SurePoint PUMPRIGHT PR17 User manual

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
PumpRight &
With PWM Control
Maximum Pump Flow and Application Rates
396-4953Y1
Number of
Diaphragms
Max Flow
GPM
Max GPA on 40’ at
6 MPH
Max GPA on 60’
at 6 MPH
PR17 317 35 23.5
PR30 330 62 41
PR40 440 82 55
D250 655 75
Operator should read this
manual before operating the
system.
SurePoint Sentinel
Rate Control
Sentinel Instructional Videos
Scan or click

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
See the Sentinel Manual, 396-4035Y1, for harness layouts, system setup, module addressing and
more about operating the Sentinel Rate Control system.
Scan or click the QR Code to go to the Sentinel Instructional Videos Playlist on YouTube.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control ii Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Table Of Contents
A
Introduction
Introduction
• Important Safety Information—Read this first...................................................
• Basic Steps to Install your Fertilizer System ....................................................1
• Complete Fertilizer System Example Drawing .................................................2-3
B
Components
Liquid
Components - Liquid
• Flowmeters ......................................................................................................4-5
• Section Valves .................................................................................................6
• Pressure Sensor, .............................................................................................7
• Pump Priming and Air Bleed Valve ..................................................................8
• Recirculation & Agitation..................................................................................9
• Flow Indicators and Manifolds, Check Valves, Orifice Charts...........................10-17
• Dual Check Valve Systems, Row Distribution ..................................................18-21
• Metering Tube Charts ......................................................................................22-24
D
Components
Wiring & Elec.
Components - Wiring & Electrical
• See 396-4035Y1 Sentinel Setup and Operating Manual
E
Installation
Overview
Installation Overview
• Floating Ball Flow Indicators, PumpRight Installation .......................................26,27
• Hydraulic Connections, PWM Valve, Hydraulic Oil Flow Requirements ...........28-30
• Liquid Plumbing Connections...........................................................................31-32
F
Setup &
Operation
Setup & Operation
• See 396-4035Y1 Sentinel Setup and Operating Manual
H
Maintenance
& Parts
Maintenance & Parts
• Air Bladder, Winterization, Pump Oil, Diaphragm and Valve Replacement.. ....41
• Pre-season Service .........................................................................................42
• Replacing Valves and Diaphragms ..................................................................43-45
• Pump Assemblies and Parts Breakdowns........................................................46
• PWM Valve and Motor Parts............................................................................47
• See 396-4034Y1 PumpRightManual
G
Trouble-
Shooting
Troubleshooting
• Pump Will Not Turn, Manual Operation Mode..................................................34
• Application Rate Fluctuates or Slow Getting to Target Rate.............................34
• Flowmeter Troubleshooting and Tap Test........................................................36
• Section Valve Won’t Move, Pressure Sensor Issues........................................37
• Other Troubleshooting Issues..........................................................................38-39

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control iii Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Safety A
TAKE NOTE! THIS SAFETY ALERT SYMBOL FOUND THROUGHOUT THIS MANUAL IS USED TO CALL YOUR
ATTENTION TO INSTRUCTIONS INVOLVING YOUR PERSONAL SAFETY AND THE SAFETY OF OTHERS.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN INJURY OR DEATH.
THIS SYMBOL MEANS
ATTENTION!
BECOME ALERT!
YOUR SAFETY IS INVOLVED!
Note the use of the signal words DANGER, WARNING and CAUTION with the safety messages. The appropriate
signal word for each has been selected using the following guidelines:
DANGER: Indicates an imminently hazardous situation that, if not avoided, will result in death or se-
rious injury. This signal word is to be limited to the most extreme situations typically for machine
components which, for functional purposes, cannot be guarded.
WARNING: Indicates a potentially hazardous situation that, if not avoided, could result in death or
serious injury, and includes hazards that are exposed when guards are removed. It may also be
used to alert against unsafe practices.
CAUTION: Indicates a potentially hazardous situation that, if not avoided, may result in minor or
moderate injury. It may also be used to alert against unsafe practices.
NOTICE is used to address safety practices not related to personal safety.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control iv Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Hydraulic Fluid and Equipment Safety
This system uses hydraulic equipment with hydraulic fluid under extremely high pressure.
Hydraulic fluid escaping under pressure can have sufficient force to penetrate the skin causing serious injury.
Keep all hoses and connections in good serviceable condition. Failure to heed may result in serious personal
injury or death. Avoid the hazard by relieving the pressure before disconnecting lines or performing work on
the system.
Make sure hydraulic fluid connections are tight and all hydraulic hoses and lines are in good condition before
applying pressure to the system. Use a piece of paper or cardboard, NOT BODY PARTS, to check for sus-
pected leaks. Wear protective gloves and safety glasses or goggles when working with hydraulic systems.
DO NOT DELAY!
