SEELEY INTERNATIONAL Climate Wizard Multi-Magic CW-H10 Owner's manual

INSTALLATION, OPERATION & MAINTENANCE
(English) (CW-H15)
Climate Wizard – CW-H10, CW-H15, CW-H15S
Indirect Evaporative Cooler

TABLE OF CONTENTS Page
Number
MAINTENANCE NOTE
SAFETY
COOLER VIEWS
COOLER SPECIFICATIONS
COOLER CONTENTS
INSTALLATION
COMMISSIONING
OPERATING INSTRUCTIONS
USER MAINTENANCE INSTRUCTIONS
MAINTENANCE SCHEDULE
TROUBLE SHOOTING
INSTALLATION CHECKLIST
.......................................................................................................................................................................................1
...............................................................................................................................................................................................................2
.................................................................................................................................................................................................3
...............................................................................................................................................................................5
.........................................................................................................................................................................................6
Cooler Location....................................................................................................................................................................................................7
Mounting/Support ................................................................................................................................................................................................7
Unpacking the Cooler ..........................................................................................................................................................................................7
Moving the Cooler................................................................................................................................................................................................7
Lifting the Cooler..................................................................................................................................................................................................7
Vibration Isolation ................................................................................................................................................................................................7
Drip-tray ...............................................................................................................................................................................................................7
Duct Connections ................................................................................................................................................................................................8
Exhaust Duct Requirements ................................................................................................................................................................................8
Exhaust Transition Assembly...............................................................................................................................................................................8
Inlet Air Filter Assembly .......................................................................................................................................................................................9
Fitting the Inlet Air Filters .....................................................................................................................................................................................10
Electrical Supply Installation (Australia, Europe: 3 Phase 380-415V) .................................................................................................................11
Electrical Supply Installation (USA: 3 Phase 440-480V) .....................................................................................................................................12
Electrical Supply Installation (USA: 3 Phase 200-240V) .....................................................................................................................................13
Electrical Supply Installation (USA: 1 Phase 200-240V) .....................................................................................................................................14
Water Supply Installation .....................................................................................................................................................................................15
Drain Installation ..................................................................................................................................................................................................16
Control Schemes .................................................................................................................................................................................................17
Wall Control Installation .......................................................................................................................................................................................21
Climate Wizard Supercool Installation .................................................................................................................................................................22
Climate Wizard Cooling Applications ...................................................................................................................................................................23
Setting the Air Discharge Damper .......................................................................................................................................................................23
Turning the Cooler On .........................................................................................................................................................................................25
Check Fan Operation ....................................................................................................................................................................................25
Check Pump Operation .................................................................................................................................................................................25
Check Drain Operation..................................................................................................................................................................................25
Clean Up the Site.................................................................................................................................................................................................25
Show the Customer Their New Cooler ................................................................................................................................................................25
Wall Control .........................................................................................................................................................................................................26
Quarterly Inspection Procedures .........................................................................................................................................................................28
Cleaning the Reservoir (Tank) .............................................................................................................................................................................28
Cleaning Pump Strainers & Impellors..................................................................................................................................................................29
Changing Pumps .................................................................................................................................................................................................29
Cleaning or Replacing the Chlorinator.................................................................................................................................................................29
Cleaning or Replacing the Water Management Probe ........................................................................................................................................30
Replacing the Drain Valve ...................................................................................................................................................................................30
Replacing the Solenoid Valve ..............................................................................................................................................................................31
Replacing the Inlet Air Filters...............................................................................................................................................................................31
Changing Cooler Cores .......................................................................................................................................................................................33
Changing Cooler Chillcel (CW-H15S only) ..........................................................................................................................................................35
Operating and Fault Code Diagnosis...................................................................................................................................................................36
.............................................................................................................................................................................38
.......................................................................................................................................................................................41
.............................................................................................................................................................................42
i
CW-H10, CW-H15, CW-H15S

MAINTENANCE NOTE
IMPORTANT
VERY IMPORTANT
ANY FAILURE TO CARRY OUT THE REQUIRED MAINTENANCE AND SERVICING, AND
ANY FAILURE TO FILL OUT THE MAINTENANCE SCHEDULE, WILL VOID YOUR WARRANTY.
As with any product that has moving parts or is subject to wear and tear, it is that you
maintain your cooler and have it regularly serviced. It is a condition of warranty cover for your cooler that you
comply with all of the maintenance and service requirements set out in this Manual. Compliance with these
requirements will prolong the life of your cooler. Further, it is also a condition of warranty cover that each item in
the Maintenance Schedule in the Manual is filled out (by signing and dating it in the places indicated) when the
item is completed.
SEELEY INTERNATIONAL – INSTALLATION MANUAL 1

SAFETY
READ AND SAVE THESE INSTRUCTIONS
EMPLOYER AND EMPLOYEE RESPONSIBILITIES
WARNING - TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO OTHER PERSONS, OBSERVE THE FOLLOWING:
Seeley International provides the following information as a guide to contractors and employees to assist in minimizing risk while
working at height.
Installer and Maintenance Contractors
Risk Assessment
Some points to consider:
The installation and maintenance of air conditioning units at height has the potential to create Occupational Health and Safety issues for those
involved. Installers are advised to ensure they are familiar with the relevant State and Federal legislation, such as Acts, Regulations, approved
Codes of Practice and Standards, which offer practical guidance on these health and safety issues. Compliance with these regulations will
require appropriate work practices, equipment, training and qualifications of workers.
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
2. Before servicing or cleaning the unit, switch power off at service panel and lock the service disconnecting means to prevent power from
being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device,
such as a tag to the service panel.
3. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including
fire-rated construction.
4. When cutting or drilling into walls or ceilings, do not damage electrical wiring and other hidden utilities.
5. Ducted fans must always be vented to the outdoors.
6. Do not use this fan with any solid-state speed control device.
A risk assessment is an essential element that should be conducted before the commencement of work, to identify and eliminate the risk of falls
or to minimize these risks by implementing control measures.
A risk assessment of all hazardous tasks is required before commencing any work, and may be required under legislation.
There is no need for this to be a complicated process, it just is a matter of looking at the job to be done and considering what action(s) are
necessary so the person doing the job does not injure themselves.
This should be considered in terms of:
What are the chances of an incident happening?
What could the possible consequence be?
What can you do to reduce, or better still, completely get rid of the risk?
What is the best and safest access to the roof and working areas?
If a worker is alone, who knows they are there and if they get into difficulty, how can they summon help? (Call some one on the ground?
Mobile phone? etc.)
What condition is the roof in? Should the trusses, underside or surface be checked?
Does the worker have appropriate foot wear?
Are all power cables/extension leads safe and appropriately rated?
Are all ladders, tools and equipment suitable in good condition?
Where ladders are to be used, is there a firm, stable base for them to stand on? Can they be tied or secured in some way at the top? Is the
top of the ladder clear of electricity supply cables?
Is there a roof anchor to attach a harness and lanyard to? If so, instruction should be issued for the use of an approved harness or only
suitably trained people used.
Are all tools and materials being used, prevented from slipping and falling onto a person at ground level? Is the area below the work area
suitably protected to prevent persons walking in this area?
Does the work schedule take into account weather conditions, allowing for work to be suspended in high winds, thunder storms/lightning or
other types of weather giving wet, slippery surfaces?
Is there an on-going safety check system of harnesses, ropes, ladders and access/lifting equipment and where they exist on roofs, anchor
points before the commencement of work?
Is there a system which prevents employees from working on roofs if they are unwell or under the influence of drugs or alcohol?
Are there any special conditions i.e. excessive roof pitch, limited ground area, fragile roof, electrical power lines?
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
OTHER IMPORTANT REQUIREMENTS
!
!
!
Never force parts to fit because all parts are designed to fit together easily without undue force.
Never drill any holes in the primary base surface or side walls of the bottom tank (reservoir) of the cooler.
Check the proposed cooler location, to ensure that it is structurally capable of supporting the weight of the cooler, or provide an adequate
alternate load bearing structure.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
2
CW-H10, CW-H15, CW-H15S

