
MG Series Boilers –Installation and Service Manual
13
2.7 VENTING
The responsibility of providing a suitable vent of adequate draft capacity and in good usable condition is
that of the gas fitter/installer. Interference with the air supply for the boiler shall be prohibited.
Vent installation and type of gas vent or vent connector MUST follow all applicable national,
provincial/state, and local codes, laws, regulations, and ordinances as described in Section 2.2.
For boilers for connection to gas vents or chimneys, vent installations shall be in accordance with “Venting
of Equipment,”of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or “Venting Systems and Air
Supply for Appliances”of the Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes.
Gas vents must be supported and supports spaced in accordance with the vent manufacturer’s installation
instructions and as required by any applicable codes. Laterals, offsets, and vertical components should be
securely supported with wall straps and at offsets so that the wall straps prevent the weight from stressing
the elbows. All portions of the venting shall be supported for the design and weight of the material
employed.
Horizontal runs shall slope upward not less than ¼ inch per foot (21 mm/m) from the boiler to the vent
terminal. Vent cannot go horizontally to vent terminal without a chimney.
This unit must be installed with the factory supplied draft hood in place. The draft hood is a safety device
designed to control chimney drafts that might affect combustion or blow out the pilot. The draft hood
supplied with the boiler must not be altered. The minimum skirt height, as indicated on the draft hood,
must be maintained.
Vent connectors serving the boiler must not be connected into any portion of mechanical draft systems
operating under positive pressure.
Vent Terminal Information
The minimum distance from the termination of a vent terminal to adjacent public walkways, adjacent
buildings, operable windows and building openings shall be not less than those values specified in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA Installation Codes.
For proper operation, the vent terminal must be kept free of snow and other debris at all times.
To prevent discoloration and degradation of building materials by flue gases and flue gas condensation,
ensure that the vent terminal is installed clear of nearby obstacles. In all cases, installation shall be in
accordance with code.
Maintain a minimum clearance of 4 feet (1.22 m) horizontally, and in no case above or below, unless a 4
foot (1.22 m) clearance is maintained from electric meters, gas meters, regulators and relief equipment.
Removal of an Existing Boiler
When an existing boiler is removed from a common venting system, the common venting system is likely to
be too large for proper venting of the appliances connected to it.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance
remaining connected to the common venting system placed in operation, while the other appliances
remaining connected to the common venting system are not in operation.
a) Seal any unused openings in the common venting system.
b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe
condition.
c) Insofar as is practical, close all building doors and windows and all doors between the space in which
the appliances remaining connected to the common venting system are located and other spaces of
the building. Turn on clothes dryers and any appliance not connected to the common venting system.
Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at
maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.