Secutron MRI-4001 User manual

LT-6135SEC rev 0 2/3/23
1
25 Interchange way, Vaughan Ontario. L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113
Web: www.secutron.com
ABOUT THIS MANUAL
This manual is included as a quick reference for installation. For further
information on the use of this device with a FACP, please refer to the
panel’s manual.
Note: This manual should be left with the owner/operator of this
equipment.
DETECTOR BASE DESCRIPTION
The MRI-4001 and MRI-4002 bases are used to interface MRI-4000
series detectors to the SLC line and remote devices. The base can be
wired and secured to a back-box during building construction, allowing the
detector to be installed later, when premises become free of dust and
other contaminants. The MRI-4001 and MRI-4002 both have a set of
mounting holes covered by the detector head. On the MRI-4001, these
are used to mount the base to single gang boxes, 3.5" octagonal boxes,
and 4" octagonal boxes. On the MRI-4002, the holes are used to mount
the base to 3.5" octagonal boxes. The MRI-4001 has an extra set of outer
holes, covered by a removable ring, for 4" square boxes (see figure 2).
When the base is secured to the box, the ring is placed back to cover the
mounting screws heads. A breakable flat tab in the center of the base can
be cut and inserted in the base outer edge then pen marking or a label can
then be used to identify the device.
Before installing this device please thoroughly read this manual and refer
to the applicable codes for guidance on location, spacing and acceptable
use. Also seek guidance from the compatible control panel instructions for
the device operation modes and the configuration requirements.
Note: If the detector is used with the remote indicator, then the voltage
value of the detector must be at least 18V as the indicators do not operate
below 18V.
SPECIFICATIONS
MRI-4001 Dimensions: 6” Diameter, 5/8” Height
MRI-4002 Dimensions: 4” Diameter, 5/8” Height
Wiring range on all terminals: 22 to 12 AWG
FIGURE 1 BASE WIRING
INSTALLATION
The MRI-4001 may be installed over a 4" square, 4" octagonal, 3.5"
octagonal, or single gang box. The MRI-4002 may be installed over a 3.5"
octagonal box. The mounting may be performed on either the ceiling or
the wall. SLC line and remote output connections for the MRI-4001/4002
base are show in figure 1. A twisted pair cable should be used for the SLC
line. If a shielded cabled is used, connect the shields to the proper
terminal on the base. Do not connect shields to earth ground. If a ground
continuity wire is required by the local code, it should be a separate
conductor. Please note that shielded cables may reduce the SLC loop
length that can be achieved due to their high capacitance.
A breakaway tab inside the base can be inserted in the outer rim of the
base to visibly identify each detector with their address. See figures 1, 3,
and 5. The detector can then be placed on the base using the following
steps:
1. Position the detector centrally on its adapter base ensuring it is level.
2. Rotate clockwise applying gentle pressure. The detector will drop
into its keyed location.
3. Continue to rotate clockwise a few degrees until the detector has fully
engaged in the adapter base.
4. When the detector is firmly engaged, check the alignment of the
raised reference marks on the detector and on the base (figure 4).
See page 2 for instructions on using the anti-tamper feature.
IMPORTANT NOTE ON BASE INSTALLATION
Disconnect loop power before installing the base.
When duplicate terminals are not provided to facilitate monitoring of the
installation wiring connections, and there is no provision to prevent looping
an unbroken wire around or under a terminal, the word "CAUTION" and
the following or equivalent text in letters not less than 2.38 mm (3/32 inch)
high shall be included on the installation drawing: "FOR SYSTEM
MONITORING - FOR TERMINALS "Loop out (+)" AND "Remote Device
(+)", DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE MONITORING OF CONNECTIONS.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MRI-4001 / 4002 DETECTOR BASE
LT-6135SEC rev 0 2/3/23
2
FIGURE 2 BASE MOUNTING:
FIGURE 3 HEAD MOUNTING:
3 1/2" OCTOGONAL BOX
SINGLE GANG BOX
OR 3 1/2” OCTAGONAL BOX
OR 4” OCTAGONAL BOX
4” SQUARE BOX
(HOLES COVERED BY
PLASTIC RING)
BREAKAWAY
ADDRESS TAB
TURN CLOCKWISE TO
LOCK PLASTIC RING
ADDRESS TAB
TURN COUNTERCLOCKWISE
TO UNLOCK PLASTIC RING
FIGURE 4 ALIGNMENT MARKS:
FIGURE 5 TO LOCK THE DETECTOR ON THE
BASE:
1. Remove the small breakaway locking tab inside the base
(Figure 5).
2. Attach the detector to the base as described in
“INSTALLATION” on page 1. You will hear a click when the base
is locked in place.
FIGURE 6 TO REMOVE A LOCKED DETECTOR:
1. Insert a thin flathead screwdriver in the slot in the base.
2. Use the screwdriver as a lever to release the locking
mechanism by moving the handle in the direction shown in
Figure 6.
3. While holding the screwdriver in place, turn the detector
counter-clockwise to remove it.
REMOVE BREAKAWAY
LOCKING TAB
1
2
33
2
1

This manual suits for next models

1

Popular Rack & Stand manuals by other brands

Auton AR 19.5-10 installation manual

Auton

Auton AR 19.5-10 installation manual

Jefferson JEFBGSSTD user manual

Jefferson

Jefferson JEFBGSSTD user manual

pleasant hearth LS938-144SC manual

pleasant hearth

pleasant hearth LS938-144SC manual

Vu Ryte VUR 79GR installation instructions

Vu Ryte

Vu Ryte VUR 79GR installation instructions

Victor High Rise DC350 Assembly instructions

Victor

Victor High Rise DC350 Assembly instructions

Clas Ohlson 38-4242 instruction manual

Clas Ohlson

Clas Ohlson 38-4242 instruction manual

Vivo STAND-V100HU instruction manual

Vivo

Vivo STAND-V100HU instruction manual

AUDIOLINE LDT35-T01 installation manual

AUDIOLINE

AUDIOLINE LDT35-T01 installation manual

Monoprice 34303 installation manual

Monoprice

Monoprice 34303 installation manual

Metro DataVac CBC11C Assembly instructions

Metro DataVac

Metro DataVac CBC11C Assembly instructions

ricoo TS0311 Assembly instructions

ricoo

ricoo TS0311 Assembly instructions

iTOOLco REAL BIG JACKS user guide

iTOOLco

iTOOLco REAL BIG JACKS user guide

Sharp AN-CM270 installation instructions

Sharp

Sharp AN-CM270 installation instructions

Axis T94N01D manual

Axis

Axis T94N01D manual

Ultimate Support Sunken 6 instructions

Ultimate Support

Ultimate Support Sunken 6 instructions

Mount-It! MI-2757 installation manual

Mount-It!

Mount-It! MI-2757 installation manual

peerless-AV DS-LEDFLAAF-3X3 installation instructions

peerless-AV

peerless-AV DS-LEDFLAAF-3X3 installation instructions

Cloudinary 56402 Assembly instructions

Cloudinary

Cloudinary 56402 Assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.