COOLER VIEWS
ISOMETRIC
1610 mm
(63.4” )
TOP
CW-H15 & CW-H15S
1825mm (71.9”)
CW-H10
1230mm (48.4”)
+20
-0
+0.75”
- 0
SIDE
BOTTOM
1990mm (78.3”)
(Control Box Handle)
CW-H10 = 2270mm (89.5”)
CW-H15, CW-H15S = 2325mm (91.5")
(Air Filter)
Mounting Base
1300mm (51.2”)
400mm
(15.7”)
Drain Connection
120mm
(4.7”)
120mm
(4.7”)
400mm
(15.7”)
CW-H10
= 350mm (13.8”)
CW-H10
= 350mm (13.8”)
CW-H10
= 400mm (15.7”)
CW-H15 & CW-H15S
= 550mm (21.7”)
CW-H15 & CW-H15S
= 550mm (21.7”)
CW-H15 & CW-H15S
= 600mm (23.6”)
400mm
(15.7”)
Outlet centreline
667mm (26.2”)
Outlet duct
500 x 500mm
(19.7 x 19.7”)
Exhaust duct
500 x 500mm
(19.7 x 19.7”)
REAR
Mounting Base
1205mm (47.5”)CW-H10 =
CW-H15 = 1800mm (70.9”)
CW-H15S = 1800mm (70.9”)
Mounting Holes
1185mm (46.6”)CW-H10 =
CW-H15 = 1780mm (70.1”)
CW-H15S = 1780mm (70.1”)
Hole size Ø10 (0.4")
Mounting Holes
1280mm (50.4”)
CW-H15 views shown
SEELEY INTERNATIONAL –INSTALLATION MANUAL 3

INDEX DESCRIPTION
1 AIR FILTER ASSEMBLY (Standard, supplied with Climate Wizard)
2 ELECTRONICS BOX
3 INLET SAFETY GRILLE ASSEMBLY (Optional, mandatory if Inlet Filter not used)
4 INLET TRANSITION ASSEMBLY
5 WATER MANAGER COMPONENTS
6 FAN ASSEMBLY
7 TANK & CORE ASSEMBLY
8 SPREADER ASSEMBLY
9 OUTLET TRANSITION ASSEMBLY
10 DAMPER ASSEMBLY
11 OUTER PANELS (RH SIDE)
12 OUTER PANELS (LH SIDE)
13 EXHAUST TRANSITION ASSEMBLY
14 BASE FRAME ASSEMBLY
15 CHILLCEL SPREADER ASSEMBLY (CW-H15S only)
16 CHILLCEL (CW-H15S only)
CW-H15S view shown
COOLER VIEWS
4
CW-H10, CW-H15, CW-H15S