Check hydraulic hoses and fittings frequently. Loose, broken, and missing hardware can cause equipment to
not perform properly and can result in serious injury or death.
Hydraulic systems can be hot and cause burns. Before working on any system, wait until the fluid has
cooled.
If an accident occurs, see a doctor familiar with this type of injury immediately. Any fluid injected into the skin
or eyes must be treated within a few hours or gangrene may result.
A Word to the Operator
It is YOUR responsibility to read and understand the safety messages in this manual. YOU are the key to
safety.
SAFETY IS YOUR RESPONSIBILITY.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
See the Sentinel Manual, 396-4035Y1, for harness layouts, system setup, module addressing and
more about operating the Sentinel Rate Control system.
Scan or click the QR Code to go to the Sentinel Instructional Videos Playlist on YouTube.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
General Description
You have purchased a SurePoint fertilizer system for your equipment. This system will be
controlled by your SurePoint Sentinel ECU Rate Controller via your ISO VT display. The
Rate Controller will adjust the speed of the SurePoint PumpRight hydraulic pump based
on feedback from the flowmeter and vehicle speed. The system is capable of using section control or
prescription rates in conjunction with Task Control on your display to minimize overlap areas with optional
section valves or to do variable rate application.
A
Introduction
Basic Installation Steps
1. Mount the Sentinel ECU in a secure, convenient location.
2. Open the packages and familiarize yourself with the components. See the System Overview Example on
the following page to see the big picture of how SurePoint Fertilizer Systems are installed. Refer to
manual sections B & D for component information.
3. Mount the PumpRight pump and make hydraulic connections. See section E for hydraulic plumbing
information.
4. Plumb the tank to the PumpRight inlet. See section E for details.
5. Install the plumbing kit including section valves, flow indicator columns / manifolds, check valves,
plumbing to each row unit delivery point. See section B for information on these components.
6. Attach the flowmeter outlet to section valve or manifold inlet. Attach section valve outlets to flow indicator
inlets.
7. Attach harnesses as shown in the Sentinel Manual, 396-4035Y1.
8. Set up Controller for SurePoint fertilizer system as shown in the Sentinel Manual, 396-4035Y1.
9. Fill system with water, conduct initial operation and tests per the Sentinel Manual, 396-4035Y1.
10. Winterize system with RV Antifreeze if freezing temperatures are expected.
11. Do pre-season service each year as described on page 39.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 2Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
System Overview Example
The following gives an example of a complete SurePoint Fertilizer system with these
components:
• Display with UT or VT and Task Control
• Sentinel ECU Module
• PumpRight PR30
• Section Valves
• Flow Indicators
• Check Valves with Colored Disc Orifices
A
Introduction
SurePoint Adapter Harness-
(connector detail in 396-4035Y1
Manual)
Sentinel
Rate
Controller
Display
with VT or
UT in cab
ISO
Harnesses
Fertilizer Opener,
Seed Firmer, SS
Tube, etc.
Typically 3/4” hose used to
feed each manifold. Length
of this hose can vary
significantly.
This is usually 3/8” hose. Typi-
cal length is 1-4’ with check
valves placed on each row that
distance from ground.
This is usually 3/8” hose.
Maximum recommended length
is 20 feet.
Check valve is mounted
near each row. 1/4 turn
cap is always check valve
outlet. Colored disc orifice
can be placed under cap.
TANK
Hose is used from the flowmeter outlet to section
valves. If not using section valves, flowmeter is
plumbed directly to flow indicators or a simple tee
is used to divide flow to multiple flow indicator
manifolds.
Strainer
PWM Pump Harness
(connector detail in 396-
4035Y1 Manual)
Section Valve Harness
(connector detail in 396-4035Y1
Manual)

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 3Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
System Overview Example A
Introduction
Sentinel
ECU
Display with
UT or VT in
cab
ISO
Harnesses
Fertilizer Opener,
Seed Firmer, SS
Tube, etc.
The dual
color
LiquiShift
tubes run
from this
point and
end just
under
each
isolated
feed flow
indicator
column.
This is usually 3/8” hose. Typi-
cal length is 1-4’ with check
valves placed on each row that
distance from ground.
This is usual-
ly 3/8” hose.
Maximum
recommend-
ed length is
20 feet and
lengths do
not need to
be equal.
Zip valve or check valve is
mounted near each row.
1/4 turn cap is always
check valve outlet.
Hose is used from the flowmeter
outlet to LiquiShift valve stack
inlet
PWM Pump Harness
(connector detail in Section D)
Extension harness to
reach LiquiShift mount-
ing location
The following gives an example of a complete SurePoint Fertilizer system with Gen2
LiquiShift and these components:
• Display with UT or VT and Task Control
• Sentinel Rate Controller
• PumpRight PR30
• LiquiShift Valve Stack
• Isolated Feed Flow Indicators
• Check Valves SurePoint adapter harness for 2
products and section valves
3/4” or 1” hose typical
from each LiquiShift
valve to each Li-
quiShift tube assem-
bly.
