PAGE 12 of 41 HG-1-1401A GAS-FIRED HEATER
© SAMUEL JACKSON, INCORPORATED 2005 ALL RIGHTS RESERVED
* ERROR 130
GAS LOW PRESSURE SWITCH FAILED TO OPEN: The gas low pressure switch is not
responding as it should in normal operation. The PLC performs an automatic check of
the heater's switches and safety devices each time the burner is started. One of these
checks is the Gas Low Pressure Switch (GLPS). If this switch is closed when it should
be open, the PLC will not permit the burner to start.
Possible causes of this abnormal operation of GLPS are:
(1) SSOV is malfunctioning and is open, maintaining gas pressure on GLPS at all times.
(2) the GLPS switch is out of adjustment. GLPS should close above 1.5 PSI.
(3) GLPS has been tampered with or bypassed electrically.
(4) Excessively high static pressure within the combustion chamber.
(5) The low fire gas valve is closed off too far to allow gas to bleed off when gas is
evacuated from the gas train by the Pilot Valve (PV) during the startup tests.
If the operator is aware of the safety issues involved in bypassing the function of this
switch, a software bypass is available for emergency operation. The passcode for this
bypass is described in the footnote for this section.
To check GLPS, run the TESTS program step for Gas Low Pressure and then turn the
local START-STOP selector switch to "-". This opens the Pilot Valve (PV). This
evacuates the gas pressure cavity in the gas train and the gas pressure gauge should read 0
PSI.
ERROR 131
USER SPECIFIED TIME FOR SHUTDOWN: Some countries require that gas-fired
combustion products turn off once every 24 hours as a safety measure. To accommodate
operators that need to comply with this regulation, ERROR 131 will force the heater to
shut down once a day at a user defined time. This error will only occur if the 24 Hour
Shutdown routine is enabled in the SETUP program. This error can be disabled in the
SETUP program at any time. See the SETUP EXPLANATION section for more
information.
ERROR 134
CHECK GAS SUPPLY AND OPERATION OF SSOV: Gas pressure is tested when the
heater is started. ERROR 134 occurs when the GLPS switch does not close with this gas
pressure. Possible causes are low gas pressure, a defective SSOV valve actuator that
prevents gas from reaching the GLPS switch, or a maladjusted GLPS switch. If upstream
gas pressure gauges indicate that gas pressure is sufficient (6 PSI before the regulator
should be minimum), suspect the SSOV valve actuator. GLPS switches are normally not
a problem and should not be adjusted unless suggested by the factory.
ERROR 136
GAS VALVE LEAK, UPSTREAM: This is a serious ERROR caused by a leak in the first
SSOV valve. This is the "upstream" gas valve. The test program may be run to determine
the severity of the leak. See the TESTS program for Gas Low Pressure. A leak in the
first SSOV valve is usually caused by dirt or other contaminants on the rubber seat of the
valve. This can be easily cleaned by removal of the lower housing of the valve (with the
gas supply turned off). Contact the factory for technical assistance if required.