COOLER SPECIFICATIONS
ACCESS COVER
FOR DRAIN VALVE
CONNECTION
ELECTRICAL SUPPLY
TERMINATIONS MADE
INSIDE CONTROL BOX
WATER CONNECTION
1/2”(15mm) BSP (Aus/Eur)
½" NPT (USA)
(Water connection may
require an adaptor to
suit local pipe sizes)
806mm
(31.7”)
610mm (24”)
250mm (9.8”)
*910mm
452mm (17.8”)
660mm (26”)
200mm
(7.9”)
500mm 500mm
CW-H10
CW-H15
664mm (26.4")
364mm (14.3”)
120mm (4.7”) Drain Outlet position
120mm
(4.7”)
180mm
(7.1”)
500
410
(16.1”) (19.7”)
(19.7”) (19.7”)(19.7”)
*(35.8”)
500mm
493
410
+20
-0
*Overall height can vary as shown due to manufacturing
and material tolerances.
(16.1”)
+0.75”
- 0
(19.4”)
SEELEY INTERNATIONAL –INSTALLATION MANUAL 5
SPECIFICATIONS
CW-H10
CW-H15
CW-H15S
Electrical rating:
Refer to the below distinct models for the voltage, frequency rating required.
Aus/Europe
USA
3N~, 380-415V, 50Hz,
3~, 440-480V, 60Hz, 3 amps, 8.5 MCA, 15 MOPD
1~, 200-240V, 60Hz, 8 amps, 11 MCA, 15 MOPD
3 amps
3N~, 380-415V, 50Hz,
3~, 440-480V, 60Hz, 3 amps, 8.5 MCA, 15 MOPD
3~, 200-240V, 60Hz, 6 amps, 14.5 MCA, 20
MOPD
1~, 200-240V, 60Hz, 8 amps, 11.5 MCA, 15
MOPD
3 amps
3N~, 380-415V, 50Hz,
3~, 440-480V, 60Hz, 3 amps, 8.5 MCA, 15 MOPD
3~, 200-240V, 60Hz, 6 amps, 14.5 MCA, 20
MOPD
1~, 200-240V, 60Hz, 8 amps, 11.5 MCA, 15
MOPD
3 amps
Water Supply:
½”BSP (Aus/Eur), ½”NPT (USA) male
connection
min 100 kPa, max 800 kPa, 20 L/min
(min 15psi, max 115psi, 5.3gal/min)
½”BSP (Aus/Eur), ½”NPT (USA) male
connection
min 100 kPa, max 800 kPa, 20 L/min
(min 15psi, max 115psi, 5.3gal/min)
½”BSP (Aus/Eur), ½”NPT (USA) male
connection
min 100 kPa, max 800 kPa, 20 L/min
(min 15psi, max 115psi, 5.3gal/min)
Max. operating
temperature:
55°C (131°F) ambient (shade)
55°C (131°F) ambient (shade)
55°C (131°F) ambient (shade)
Aiflow:
800 L/sec - at 0 - 140Pa
(1695cfm - at 0 - 0.56" static pressure water gauge)
1100 L/sec - at 0 - 175 Pa
(1695cfm - at 0 - 0.70" static pressure water gauge)
1,700 L/s - at 0 - 80 Pa
(3,600 cfm - at 0 - 0.32" st )
1,100 L/s - at 0 - 175 Pa
(2330cfm - at 0 - 0.70" st
atic pressure water gauge
atic pressure water gauge)
Winery configuration:
Sound Pressure:
73.5 dB(A) at 1m on centreline from discharge
79 dB(A) at 1 m on centreline from discharge
79 dB(A) at 1 m on centreline from discharge
Drain Valve:
1½”(40mm) BSP male outlet (elbow) SI 12Vdc,
vertical, electric drive
1½”(40mm) BSP male outlet (elbow) SI 12Vdc,
vertical, electric drive
1½”(40mm) BSP male outlet (elbow) SI 12Vdc,
vertical, electric drive
Shipping -
dimensions: (Air filter
shipped sparately)
1985mm L x 1230mm W x 1280mm H (78.1”L x
48.4”W x 46.1”H)
2000 L x 2050mm W x 1280mm H (78.1”L x
71.8”W x 46.1”H)
2000 L x 2050mm W x 1280mm H (78.1”L x
71.8”W x 46.1”H)
Shipping weight *
230 kg (505 lb)
275 kg (605 lb)
285 kg (628 lb)
Operating Weight **
255 kg (560 lb)
305 kg (670lb)
320 kg (705 lb)
* includes pallet, does not include air filter & cowling assembly weight
** includes air filter and cowling assembly weight

COOLER CONTENTS
COOLER INSTALLATION KIT COMPONENTS
ITEM PART No
1
2
3
4
5
6A
6B
6C
7
8
9
10
834245
114279
859736
879239
879345
584331
861883
593104
861593
805306
804644
805597
-
120102
QTY
1
1
1
1
1
1
1
1
2
2
42
1
1*
1*
1*
DESCRIPTION
CONTROL CABLE 20m (65’)
1
ITEM 1. ITEM 2 ITEM 3 ITEM 4
ITEM 6A ITEM 7
ITEM 10ITEM 6C
ITEM 6B ITEM 9
ITEM 8
ITEM 5
WALL CONTROL
INSTRUCTIONS - INSTALLATION, SERVICE & OPERATION
WARRANTY CARD - AUSTRALIA
WARRANTY CARD - USA
WALL CONTROL MOUNT PLATE
ADAPTOR DRAIN ELBOW
ADAPTOR, DRAIN 32/20mm
NUT, PIPE FITTING 1.5" BSP
SCREW PAN PHIL 6ABX1”ZNP
WALL PLUG YELLOW 5mm (3/16”)
SCREW 8AB x ½" PAN PHILL SS
HANDLE, CONTROL BOX
INLET AIR FILTER ASSY CW-H10 or CW-H15 (See Pg 31)
AIR FILTER COWLING CW-H10 or CW-H15 (See Pg 31)
INLET AIR SAFETY GRILLE (REFER OPTIONAL PARTS)
REPLACEMENT, OPTIONAL or SPARE PART COMPONENTS
ITEM
1
2A
2B
3
4
5
6A
6B
7
8
9A
9B
9C
9D
SEELEY
PART #
094526
095806
094946
094519
094700
094861
094885
094960
093987
094823
094755
116877
114729
114743
114712
094762
094724
094717
094540
094588
094557
094373
094564
094571
094335
094366
093956
093963
094397
094380
093970
094830
094847
094854
094779
094786
094793
094748
094731
115894
115993
116082
117270
117294
115887
134192
134215
120102
875474
094595
DESCRIPTION
CONTROL CABLE 40m (131’)
CONTROL CABLE 20m (65’)
AIR FILTER COWLING - See Page 31
COWLING LOCK - QUARTER TURN
AIR FILTER FRAME - See Page 31
SMARTCARD 113876 CW-H10 - ZA500 MOTOR
SMARTCARD 114125 CW-H10 - EBM500 MOTOR
SMARTCARD 113852 CW-H10 - EBM560 MOTOR
REPLACEMENT AIR FILTERS - See Page 31
SPREADER KIT 1PK CW-H
EXHAUST KIT CW-H10
EXHAUST KIT CW-H15
CONTACTOR ELEC BOX CW-H
TERMINALS ELEC BOX CW-H
(5 x GREY, 2 x GRN/YL, 2 x END, 2 X JUMPER)
RFI FILTER ELEC BOX CW-H
POWER SUPPLY, 12Vdc, CW-H USA
TRANSFORMER, 230-460V, CW-H USA
PANEL DOOR SCREW KIT
PANEL DOOR KIT - CORE
PANEL DOOR KIT - PUMP
24VDC RELAY CW-H15S
CHILLCEL 3x 637x545x150 CW-H15S
EXHAUST LID BRACE
ROOFSTAND 0-10º CW-H10
INLET AIR SAFETY GRILLE (optional)
DRAIN VALVE, 12VDC & ADAPTOR
PUMP, 1.5m (4.92’) LEAD, 230/50
PUMP, 1.5m (4.92’) LEAD, 230/60 USA
WALL CONTROL, MOUNT PLATE & FASTENERS
PCB, BMS INTERFACE
CORE BLOCK CW-H
SOLENOID, WATER INLET - BSP
SOLENOID, WATER INLET - NPT
CHLORINATOR PROBE ASSY
FAN/MOTOR/PCBA KIT CW-H10 AUST
FAN/MOTOR/PCBA KIT CW-H15 AUST
FAN/MOTOR/PCBA KIT CW-H15 USA 460V
FAN/MOTOR KIT CW-H15 USA 230V
PCB, COOLER CONTROL CW-H AUST/EUR
PCB, COOLER CONTROL CW-H USA
WATER LEVEL & SALINITY PROBE
ITEM 3 ITEM 4ITEM 1 ITEM 2 ITEM 6
2
10A
10B
11A
11B
14
13
13C
12
15
18
16A
16B
19A
19B
20
21
22
23
24
25
27
28
29
30
26
17A
17B
17C
17D
17E
17F
17G
17H
17I
17L
17J
17M
17K
17N
ITEM 5
ITEM 9 ITEM 10
ITEM 14
ITEM 12 ITEM 13 ITEM 13C
ROOFSTAND 0-10º CW-H15
ITEM 11
ITEM 16
ITEM 17 ITEM 18
ITEM 20
ITEM 25 ITEM 27ITEM 26 ITEM 28 ITEM 29 ITEM 30
ITEM 19
ITEM 21 ITEM 22 ITEM 23 ITEM 24
ITEM 15
SMARTCARD 113853 CW-H15 - EBM560-RAD MOTOR
SMARTCARD 114132 CW-H15 - ZA560 MOTOR
SMARTCARD 113869 CW-H15 - EBM500 MOTOR
SMARTCARD 113838 CW-H15 - EBM560 MOTOR
SMARTCARD 113859 CW-H15 - EBM560RAD
SMARTCARD 114860 CW-H15 - EBM560RAD HI ALT
SMARTCARD 116458 CW-H15S - EBM560-G2 220-240V 3~
SMARTCARD 116457 CW-H15 - EBM560-G2 220-240V 3~
SMARTCARD CW-H15W 380-480V 3~ WINERY CONVERSION
SMARTCARD 114861 CW-H15S - EBM560RAD
SMARTCARD CW-H15W 220-240V 3~ WINERY CONVERSION
ITEM 7 ITEM 8
INSTALLATION,OPERATION & MAINTENANCE
(English)(CW-H15)
Climate Wizard –CW-H10, CW-H15
IndirectEvaporative Cooler
WARRANTY INFORMATION
DUCTED INDIRECT EVAPORATIVE
AIR COOLER
INTERNATIONAL
6
CW-H10, CW-H15, CW-H15S
9 3 1 2 1 6 8 0 0 1 7 0 8