TANK
Strainer

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 4Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
PR17 & PR30 Electromagnetic Flowmeter Kits
0.13 - 2.6 GPM Item Number 500-02-2082 (PR17)(FM only 204-01-46211CUF00)
0.3 - 5.0 GPM Item Number 500-02-2085 (PR17) (FM only 204-01-46211CUF01)
0.6 - 13 GPM Item Number 500-02-2090 (PR17 & PR30) (FM only 204-01-46211CUF02)
1.3 - 26 GPM Item Number 500-02-2095 (PR30) (FM only 204-01-46211CUF03)
Kits include flowmeter, adapter harness, mounting bracket, hose barb fittings & hose
clamps.
Flowmeter Model
(black meter with orange label)
Flow Cal
Pulses per gallon FPT Size
Hose Barb
In kit
0.13 - 2.6 GPM 3000 3/4” 1”
0.3 - 5 GPM 3000 3/4” 1”
0.6 - 13 GPM 2000 3/4” 1”
1.3 - 26 GPM 2000 1” 1”
B
Components
Liquid
-Before doing any arc welding on the implement, unplug the cable to the flowmeter, or damage to the
flowmeter may result.
-Do not power wash the flowmeter. High pressure spray directed at the back edge of the face plate or at
the wire connector may allow water into the flowmeter electronics.
Amp SuperSeal 3-pin connector
Use adapter 201-17842
to connect to 3-pin MP harness
Mounting Bracket,
400-3826Y1 (QTY 1)
(not used for PR40 and
D250 Pump)
Mounting Bracket,
410-4015Y1 (QTY 1)
(not used for PR40 and
D250 Pump)
Troubleshooting Tip:
3-pin MP Tower A- Signal B- 12V Power C- Ground (See the next page for more flowmeter tips)
3-pin AMP SuperSeal 1– Ground 2– 12V Power 3– Signal
Remove red guard to reach pins. Be careful so you don’t break red side keepers.
1 2 3
Electromagnetic flowmeters are superior to traditional turbine flowmeters in two basic ways. First, they
have no moving parts. There are no wear items or potential for contaminants to jam a spinning turbine.
Second, electromagnetic flowmeters detect the flow by electrically measuring the velocity of the liquid,
which makes them independent of viscosity or density of the fluid measured. They are extremely accurate
using the standard calibration number. SurePoint still recommends you perform a catch test to verify the
system is properly installed and configured.
The flowmeters will accurately read higher than the rated range.
Earlier model flowmeters (meters with white labels with black text) have different calibration numbers. The flow cal
number (pulses per gallon) is printed on the serial number sticker on the side of the flowmeter.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 5Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
PR40 & D250 Electromagnetic Flowmeter Kit
2.6 - 53 GPM Item Number 500-02-2080 (FM only 204-01-46211CUF04)
Kits include flowmeter, adapter harness, mounting bracket, hose barb fittings & hose
clamps.
Flowmeter Model
(black meter with orange label)
Flow Cal
Pulses per gallon FPT Size
Hose Barb
In kit
2.6—53 GPM 2000 1-1/4” 1-1/2”
1.3—26 GPM 2000 1” 1”
B
Components
Liquid
Amp SuperSeal 3-pin connector
Use adapter 201-17842
to connect to 3-pin MP harness
-Before doing any arc welding on the implement, unplug the cable to the flowmeter, or damage to the
flowmeter may result.
-Do not power wash the flowmeter. High pressure spray directed at the back edge of the face plate or at
the wire connector may allow water into the flowmeter electronics.
Mounting Bracket,
400-3335Y1 (QTY 2)
(used for PR40 and D250
Pump only)
Troubleshooting Tip:
Remove red guard to
reach pins. Be care-
ful so you don’t break
red side keepers.
1 2 3
3-pin AMP SuperSeal 1– Ground 2– 12V Power 3– Signal
Power to Ground should be 12 volts.
Signal to Ground should be 4.5 to 5 volts
Do Tap Test between Signal and Ground to test harnessing.
3-pin MP Tower A- Signal B- 12V Power C- Ground
Additional Tip:
If flowmeter is not
reading and the har-
nessing has checked
out OK with voltage
readings and tap test,
try cleaning the inside
tube of flowmeter with
warm soapy water
and a soft brush.
Sometimes, a film
builds up on the elec-
trodes.
The flowmeters will accurately read higher than the rated range.
