication
light, assemblied with fully sealed nickel cadmium battery
and good electronic components. Its circuit has a function of
over charge and over discharge protection which can protect
the battery from damage and extend its lifetime greatly by
preventing the voltage from dropping to the limited value
when discharging.
Operation
1. When this product is connected to the mains power supply,
the green mains indicator and the red charging indicator
automatically turn on. When the light is fully charged, the
luminaire will light normally, while the red indicator
automatically turns off. Press the test switch, the luminaire
will flash for a short time and will remain on if it is
working correctly.
2. When the AC power is suddenly shutdown, the luminaire
remains on. Press the test switch for about one second, the
luminaire turns off. Press the test switch for half second,
the luminaire turns on.

Ceiling Mount LED
Exit Sign
Installation Instructions p.2
For models: HTLEDCM
Notes
1. Before operation please check if the voltage of mains supply is the same as the input voltage of this product. This product
has a nickel-cadmium battery installed. It is required to be charged for 18 hours before first operation to ensure the
emergency circuit works correctly.
2. Only use a fuse with the same specification (1.0A) for replacement.
3. If the yellow indicator is on during normal operation, it means the light has a malfunction or error and needs to be
repaired immediately.
4. Long storage time of this product will shorten its battery life. Therefore, it is strongly recommended to discharge and
recharge this product at least once every three months if it is not regularly used. It also needs to be discharged once every
six months even if it is regularly used. The battery installed needs to be replaced when the discharge time is less than 50%
of the rated time. Please note the size, the pole, the voltage and the capacity of the replaced battery, this must be the same
as the installed battery.
5. Period of guarantee on this product is within 1 year from the date of purchase. Guarantee will be void if the housing of
this product is removed without our permission.
ONCE A MONTH
Each unit should be energised from it’s battery for about 30 seconds by simulation of a failure of the normal lighting supply,
to ensure the lamp operates in the emergency condition.
TWICE A YEAR
Each unit should be energised from it’s battery for a continous period of at least one hour.
AFTER THREE YEARS & EACH SUBSEQUENT YEAR
Each unit should be energised for their 3 hours.
T: 0800 195 0006 F: 0870 043 3946
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS

Ceiling Mount LED
Exit Sign
Installation Instructions p.3
For models: HTLEDCM
Month Test Year 1 Year 2 Year 3 Year 4 Year 5
signed date signed date signed date signed date signed date
1Functional
2Functional
3 Functional
4 Functional
5 Functional
6 1 hour
7 Functional
8 Functional
9 Functional
10 Functional
11 Functional
12 1 hour
3 hour
T: 0800 195 0006 F: 0870 043 3946
Guarantee
This product is guaranteed for a period of 1 year from the date of purchase. The guarantee is invalid in the case of improper use, tampering, removal of the Q.C. date label, installation in
an improper working environment or installation not according to the current edition of the I.E.E. Wiring Regulations (BS7671). The guarantee is also invalidated if the luminaire has
been Mega tested. Should this product fail during the guarantee period it will be replaced free of charge, subject to correct installation and return of the faulty unit. We do not accept
responsibility for any installation costs associated with the replacement of this product. We reserve the right to alter specifications without prior notice.
Product complies with
all relevant European
standards
Product is suitable for
mounting on flammable
material
F
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
Table of contents