INSTALLATION
Cooler Location
Check the proposed cooler location, to ensure that it is structurally
capable of supporting the weight of the cooler, or provide an adequate
alternate load bearing structure.
Always locate the cooler where it will receive a plentiful supply of fresh air, in a recess where it may be starved for air or where the air is polluted.
Air exiting the exhaust hood is warm and heavily laden with moisture. Ensure the cooler’s exhaust outlet location will not cause corrosion or damage
to other nearby items.
Allow adequate access to and around the cooler for maintenance. Provision must be made for access to electricity, water supplies and drains.
Do you need to discuss the installation of items like safety anchor points with the customer?
NOT
•Ensure the location is a minimum of:
(10’) from a solid fuel heater flue,
(5’) from a gas flue,
(16’) from a sewer vent
Rear = Min (3.5’) from a wall, at sides
to allow easy access for maintenance and core replacement.
Note:
Do not allow exhaust air to re-circulate into the air intake of the cooler.
3.0m
1.5m
5.0m
1.0m 1.0m (3.5’)
Mounting/Support
Unpacking the Cooler
Moving the Cooler
Lifting the Cooler
Vibration Isolation
Drip-tray
Industry standard support frames can be used with this cooler.
Recommended steel specification:
50 x 50 x 3mm (2”x 2”x 1/8”) RHS Galvanized or Painted
Specific CW-H Roofstands are available for order via Seeley to suit cooler size
and accommodating 5 or 10 degree roof pitches.
CW-H10: 0-10º - P/No. 134192
CW-H15, CW-H15S: 0-10º - P/No. 134215
The cooler will be delivered wrapped in a plastic stretchwrap film which will need to be removed before installation. A small bag of Installation
components along with the exhaust hood sheet metal components can be found under the lid of the main cabinet of the cooler. The lid will need
to be removed and the exhaust transition components assembled and fitted to the lid before re-installing the lid assembly back onto the cooler.
The wall control and communications cable, along with ancillary mount plates, fasteners and drain adaptors will need to be placed aside for later
connection.
The cooler has in-built fork-truck tyne openings in the base for ease of
movement. The openings can also be used with lifting straps or slings
(refer diagram & see below).
The cooler may be lifted either by fork-truck or crane with slings. The method for lifting by crane is by lifting straps through the cooler base fork-
truck tyne openings. Do not attempt to lift using any cabinet features or by retro-fitting lifting lugs. The cabinet may be damaged and/or lift safety
compromised.
It is recommended to use a spreader bar on the straps or slings and/or to protect the upper edges of the cooler with a corner protector beneath
the lifting straps to avoid any damage to the cabinet during the lift.
Waffle pads are recommended to be used under each corner of the cooler. Pad size approx. 200mm (8”) x 200mm (8”). Use industry standard
methods of fixing to the building structure.
When Climate Wizard coolers are installed indoors, or anywhere that water leakage could cause damage, install a corrosion resistant drip tray
under the whole machine. Recommended size:
CW-H10 - 1500w x 1300d x 50h mm (59"w x 51"d x 2"h)
CW-H15, CW-H15S - 1500w x 1900d x 50h mm (59"w x 75"d x 2"h)
Apply silicone sealant between drip-tray and cooler base at every fixing.
CW-H10: A = 1300mm (51.2”) x 1206mm (47.5”)
1300mm x 1800mm (70.9”)
CW-H10, CW-H15 & CW-H15S: B = 50mm min (2”min.)
Angle to match roof pitch
CW-H15 & CW-H15S: A = (51.2”)
Model
CW-H10 230kg (505 lb) 255kg (560 lb)
305kg (670 lb)
320kg (705 lb)
275kg (605 lb)
285kg (628 lb)
CW-H15
CW-H15S
Shipping Weight Operating Weight
1.0m 1.0m
1.0m
(3.5’)(3.5’)
(3.5’)
Min. Fork tyne gap
= 460mm (18.2”)
SEELEY INTERNATIONAL –INSTALLATION MANUAL 7