Earlier model flowmeters (meters with white labels with black text) have different calibration numbers. The flow cal
number (pulses per gallon) is printed on the serial number sticker on the side of the flowmeter.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 6Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Section Valves and LiquiShift Valves
105-100075BRB90
105-100PLG (alternate
105-100PLG025 includes 1/4” pipe
thread for gauge)
103-2501Y1
KZ TX2 Valve
(single complete valve)
117-211-0066
Liquid outlet to
each section
Additional Parts:
1” Gasket 105-100G-H
1” Clamp 105-FC100
B
Components
Liquid
Liquid
inlet
Pressure Sensor
How section valves work
Section valves can be assembled into
groups with a common inlet to control flow to each
section. Common assemblies use up to 5-6
valves, however, more can be used where
practical. Many alternate fittings can be used to
accommodate different hose sizes and
configurations.
The valves have a 3-pin weather pack
electrical connector. This has a power, ground,
and switched wire. The power measured to
ground should have 12 volts when the controller is
on. The switched wire will have 12 volts to turn
the valve on, and 0 volts to turn the valve off.
Wiring Connector:
Pin A—Red, 12 Volts +
Pin B—Black, Ground -
Pin C—White, Signal
12V=on ; 0V=off
Mounting Hardware:
2 Valve Bolt Kit
384-1100
Mounting Bracket
400-2493Y1
Note: Ensure back-side port is
capped prior to use
Liquid
inlet
Gen2
How LiquiShift Works
LiquiShift is a two-valve manifold specifically
built and controlled to provide the operator a very
wide flow range for variable rate application. It is
valuable for variable rate prescription application or
high-speed implements, or variable rate between
different fields. LiquiShift has an A and B valve that
are opened based on the system pressure.
The valves themselves are identical to a
regular section valve (KZ TX2) and have a 3-pin
weather pack electrical connector.
The A Valve is connected to a set of smaller
metering tubes. The B Valve is connected to a set of
larger metering tubes. The LiquiShift controller
automatically turns on the A valve, or the B valve, or
both valves depending on the flow required.
Gen3 LiquiShift systems on the Sentinel are
available with up to 16 sections depending on the
implement.
See also: Gen3 LiquiShift Manual (396-4608Y1)
Gen2 LiquiShift Manual (396-4063Y1)

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 7Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
The Sentinel has the ability to show fertilizer system pressure on the display. The pressure
sensor is most often mounted on electric section valves when used in PumpRight systems.
The pressure sensor is a 100 psi, 0 to 5 volt 3-wire type sensor. The sensor has a 1/4” MPT fitting.
The pressure sensor is very helpful to optimize system performance and troubleshoot any issues.
See the troubleshooting section for more help.
Pressure Sensor
3 Wire Sensor with 2” Manifold x 1/4” MPT Fitting
Item Number 520-00-055100
B
Components
Liquid
Pressure Sensor (3-wire
type) with harness
521-05-050150
2” Plug with 1/4” gauge port
105-200PLG025
Pressure Sensor Hose Tap Kits
When electric section valves or LiquiShift is not used in the fertilizer system, the best location to install the
pressure sensor is in the hose after it leaves the flowmeter. To use these kits, order the correct kit for your
hose size. Then also order the kit above that includes the 2” Manifold x 1/4” MPT fitting.
3/4” Hose Pressure Tap 520-00-055800
1” Hose Pressure Tap 520-00-055850
1 1/2” Hose Pressure Tap 520-00-055900
0 to 5 v - 100 PSI
Pressure Calibration: 50 mv/psi
1” Plug with 1/4” gauge port
105-100PLG025
Pressure Sensor for
LiquiShift is mounted at the base of
the valve stack. The same sensor is
used for LiquiShift and displayed on
the display.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 8Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Pump Priming and Air Bleed Valve
An air bleed valve is included with each pump to aid in system
priming. It is shipped in the pump accessories bag and must
be installed during system installation.
Why use an air bleed valve:
Most fertilizer systems are equipped with a 4 lb or 10 lb check valve on the end of each hose delivering
fertilizer to the ground. These valves do not let air escape from the system, unless it is pressurized.
PumpRight liquid pumps are not good air compressors. Therefore, the pump can struggle to prime due to air
trapped on the outlet side of the pump.
The air bleed valve is a small 1/4” valve that when opened lets air escape from the pump outlet at zero
pressure. Open until liquid comes out and then close the valve.
Be sure the air bleed valve tube does not become plugged with dirt or it will not allow air to bleed.
How to install the air bleed valve:
Remove the 1/4” plug from the quick connect fitting on the pump outlet side (see pictures below). Next, insert
the 1/4” tubing in the quick connect fitting. Run the 1/4” tubing to an easily accessible spot on your
equipment. Next, cut the tubing and push the 1/4” valve onto the tubing. Finally, run the tubing to a low
location where any fertilizer that escapes will run on the ground.
Be sure the air bleed valve tube does not become plugged with dirt or it will not allow air to bleed.
