MI00532-3-EN INSTALLATION MANUAL 5/7
ModBUS CONNECTION RULES
1) Install the modules in the DIN rail (120 max)
2) Connect the remote modules using cables of an appropriate length. The following table shows cable length data:
-Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables
that connect the two farthest modules (see Diagram 1).
-Derivation length: maximum length of a derivation 2 m (see Diagram 1).
Lunghezza
bus
Lunghezza
derivazione
1200 m 2 m
Schema 1
Modulo 2Modulo 1
Modulo 3
Modulo 4
Modulo 5
Lunghezza del Bus
Ld= Lunghezza derivazione
Ld
For maximum performance, it is recommended to use special shielded cables, such as BELDEN 9841.
(*)
Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.
USB PORT
The module is designed to exchange data according to the modes dened by the MODBUS protocol. It has a
micro USB connector on the front panel and can be congured using applications and/or software programs.
The USB communication has priority over the RS485 communication.
The USB serial port uses the following communication parameters: 2400 BAUD, 8BIT, NO PARITY, 1 STOP BIT, ModBUS
ADDRESS 1. The USB communication port responds exactly like the RS485 port with the exception of the
communication parameters. During the use of the USB port, the bus will be inactive; it will reactivate automatically
after disconnecting the USB port cable. EASY SETUP (for Windows systems) is the software to be used for the
conguration and calibration of the load cell.
For more information, visit www.seneca.it/prodotti/z-sg.
INSTALLATION REGULATIONS
The module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life,
adequate ventilation must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots.
Avoid mounting modules over heat-generating equipment.
Installation in the bottom part of the electrical panel is recommended.
Guida DIN
MODULO
Inserimento nella
guida DIN
Insertion in the DIN rail
As shown in gure:
1. Insert the IDC10 rear connector of the module on a
free slot of the DIN rail
(the insertion is univocal since the connectors are
polarized).
2. To secure the module to the DIN rail, tighten the two
hooks on the sides of the IDC10 rear connector.
Bus
length
1200 m 2 m
Diagram 1
DL
Bus length
Ld= Derivation length
Derivation
length Module 1 Module 2
Module 3
Module 4
Module 5
Insertion in the
DIN rail
MODULE
DIN rail