TEST SEQUENCE EPLANATION
-2-
STEP
3
--
The digital temperature controlle
this opportunity to check its configuration
configurationand tuning is standard). In a fe
full
ouput, the local start-stop switch can
be
drive the motor to the open position. Center
it
closed. Press RESET to proceed.
trol station is now energized. Take
as
not yet been configured (factory
r
the digital controller has increasedto
modulating motor. Turn to START to
it
in
position. Turn to STOP to drive
STEP
4
--
The local start-stop switch is now used
t
for valve leakage and adjust the ga
pilotvalve P1, admitting gas pressur
Input 6 should turn on at about
1
psi.
valvesclosed several minutes to
see
downstreamvalves, P2 a
pressurefrom the cavity.
build
up.
This tells us that the upstream
The operating program will perform simi
reasonelectrical power must be sup
each shutdown.
r presence of gas, adjust its pressure, test
,
if
necessary. The START position opens
P1 and P2. Slowly pressurizethe cavity.
should be between
3
and 4 psi. Leave the
does not leak off. This tells us that the
urn switch to the STOP position to bleed
ral minutesto see that the pressure does not
safety shut-off valve SSOVl, are not leaking.
s
every time the heater is shut down. This is one
tinuously, or at least for 15 minutes after
START
FAN
and pressRESET to proceedto Step
5.
STEP
5
--
The heater's PLC will open valves P1 and P2 for
5
seconds to
fill
the pipe to the burner
with gas.
It
will then automaticallystep to
6.
STEP
6
--
This step requiresthe fan to run for
15
seconds to purge the burner of any combustible
gas. It then automaticallysteps to
7.
STEP
7
--
The local start-stop switch is now used to test the ignition transformers. Turning the switchto
STARTturns on the ignition transformer IGT.
If
the gin is quiet, you can hear the spark.
If
there is
difficulty, check the spark plug electrode gap at 1/16 to 1/8 (1.5 to
3
mm). Hold the IGT on for
two
secondswhile observing the flame light on the sequence panel.
If
the flame light turns on,
it
means that
there is electrical interference between the spark plug wire and the flame electrode wire. They should be
run to the burner
in
separate conduits to avoid such interference. Since the operating program makes a
similar test beforeeach ignition, the burner will not operate untilthis problem is corrected.
Press RESET to proceed.
STEP
8
--
This step is the trial for ignition and only lasts 10 seconds. During this time, adjust the small
gas cock between P1 and P2. Start with it closed, and slowly open
it
until the burner ignites. Adjust it for
the lowest flame possible, yet high enough for dependable ignition.
As
soon as the burner ignites, the
programsteps to
9.
STEP
9
--
The burner should now operate normally, with TCV free to modulate the flame up to high
output. Make sure that the temperature controller gives the proper 4-20 mA signal to control the
modulatingmotor. The burner will stop when either STOP is operated, air flow fails, RESET is pressed, or
on flame failure. To exit the test program, kill power or press RESET and turn the local STOP switch left
momentarily. The STATUS light should stop blinking. To operate the burner normally, operate either
START switch.
IIIOCTEX
VERSION
2.0
911017