B
Components
Liquid
PR17 & PR30 PR40 & D250
1/4” Tubing
Attach 1/4” tubing to 1/4” QC on the
90 deg HB sweep gauge port
1/4” air
bleed
valve
Attach 1/4” tubing to 1/4” QC on
back side of 1” x 2” tee on outlet side
of pump
1/4” air
bleed
valve

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 9Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Recirculation & Agitation
A recirculation valve is standard on all 4 PumpRight models outlet
plumbing assembly.
How Recirculation Works:
When running a PumpRight pump at less than 20% of it’s maximum flow, it sometimes improves system
stability to allow the pump to run faster. Opening the recirculation valve diverts some pump flow before the
flowmeter, causing the pump to run faster. The application rate is still measured by the flowmeter and
everything that passes through the flowmeter is applied to the ground. If the pump is surging at a low flow
rate, open the recirculation regulation valve slowly until the pump runs smoothly. Start with a quarter to a half
turn. OPENING THE VALVE LOWERS THE MAXIMUM RATE THAT CAN BE APPLIED TO THE GROUND.
Close the valve if a higher rate is required.
How to modify for tank agitation:
If tank agitation is required, the recirculation valve can be re-plumbed to divert flow to the tank. All that is
required is to remove the 1/2” recirculation hose from the pump. Then replace the 3/8” MPT x 1/2” HB on the
inlet side of the pump with a 3/8” plug which is included in your PumpRight accessories bag. Finally, install a
longer 1/2” hose from the recirculation valve back to the tank.
B
Components
Liquid
1/2”
recirculation
hose
Recirculation Regulation Valve,
102-23520-3/4
Start with a quarter to a half turn.
PR17 & PR30 PR40 & D250
Recirculation Regulation
Valve, 102-23520-3/4
1/2”
recirculation
hose
Recirculation hose attaches to back of 2” x 1” tee
on pump inlet

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 10 Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
B
Components
Liquid
Floating Ball Flow Indicator & Manifold System
Flow indicators give a clear visual signal that a fertilizer
system is working. These indicators use an o-ring and wire
clip connection to snap together in any configuration
necessary.
SurePoint has simple tee brackets and U-bolts that will
mount these to a variety of bar sizes.
Two main types of flow indicators are used. On 30”
row spacing, the low flow column with 1/4” push to connect
outlet is recommended for rates under 10 GPA. For rates over
10 GPA the full flow column with 3/8” hose barb outlet is
preferred.
Product Distribution
To assure proper and even distribution to each row, the product being applied
must be metered to each individual row. This metering is done by one of the 3
following methods which create back pressure so an equal amount of liquid is
applied to each row:
1. A metering orifice may be placed in the top cap of each floating ball flow indicator. (See
photos on page 12. This is not used very often.)
2. A metering orifice may be placed in the check valve cap in the line that leads to each
row. (See photo on page 14)
3. A dual metering tube kit with dual check valves may be used. (See pages 18-21)
4. A LiquiShift valve stack may be used that automatically selects which metering tube to
use based on system pressure.
Parts List
Complete Columns
701-20460-950 Single Full Flow Column with 3/8" HB - 90 Degree Outlet
701-20460-940 Single Full Flow Column with 3/8” QC - 90 Degree Outlet
701-20460-960 Single Full Flow Column with 1/2” HB - 90 Degree Outlet
701-20460-935 Single Low Flow Column with 3/8” QC - 90 Degree Outlet
701-20460-920 Single Low Flow Column with 1/4" QC - 90 Degree Outlet
Fittings
701-20503-00 ORS x 3/4" HB - Straight Service Parts Only
701-20511-00 ORS x 3/8" HB - 90 Degree 701-20460-02 Wilger Flow Indicator Ball Retainer
701-20512-00 ORS x 1/2" HB - 90 Degree 701-20460-03 FKM O-Ring for indicator body & fittings
701-20513-00 ORS x 3/4" HB - 90 Degree 701-20460-04 Wilger Lock U-clip
701-20516-00 ORS x 1/4" QC - 90 Degree 701-20460-05 Flow Indicator Ball - 1/2" SS Ball
701-20517-00 ORS x 3/8" QC - 90 Degree 701-20460-06 Flow Indicator Ball - Maroon Glass
701-20518-00 ORS x 1/4" FPT - 90 Degree 701-20460-07 Flow Indicator Ball - Red Celcon
701-20519-00 ORS x 1/4" FPT - Straight 701-20460-08 Flow Indicator Ball - Green Poly
701-20520-00 ORS Male x ORS Female - 90 degree 701-20460-09 Flow Indicator Ball - Black Poly
701-20521-00 Wilger End Cap 701-20460-15 Viton O-Ring for column & fittings
701-20523-00 ORS Male x ORS Female x 3/8" FPT - Isolator 701-40225-05 Viton O-Ring for Orifice
701-20525-00 ORS Male x ORS Male x 1" FPT - Tee
Brackets & U-Bolts
400-1037A1 3-6 Row Bracket
400-3155Y1 7-12 Row Bracket
400-2011A1 White Backer Plate for 3-6 Row Bracket
400-2010A1 White Backer Plate for 7-12 Row Bracket
400-1315A2 Flow Indicator Bracket, 6-8 in wide hitch mount

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 11 Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
701-20521-00
End Cap
400-3155Y1
7-12 Row
Bracket
101-100075BRB
1” MPT x 3/4” HB
The full flow column is
typically used with rates over 10
GPA on 30” rows. For rates less
than 10 GPA SurePoint
recommends the low flow columns
with 1/4” push to connect outlet
fittings.