INSTALLATION
Duct Connections
Exhaust Duct Requirements
Exhaust Transition Assembly
Vibration absorbing flexible connections are recommended for all duct connections to the cooler, for any ducts that are attached to the building
structure. All ducts attached to the flexible connection must be independently supported.
Ensure the exhaust discharge opening is located and oriented in such a way as to avoid exhaust air re-entering the cooler inlet. Exhaust air is
warm and heavily laden with moisture.
when designing the exhaust duct note that the exhaust transition and everything attached to it must be removed whenever the
heat exchanger cores need to be accessed. The weight of the assembly is therefore quite important.
The exhaust transition is supplied in knock-down form; its components are to be found beneath the lid of the cooler after shipping. This requires
the installer to remove the lid of the cooler, remove the components and assemble the Exhaust Transition and fit it to the lid with the supplied
fasteners, fit the Inlet Air Filter or Safety Grille, then refit the Lid/Exhaust assembly back onto the cooler. The flange of the exhaust transition
must be fitted beneath the lid of the cooler. The lid is fitted with a foam seal - ensure the flange sits up firmly against this. Use a high quality
sealant that is neutral cure, flexible and has good UV and weather resistance to seal around the outside of the exhaust transition flange and the
lid (3 below). Where the exhaust transition is installed externally and the exhaust opening is open to the atmosphere,
fit a rain hood (not supplied) over the exhaust opening to prevent unfiltered sunlight or precipitation entering and damaging the core.
Keep rainhood weight to a minimum. Minimum throat radius = 75mm (3"). Where an installation requires extended exhaust ducts, the increase
in static load should not exceed 20 Pa (0.08 in wg).
CW-H15S coolers are supplied with an additional exhaust cap, designed to optimise the airflow and cooling performance of the additional direct
evaporative cooling media. The cap is to be fitted over the top of the exhaust grille, utilising the existing fasteners.
When fitted directly to the exhaust transition, the exhaust opening should be on the same side as the supply air transition.
When fitted to rain hood, the exhaust opening should be on the bottom.
PLEASE NOTE:
PLEASE NOTE: YOU
MUST
Supercool Exhaust Cap.
3. Fit the lid the exhaust transition and assemble.over
Apply sealant to the top of the Exhaust Transition.
1. Remove lid, obtain exhaust transition
and installation components
2. Assemble the exhaust transition
8
CW-H10, CW-H15, CW-H15S
Rain hood specifications
(hood not supplied):-
Min. throat radius =
75mm (3")
Allowable pressure
drop =
20Pa (0.08in wg) max.
Bend Angle =
90°min
Opening =
500mm x 500mm
(19.7"x19.7")
Grille size =
495mm x 495mm
(19.5"x19.5") external
4. Assemble the exhaust grille to the Lid assembly.
(Fit rain hood as required, relocate grille to
rain hood opening)
Relocate exhaust grille and cap
(CW-H15S only) to rain hood if fitted.

INSTALLATION
Inlet Air Filter Assembly
Climate Wizard coolers - use either the Inlet Air Filter Assembly supplied from
the factory or use approved dust filters on the inlet air with a maximum 35 Pa (0.14 in wg) pressure drop for a clean filter. Should the Inlet Air
Filter Assembly not be required an optional Safety Grille is available and be fitted for safety reasons.
To reduce the risk of fire, electric shock, and injury to persons, Climate Wizard coolers must be installed with Filter Assemblies or
Safety Grilles, that are marked to indicate their suitability with this model. Other Filter Assemblies or Safety Grilles cannot be substituted.
The Inlet Air Filter assembly is supplied in separate cartons when shipped with the Climate Wizard. This requires the installer to remove the lid
of the cooler, remove the filters from their shipping position in the frame, fit the filter frame to the cooler, secure the cowling top and sides to the
filter frame and cooler, slide the filters back into the frame and secure the cowling front access panel with the supplied fasteners. Refit the
Lid/Exhaust assembly back onto the cooler, over the flange of the Inlet Filter Cowling.
SHOULD NEVER BE INSTALLED WITHOUT DUST FILTERS
MUST
WARNING:
Fit filter frame to inlet of cooler
Fit the Filter Cowling top and sides
to the Filter Frame and Cooler.
The top lip of the filter cowling (shaded, 3 above) must locate inside the lid of the cooler (refer 4 above), this may require the lid to be unfastened
(if already assembled) and lifted or, alternately, assemble the lid to the cooler after the filter assembly and cowling is fitted. Insert the filters to the
filter frame. Fit the front panel of the cowling onto the cowling assembly.
No. Description
1
2
3
4
5
6
Inlet Air Filter Cowling
Inlet Air Filter Frame
Air Filter - Front
Air Filter - LH (CW-H15 & CW-H15S)
Air Filter - Base
Air Filter - RH
1
4
2
CW-H10
Inlet Air Filter components
123456
3
CW-H15 & CW-H15S
SEELEY INTERNATIONAL –INSTALLATION MANUAL 9

INSTALLATION
Fitting the Inlet Air Filters
When servicing the filters the front plate of the filter cowling must be removed to provide access. To fit the filters into the Air Filter frame, slide
the bottom filter into position into the base of the frame. Slide the side filter(s) into the frame in the same manner. To fit the front filter, locate the
top edge of the filter under the top brackets and lift to engage the filter inside them. Allow the filter to drop, to engage the 2 bottom brackets at
the bottom of the frame.
The Air Filters should be replaced as soon as airflow through the filters is restricted by choking or clogging with dust or contaminants. The
frequency of changing the filter is dependent on the air quality on the site.
Replacement Inlet Air Filters are available from SI Service Agents and Climate Wizard distributors.
Remove screws to dismantle the front
section of the filter cowling, the lid and
sides of the cowling remain attached to
the cooler.
Filters slide into frame channels
(CW-H10 Fit 3 Filters only, omit LH side)
(CW-H15, CW-H15S Fit 4 Filters)
retaining wire is on
the INSIDE of the filter.
NOTE:
To fit the front filter, locate the top edge of the filter under the top brackets and lift to engage the filter inside them. Allow the filter to drop, to
engage the 2 bottom brackets at the bottom of the frame.
10
CW-H10, CW-H15, CW-H15S

