NBS – Fan coil unit
INSTALLATION, MOUNTING AND MAINTENANCE
Identification of the delivered model
Construction subject to change.
No return possible. Version: 03.03.21 | Page 5
STORAGE
If the device is not installed immediately after its reception, it
must be stored according to the following instructions:
--- The device must be stored at a dry, clean, safe location
where no damage to the device can occur, i.e., outside
corrosive atmospheric influences.
--- Leave the protections attached ex works (film, tapes,
pallets, etc.) on the device, unless they have already been
removed beforehand.
--- Cover the device with tarpaulins, in order to protect it
from dust, moisture and extreme temperatures.
--- Rotate the fan rotor at regular intervals.
--- Protect the electric components adequately. In case of
storage over a prolonged period of time, remove the
electric unit and store it at a dry location.
--- Entries, openings and pipes must be hermetically sealed
with dust caps.
MOUNTING POSITION
The devices must not be installed in places with extreme
moisture (e.g. laundries or swimming pools), with high dust
formation, outdoors or in places subject to explosion hazards.
For correct installation, the following instructions must be
followed:
--- Make sure that places that are intended as openings for
air admission and air discharge are free of pipes, electric
cables, crossbeams, stands, etc.
--- Install the unit at a site that has good air quality.
--- Make sure that wall and ceiling correspond to the weight
of the device and also allow correct mounting of the
fastening elements.
--- Make sure that there is sufficient clearance distance to
the wall and no obstacles are present on the outside of
the wall that could impair optimum air circulation (plants,
furniture, curtains, etc.).
--- Install the device such that the air flow is not directed
directly at persons staying there.
--- The installation site must have sufficient space and the
necessary resources for carrying out mounting and
maintenance activities of all device components.
Recommended size for inspection opening (mm)
-100-1 880 x 915
-100-2 1350 x 915
-100-3 1860 x 915
-150-1 1074 x 1099
-150-2 1574 x 1099
-150-3 2024 x 1099