The full flow columns are
most often assembled with 3/8”
hose barb outlets. See the low flow
info below for the difference
701-20460-95
Full Flow Col-
umn w/ 3/8”
HB Outlet 701-20525-00
Center Fed Tee
with Gauge Port
380-1001
Fits 7”x7” Tube
Full Flow Indicators w/ 3/8” Hose Barb Outlet
Column Flow (GPM): .05-2.70 GPM
Equivalent Application Rate
On 30” Rows at 6 MPH: 2-70 GPA
Ball Selection for 30” Rows
GPM GPA Ball
.05-.18 2-6Green Plastic*
.09-.30 3-10 Red Plastic*
.31-.72 10-20 Maroon Glass
.40-2.1 13-70 Stainless Steel (1/2”)
*Plastic balls may float on heavier fertilizers, such as 10-34-0.
SurePoint recommends using the low flow column for these
flow rates.
1/4” x 2”
Bolt
Floating Ball Flow Indicators-
Full Flow Column (mostly 3/8” HB) B
Components
Liquid
400-2010A1
12 Row White
Visibility Back-
er Plate
400-1037A1
3-6 Row
Bracket
400-2011A1
6 Row White Visi-
bility Backer Plate
701-20513-
00 3/4” HB
90 degree
inlet
Low Flow Column (mostly 1/4” QC or 3/8” QC)
The low flow column has a smaller internal diameter. This means a
heavier ball can be used to monitor a smaller flow.
SurePoint uses the low flow columns with 1/4” push to connect out-
let fittings. The flow capability of 1/4” tubing and the low flow column are a
great pair for rates on 30” rows under 10 GPA.
Externally, the low flow column can only be identified by “Low Flow”
molded into one side of the column. All the same fittings work with low flow
and full flow columns.
Low Flow Indicators w/ 1/4” Push to Connect Outlet
Column Flow (GPM): .03-.30 GPM
*** Low Flow Column with 3/8” hose barb .03 - .70 GPM
Equivalent Application Rate
On 30” Rows at 6 MPH (1/4” QC): 1-10 GPA
Ball Selection for 30” Rows
GPM GPA Ball
.03-.09 1-3Green Plastic*
.05-.14 2-4Red Plastic*
.10-.18 3-6Maroon Glass
.15-.70 5-10 Stainless Steel (1/2”)
*These balls may float on heavier fertilizers, such as 10-34-0. Use Maroon
Glass in this case.

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 12 Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Floating Ball Flow Indicators–
Metering Orifice Selection for 30” Rows
See www.SurePointag.com for other row spacings
Orifice PSI 4.0 4.5 5.0 5.5 6.0 6.5 7.0
10 0.043 2.15 1.91 1.72 1.56 1.43 1.32 1.23
20 0.061 3.02 2.69 2.42 2.20 2.02 1.86 1.73
30 0.075 3.72 3.31 2.98 2.71 2.48 2.29 2.13
40 0.087 4.29 3.82 3.43 3.12 2.86 2.64 2.45
50 0.097 4.82 4.28 3.85 3.50 3.21 2.97 2.75
60 0.106 5.26 4.67 4.21 3.82 3.50 3.23 3.00
10 0.070 3.46 3.08 2.77 2.52 2.31 2.13 1.98
20 0.098 4.86 4.32 3.89 3.54 3.24 2.99 2.78
30 0.120 5.96 5.30 4.77 4.33 3.97 3.67 3.40
40 0.139 6.88 6.11 5.50 5.00 4.58 4.23 3.93
50 0.156 7.71 6.85 6.17 5.61 5.14 4.74 4.41
60 0.170 8.41 7.48 6.73 6.12 5.61 5.18 4.81
10 0.090 4.47 3.97 3.57 3.25 2.98 2.75 2.55
20 0.127 6.31 5.61 5.05 4.59 4.21 3.88 3.60
30 0.157 7.75 6.89 6.20 5.64 5.17 4.77 4.43
40 0.181 8.94 7.94 7.15 6.50 5.96 5.50 5.11
50 0.202 9.99 8.88 7.99 7.26 6.66 6.15 5.71
60 0.221 10.95 9.73 8.76 7.96 7.30 6.74 6.26
10 0.119 5.91 5.26 4.73 4.30 3.94 3.64 3.38
20 0.169 8.37 7.44 6.69 6.08 5.58 5.15 4.78
30 0.207 10.25 9.11 8.20 7.45 6.83 6.31 5.86