INSTALLATION
Electrical Supply Installation
(Australia, Europe - 3PH 380-415V)
PLEASE NOTE! There are specific models for regional specific voltages and frequencies WHICH ARE NOT INTERCHANGEABLE, as
these require differing component configurations that vary according to the supply frequency and voltage. Specifically, the main fan
motor, 3 phase filter, transformer and pump are unique to the voltage/frequency of supply. Please ensure the cooler matches the
electrical requirements shown in the following pages.
Installation of the Cooler must conform to local electrical rules, regulations and standards.
Amps per phase
It is a requirement of Seeley International that all Coolers be wired with a dedicated circuit and circuit breaker to the distribution
board, incorporating an isolation switch in the fixed wiring with all pole disconnection from the mains power in accordance with the
local wiring rules.
Specification : 380 - 415V / 50 Hz / 3 Phase with Neutral / 3
Climate Wizard requires 3-phase Neutral and Earth electrical power. If required, mains isolation switch is to be furnished by the contractor
adjacent to the cooler - if mounting on the cooler cabinet, take care not to puncture the water reservoir. Mains power terminals are provided
inside the electrical cabinet with glands provided for cable entry.
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
SEELEY INTERNATIONAL –INSTALLATION MANUAL 11
MAIN PCB
C1
C2
C3 C4 C5
C6
C7
C8 C9 C10
C11 C11
C13
C13
C10
C12
C12
C4
C17
C16
C15
C14
3 PHASE
FILTER
BMS CONTROLS
FAN CONTACTOR
INTERFACE PCB
T1 T2 T3 T4 T5 T6
L1 L2 L3 N
A153
1
246A2
U2
V2
W2
N2
U1
V1
W1
E
gn/y
gn/y
CHLORINATOR
MAIN SUPPLY
N1
FAN
380-415V / 3N~ / 50Hz SUPPLY
PUMP JUNCTION BOX
859651-E
864761-B
MAIN PCB
C1
C2
C3 C4 C5
C6
C7
C8 C9 C10
C11 C11
C13
C13
C10
C12
C12
C4
C17
C16
C15
C14
3 PHASE
FILTER
BMS CONTROLS
FAN CONTACTOR
INTERFACE PCB
T1 T2 T3 T4 T5 T6
L1 L2 L3 N
A153
1
246A2
U2
V2
W2
N2
U1
V1
W1
E
gn/y
gn/y
CHLORINATOR
MAIN SUPPLY
N1
FAN
380-415V / 3N~ / 50Hz SUPPLY
PUMP JUNCTION BOX
87
5
3
RELAY
24VDC
BMS
PUMP
ON/OFF
FUSE 3A
AUX
PUMP
CWH10 & CW-H15
CW-H15S

INSTALLATION
Electrical Supply Installation (USA 3PH, 440 - 480V)
Installation of the Cooler must conform to local electrical codes, regulations and standards.
Amps per phase, *
It is a requirement of Seeley International that all Coolers be wired with a dedicated circuit and circuit breaker to the distribution
board, incorporating an isolation switch in the fixed wiring with all pole disconnection from the mains power in accordance with the
National Electric Code.
Specification : 440 - 480V / 60Hz / 3 Phase / 3 8.5 MCA, 15 MOPD
Climate Wizard requires 3-phase (No Neutral) and Ground electrical power. If required, mains isolation switch is to be furnished by the
contractor adjacent to the cooler . Mains power terminals are
provided inside the electrical cabinet with glands provided for cable entry.
- if mounting on the cooler cabinet, take care not to puncture the water reservoir
* 50 & 60Hz models require differing component configurations that vary according to the supply frequency and voltage.
Specifically, the fan motor, 3 phase filter, transformer and pump are unique to the voltage/frequency of supply.
230V/60Hz pump configuration is shown in the above wiring diagram.
860312-D
865102-B
MAIN PCB
230Vac
INPUT
12Vdc
OUTPUT
DENOTES CLASS
2 CIRCUIT
CLASS 2
POWER SUPPLY
MPS-30-12
C1
C2
C3 C4 C5
C6
C7
C8 C9 C10
C11 C11
C13
C13
C10
C12
C12
C4
C17
C16
C15
C14
100VA TRANSFORMER
380-480V TO 230V
BMS CONTROLS
FAN CONTACTOR
INTERFACE PCB
T1 T2 T3 T4 T5 T6 T7
L3L2L1
A153
1
246A2
gn/y
gn/y
CHLORINATOR
CHLORINATOR
PUMP JUNCTION BOX
MAIN SUPPLY
440-480V / 3~ / 60Hz SUPPLY
FAN
38
PRIMARY
0V
0V
115V
115V
3736 35
SET FOR 480V
3433 3231
12
CW-H10, CW-H15, CW-H15S
CWH10 & CW-H15
CW-H15S
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
JUMPER
BETWEEN
PHASE TO PHASE
PRIMARY VOLTAGE

INSTALLATION
Electrical Supply Installation (USA 3PH, 200 - 240V)
Installation of the Cooler must conform to local electrical codes, regulations and standards.
Amps per phase, 14 *
It is a requirement of Seeley International that all Coolers be wired with a dedicated circuit and circuit breaker to the distribution
board, incorporating an isolation switch in the fixed wiring with all pole disconnection from the mains power in accordance with the
National Electric Code.
Specification : 200 - 240V / 60Hz / 3 Phase / 6 .5 MCA, 20 MOPD
Climate Wizard requires 3-phase (No Neutral) and Ground electrical power. If required, mains isolation switch is to be furnished by the
contractor adjacent to the cooler - if mounting on the cooler cabinet, take care not to puncture the water reservoir. Mains power terminals are
provided inside the electrical cabinet with glands provided for cable entry.
* 50 & 60Hz models require differing component configurations that vary according to the supply frequency and voltage.
Specifically, the fan motor, 3 phase filter, transformer and pump are unique to the voltage/frequency of supply.
230V/60Hz pump configuration is shown in the above wiring diagram.
SEELEY INTERNATIONAL –INSTALLATION MANUAL 13
FUSE 3A
87
5
3
RELAY
24VDC
BMS PUMP
ON/OFF AUX
PUMP
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
865164-B
MAIN PCB
230Vac
INPUT
12Vdc
OUTPUT
DENOTES CLASS
2 CIRCUIT
CLASS 2
POWER SUPPLY
MPS-30-12
C1
C2
C3 C4 C5
C6
C7
C8 C9 C10
C11 C11
C13
C13
C10
C12
C12
C4
C17
C16
C15
C14
BMS CONTROLS
FAN CONTACTOR
INTERFACE PCB
T1 T2 T3 T4 T5 T6 T7
L3L2L1
A153
1
246A2
gn
gn
CHLORINATOR
PUMP JUNCTION BOX
MAINS SUPPLY
200-240V / 3~ / 60Hz SUPPLY
FAN
wh bk
CWH10 & CW-H15
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
861371-C
MAIN PCB
230Vac
INPUT
12Vdc
OUTPUT
DENOTES CLASS
2 CIRCUIT
CLASS 2
POWER SUPPLY
MPS-30-12
C1
C2
C3 C4 C5
C6
C7
C8 C9 C10
C11 C11
C13
C13
C10
C12
C12
C4
C17
C16
C15
C14
BMS CONTROLS
FAN CONTACTOR
INTERFACE PCB
T1 T2 T3 T4 T5 T6 T7
L3L2L1
A153
1
246A2
gn/y
gn/y
CHLORINATOR
PUMP JUNCTION BOX
MAIN SUPPLY
200-240V / 3~ / 60Hz SUPPLY
FAN
CW-H15S