40 0.239 11.83 10.51 9.46 8.60 7.88 7.28 6.76
50 0.267 13.23 11.76 10.58 9.62 8.82 8.14 7.56
60 0.293 14.50 12.89 11.60 10.55 9.67 8.92 8.29
10 0.149 7.36 6.54 5.89 5.35 4.91 4.53 4.21
20 0.210 10.38 9.23 8.31 7.55 6.92 6.39 5.93
30 0.257 12.70 11.29 10.16 9.24 8.47 7.82 7.26
40 0.296 14.67 13.04 11.74 10.67 9.78 9.03 8.39
50 0.332 16.43 14.60 13.14 11.95 10.95 10.11 9.39
60 0.363 17.96 15.96 14.37 13.06 11.97 11.05 10.26
10 0.218 10.78 9.58 8.62 7.84 7.18 6.63 6.16
20 0.307 15.20 13.51 12.16 11.05 10.13 9.35 8.69
30 0.376 18.62 16.55 14.89 13.54 12.41 11.46 10.64
40 0.435 21.51 19.12 17.21 15.64 14.34 13.24 12.29
50 0.486 24.05 21.38 19.24 17.49 16.03 14.80 13.74
60 0.532 26.33 23.40 21.06 19.15 17.55 16.20 15.04
10 0.341 16.87 14.99 13.49 12.27 11.24 10.38 9.64
20 0.481 23.83 21.18 19.06 17.33 15.89 14.66 13.62
30 0.590 29.22 25.97 23.37 21.25 19.48 17.98 16.70
40 0.681 33.73 29.98 26.98 24.53 22.49 20.76 19.27
50 0.762 37.72 33.53 30.17 27.43 25.14 23.21 21.55
60 0.835 41.31 36.72 33.05 30.04 27.54 25.42 23.60
10 0.553 27.38 24.34 21.90 19.91 18.25 16.85 15.64
20 0.782 38.72 34.42 30.98 28.16 25.82 23.83 22.13
30 0.956 47.31 42.05 37.85 34.41 31.54 29.11 27.03
40 1.106 54.76 48.67 43.81 39.82 36.50 33.70 31.29
50 1.239 61.33 54.51 49.06 44.60 40.88 37.74 35.04
60 1.354 67.02 59.58 53.62 48.74 44.68 41.24 38.30
10 0.649 32.11 28.54 25.69 23.35 21.41 19.76 18.35
20 0.920 45.56 40.50 36.45 33.13 30.37 28.04 26.03
30 1.124 55.63 49.45 44.51 40.46 37.09 34.24 31.79
40 1.301 64.39 57.24 51.52 46.83 42.93 39.63 36.80
50 1.451 71.84 63.86 57.47 52.25 47.89 44.21 41.05
60 1.584 78.41 69.70 62.73 57.03 52.27 48.25 44.81
10 0.938 46.43 41.27 37.15 33.77 30.96 28.57 26.53
20 1.319 65.27 58.02 52.22 47.47 43.51 40.17 37.30
30 1.619 80.16 71.26 64.13 58.30 53.44 49.33 45.81
40 1.867 92.43 82.16 73.94 67.22 61.62 56.88 52.82
50 2.088 103.38 91.89 82.70 75.19 68.92 63.62 59.07
60 2.292 113.46 100.85 90.76 82.51 75.64 69.82 64.83
All application rates (gallons/acres) are estimates based on 0-28-0 (10.65 lbs/gallon) at 70 degrees F.
130
MPH
28
35
40
46
52
63
78
98
Gal/Min
28-0-0
107
PumpRight Pressure Recommendations
(with 10 lb check valves):
• Minimum 20 PSI
• Maximum 80 PSI
Tower Electric Pump Pressure
Recommendations (with 4 lb check valves):
• Minimum 10 PSI
• Maximum 30 PSI
Chart is for 28-0-0 Fertilizer @ 70°
• Heavier fertilizers (like 10-34-0) will
have 5-15% less flow than chart
indicates for a certain pressure
• Cold fertilizers will cause system
pressure to increase at a given
application rate.
• Tower Electric Pump Systems will have
reduced flow and increased electrical
current draw due to cold fertilizer
increasing operating pressure. Use the
largest orifice possible for cold
weather operation.
B
Components
Liquid
30” Spacing
Remove top fitting
of each column.
Then push the
metering orifice into
bottom of each
outlet fitting. (This is
not used very
often.)
If using a metering
orifice in the flow
indicator, the orifice
replaces the ball
retainer. If not using
an orifice here, the
ball retainer must
be in place.