INSTALLATION
Electrical Supply Installation (USA 1PH, 200 - 240V)
Installation of the Cooler must conform to local electrical codes, regulations and standards.
Amps per phase, 11.5 *
It is a requirement of Seeley International that all Coolers be wired with a dedicated circuit and circuit breaker to the distribution
board, incorporating an isolation switch in the fixed wiring with all pole disconnection from the mains power in accordance with the
National Electric Code.
Specification : 200 - 240V / 60Hz / 1 Phase / 8 MCA, 15 MOPD
Climate Wizard requires 1-phase (central tapped neutral) and Ground electrical power. If required, mains isolation switch is to be furnished by
the contractor adjacent to the cooler - if mounting on the cooler cabinet, take care not to puncture the water reservoir. Mains power terminals
are provided inside the electrical cabinet with glands provided for cable entry.
* 50 & 60Hz models require differing component configurations that vary according to the supply frequency and voltage.
Specifically, the fan motor, 3 phase filter, transformer and pump are unique to the voltage/frequency of supply.
230V/60Hz pump configuration is shown in the above wiring diagram.
864730-B
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
MAIN PCB
230Vac
INPUT
12Vdc
OUTPUT
DENOTES CLASS
2 CIRCUIT
CLASS 2
POWER SUPPLY
MPS-30-12
C1
C2
C3 C4 C5
C6
C7
C8 C9 C10
C11 C11
C13
C13
C10
C12
C12
C4
C17
C16
C15
C14
BMS CONTROLS
FAN CONTACTOR
INTERFACE PCB
T1 T2 T3 T4 T5 T6
L2L1
A153
1
246A2
gn/y
gn/y
CHLORINATOR
PUMP JUNCTION BOX
MAIN SUPPLY
200-240V / 1~ / 60Hz SUPPLY
FAN
14
CW-H10, CW-H15, CW-H15S
FUSE 3A
87
5
3
RELAY
24VDC
BMS PUMP
ON/OFF AUX
PUMP
C1 MOTOR CONTACTOR COIL
C2 FUSE T12.5A
C3 MAIN PCB POWER IN
C4 PUMP LINK
C5 DRAIN VALVE
C6 SALINITY PROBE
C7 MOTOR CONTROL SIGNAL
C8 WALL CONTROL
C9 WATER INLET SOLENOID
C10 CHLORINATOR LINK
C11 INTERFACE BOARD LINK
C12 NOT USED
C13 CHLORINATOR
C14 BMS COOL/VENT INPUT
C15 BMS ERROR SIGNAL OUTPUT
C16 BMS REMOTE ON/OFF INPUT
C17 BMS FAN SPEED INPUT 0-10Vdc
865171-B
MAIN PCB
230Vac
INPUT
12Vdc
OUTPUT
DENOTES CLASS
2 CIRCUIT
CLASS 2
POWER SUPPLY
MPS-30-12
C1
C2
C3 C4 C5
C6
C7
C8 C9 C10
C11 C11
C13
C13
C10
C12
C12
C4
C17
C16
C15
C14
BMS CONTROLS
FAN CONTACTOR
INTERFACE PCB
T1 T2 T3 T4 T5 T6
L2L1
A153
1
246A2
gn
gn
CHLORINATOR
PUMP JUNCTION BOX
MAINS SUPPLY
200-240V / 1~ / 60Hz SUPPLY
FAN
wh bk
CWH10 & CW-H15
CW-H15S

INSTALLATION
Installation of the water supply to the cooler must conform to local plumbing rules, regulations and standards:
The following specifications for water supply are required:
The installer must provide a manual 1/4 turn ball type shut off valve (do not use a stop cock) in the water supply line adjacent to the cooler,
subject to local plumbing regulations. This allows the water supply to be isolated whenever work needs to be done on the cooler.
Climate Wizard requires a permanent water supply to be connected. 1/2" male connection point provided on the cooler (see diagram), suitable
for a compression fitting.
Seeley International requires an inlet filter to be installed on the water supply line, external to the Climate Wizard cooler to prevent any debris
from entering and damaging cooler components.
Climate Wizard’s water management system is designed to use water that is suitable to be classified as ‘potable’and fit for human consumption.
If alternative water is to be used that contains high levels of salinity, hardness, acidity or chemical contaminants, then additional filtration or
treatment systems should be employed to render the water ‘potable’.
Not all installation pipeworks are the same, and some may require additional prevention against water hammer.
If water hammer is a problem, it is the responsibility of the to fit an appropriate water hammer arresting device external to the cooler.
Water Connections :
Water Supply : 100kPa (15psi) - 800 kPa (115psi) MAXIMUM @ 20L/min (5.3 gal/min)
Water Supply Temperature : 40°C (105°F) MAXIMUM
Important! If the water pressure exceeds this maximum specification then a pressure reducing valve is required and must be supplied
and fitted by the installer.
In areas subject to freezing, the water line needs a drain down facility.
WATER SUPPLY FILTRATION
Important! Flush the water pipe to remove any contaminants (swarf, filings or dirt) before final fitting. Contaminants can lodge in the
solenoid , preventing it from functioning correctly.
WATER HAMMER
Installer
½”BSP (Aus/Eur), ½”NPT (USA) male connection supplied
Water Supply Installation
ACCESS COVER
FOR DRAIN VALVE
CONNECTION
WATER CONNECTION
1/2”MALE NIPPLE
(Water connection may
require an adaptor to
suit local pipe sizes)
660mm
(26”)
200mm
(7.9”)
DO NOT OVER-TIGHTEN
OR CROSS-THREAD
COMPRESSION FITTINGS
ONTO THE PLASTIC
WATER INLET NIPPLE.
REAR VIEW
SEELEY INTERNATIONAL –INSTALLATION MANUAL 15

200mm
(8")
200mm
(8")
Ø25mm
(1")
INSTALLATION
Drain Installation
A built-in Drain Valve is controlled by the water management system. The valve has 1½”(40mm) BSP male connection and is provided with a
reducing fitting for connection (if desired) to a flexible hose for running water to waste. See diagram for location. Recommended minimum drain
hose diameter is ¾”(20mm).internal
DRAIN VALVE
It is a requirement of Seeley International - Never drain the water directly on to the roof
The correct drain system must be used. Water drained from the drain valve must be carried away to a suitable discharge point on the building or
property, in accordance with local regulations.
The positive pressure tube helps prevent ingress of moisture into the electrical components of the drain
valve by providing an air pressure barrier. The air pressure is provided by a small amount of air flow (provided by the cooler fan) re-directed and
ducted into the Drain Valve’s electrical enclosure.
Drain fittings location
(Access panel removed,
view from rear of cooler)
Drain Valve positive pressure tube fitted
TOP VIEW
120mm (4.7”) Drain Outlet position
120mm
(4.7”)
2
1
3
54
6
1. = Drain Valve Assy
2. = O Ring
3. = Nut
4. = Elbow spacer
5. = Drain Elbow
6. = Positive Pressure tube
Pressure tube hole location
16
CW-H10, CW-H15, CW-H15S

INSTALLATION
Control Schemes
Climate Wizard coolers are supplied from the factory with one (1) Wall Control and a 20m (65’) control cable. This makes it possible for the
Cooler to be controlled independently and automatically from the zone to which it is delivering cool air. No additional equipment is required. The
Wall Control incorporates a thermostat that regulates fan speed to maintain indoor temperature within 0.5°C ( 1°F) of the set temperature.
Climate Wizard coolers are also supplied with input/output connectors to enable the cooler to be controlled from an external location, including a
BMS system.
Whatever control option is being used, the inbuilt Climate Wizard water management and fault monitoring features are always functional. The
Climate Wizard control scheme incorporates some parameters that can be altered to other settings if the default settings are not suitable.
Individual coolers can be controlled completely from within their cooling zone using the Wall Control-thermostat supplied.
A 20m (65’) connecting cable, plugged each end, is supplied. 40m (130’) cables are also available on request (Cable kit 40m Part No. 094724).
Maximum permissible cable length between the Wall Control and the cooler is 40m (130’).
No interconnection between coolers to achieve ‘Group control’is possible.
Climate Wizard Coolers are supplied with an ‘Interface PCBA’.
This can be set up to control the Climate Wizard from EXTERNAL devices, such as PLCs and Building Management Systems. In this case the
Climate Wizard will cease to function in its standard AUTO [Auto] or MANUAL [Man] mode and will respond only to the external commands.
even if a BMS or PLC is used, it is recommended to leave the Wall Control and cable within the control box for use during servicing.
+ +
Local zone control
NOTE:
Control from remote location
Building Management System (BMS) Interface
Four (4) plug receptacles are provided in the electrical control enclosure as shown. These are solely for the control of the cooler from a remote
location. When any receptacle detects a voltage between 4 - 32 V DC the local Wall Control is disabled and the entire cooler comes under the
control of remote commands.
In order for the receptacles to respond to external commands the installer must provide independent power supply of 4-32V DC to any of
the receptacles he wants to activate. For example, to turn on the pump in order to initiate 'cooling' a DC voltage of 4-32V must appear on the +
pin of the COOL/VENT receptacle. When that voltage is removed the system reverts to 'vent' mode. Or, in order to stop the machine a voltage
must be applied to the + pin of the REMOTE ON/OFF receptacle. When that voltage is removed the machine will start up again.
Connect the polarity as shown - incorrect polarity connection may damage the circuit board.
The control commands may emanate from a purpose built device such as a panel containing switches for Cooler ON-OFF, Pump ON-OFF, a
potentiometer for the fan speed control, and a light to display a cooler fault condition. The panel will include its own power supply to create
signals compatible with the Climate Wizard specifications (4-32V DC). Or they may emanate from a BMS (Building Management System).
Depending on the type of BMS it may be necessary to provide an “off-the-shelf”Interface Module between the BMS serial bus and the Climate
Wizard plug receptacles.
NOTE:
NOTE:
PLUG RECEPTACLES - INTERFACE BOARD
SEELEY INTERNATIONAL –INSTALLATION MANUAL 17

INSTALLATION
Control Schemes cont.
Remote ON-OFF
The remote ON-OFF function can be used when the cooler is controlled by its local Wall Control or by an external command centre. In either
case, if a voltage (4-32Vdc or 10-32Vac) is applied to the “REMOTE ON/OFF”plug, the cooler will shut down. When the voltage is removed, the
cooler will re-start in the same mode it was running before shut down. This condition of being shut down in this way will be shown on the Wall
Control by the words ‘Preparing to start’flashing on the screen.
Error Signal
The error signal comprises of a single pole voltage free contact (solid state electronic, not mechanical relay) that closes under fault conditions.
The contact is rated at 500mA at 32 volts DC max.
In order to use this signal an external voltage must be supplied that will then drive a relay coil or indicator lamp that does not exceed the above
ratings.
R
ERROR SIGNAL
MAX 500mA
MAX 32V DC
+ve
-ve
Control Selection
4 - 32 Vdc = ON
10 - 32 Vac
Pump Control
4 - 32 Vdc = COOL
10 - 32 Vac
CONDITIONING
FILTER
Speed Control 0 - 10Vdc
0V = OFF, 10V = Max
Error Output
Open Collector.
PWM Controlled 3VF Motor
or
Electrically Commutated Motor
Optional Interface PCB
if/as required by the
Building Management System
PWM Speed
Control Signal
Micro
Controlled
Circuitry
P3
P1 P2
12.5A FUSE
Control
PCBA
Fan Relay
(controlled
via PCBA)
Power
Neutral
Junction
Box
Water Management
Chlorinator
Water Management
Tornado Pump
CW-H10 = 2 Pumps
CW-H15 = 3 Pumps
B.M.S.
INTERFACE
PCB
CONTROL
PCBA
CW-H Wiring Schematic
Wall Control &
Thermostat
(Non-BMS connected)
Water Management
12VDC Drain Valve
Water Management
Salinity & Water Level
Probe
Water
Management
Water Inlet
Solenoid
Motor/Fan
Assembly
18
CW-H10, CW-H15, CW-H15S
Other manuals for Climate Wizard Multi-Magic CW-H10
1
This manual suits for next models
2