Ball
retainer Orifice
or

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 13 Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
The recommended check valve for most PumpRight installations is the
10 lb check with 3/8” hose barbs. This works with 3/8” rubber hose which
SurePoint recommends for most applications over 10 GPA on 30” rows.
The recommended minimum system operating pressure for this check is
20 psi, to ensure all checks open fully.
Check Valves
Complete Assembly
PN 136-10-06HB06HB
101-025038-H133-03-40501-00
Black Cap = 10 PSI Disc Orifice
(optional)
133-03-40160
Gasket
Inlet
Outlet—
RadialLock
Cap
4 lb check valves are typically used with electric pump systems.
SurePoint recommends this valve for use with 1/4” tubing applying up to 10
GPA on 30” rows. The recommended minimum system operating pressure
for this check is 10 psi, to ensure all checks open fully.
133-03-40502-P4
Blue Cap = 4 PSI Disc Orifice
(optional)
133-03-40160
Gasket
Inlet
Outlet—
RadialLock
Cap
4 lb check valve with 1/4” quick connect fittings
Assembly Part Number Description Suggested Uses (30” rows)
136-10-04QC04QC 1/4" QC x 1/4" QC 10 lb < 10 GPA with PumpRight & 1/4” Tubing
136-10-06QC06QC 3/8" QC x 3/8" QC 10 lb With 3/8” tubing plumbing
136-04-06HB06HB 3/8" HB x 3/8" HB 4 lb > 10 GPA with Electric Pumps
136-04-08HB08HB 1/2" HB x 1/2" HB 4 lb > 50 GPA with PumpRight
136-10-08HB08HB 1/2" HB x 1/2" HB 10 lb > 50 GPA with PumpRight
Special Purpose Check Valve Assemblies
132-40435-05
Complete Assembly
PN 136-04-04QC04QC
10 lb check valve with 3/8” hose barbs B
Components
Liquid
132-40424-05
FLOW
FLOW

396-4953Y1 SurePoint PumpRight for Sentinel Rate Control 14 Revised 05/13/2022
© 2010-2022 SurePoint Ag Systems Inc.
Colored Disc Orifice Chart for 30” rows
Download the SurePoint Flow Calculator App for iPad B
Components
Liquid
PumpRight Pressure
Recommendations (with 10 lb check
valves):
• Minimum 20 PSI
• Maximum 80 PSI
Tower Electric Pump Pressure
Recommendations (with 4 lb check
valves):
• Minimum 10 PSI
• Maximum 30 PSI
Chart is for 28-0-0 Fertilizer @ 70°
• Heavier fertilizers (like 10-34-0) will
have 5-15% less flow than chart
indicates for a certain pressure
• Cold fertilizers will cause system
pressure to increase at a given
application rate.
• Tower Electric Pump Systems will
have reduced flow and increased
electrical current draw due to cold
fertilizer increasing operating
pressure. Use the largest orifice
possible for cold weather
operation.
PSI 4.0 4.5 5.0 5.5 6.0 6.5 7.0
10 0.033 1.62 1.44 1.30 1.18 1.08 1.00 0.93
20 0.046 2.28 2.02 1.82 1.66 1.52 1.40 1.30
30 0.057 2.80 2.49 2.24 2.04 1.87 1.73 1.60
40 0.065 3.24 2.88 2.59 2.36 2.16 1.99 1.85
50 0.073 3.64 3.23 2.91 2.64 2.42 2.24 2.08
60 0.081 3.99 3.54 3.19 2.90 2.66 2.45 2.28
10 0.050 2.50 2.22 2.00 1.82 1.66 1.54 1.43
20 0.072 3.55 3.15 2.84 2.58 2.37 2.18 2.03
30 0.088 4.34 3.85 3.47 3.15 2.89 2.67 2.48
40 0.101 4.99 4.44 4.00 3.63 3.33 3.07 2.85
50 0.112 5.56 4.95 4.45 4.05 3.71 3.42 3.18
60 0.124 6.13 5.45 4.91 4.46 4.09 3.77 3.50
10 0.070 3.46 3.08 2.77 2.52 2.31 2.13 1.98
20 0.098 4.86 4.32 3.89 3.54 3.24 2.99 2.78
30 0.120 5.96 5.30 4.77 4.33 3.97 3.67 3.40
40 0.139 6.88 6.11 5.50 5.00 4.58 4.23 3.93
50 0.156 7.71 6.85 6.17 5.61 5.14 4.74 4.41
60 0.170 8.41 7.48 6.73 6.12 5.61 5.18 4.81
10 0.094 4.64 4.13 3.71 3.38 3.10 2.86 2.65
20 0.132 6.53 5.80 5.22 4.75 4.35 4.02 3.73
30 0.162 8.02 7.13 6.41 5.83 5.34 4.93 4.58
40 0.187 9.24 8.22 7.39 6.72 6.16 5.69 5.28
50 0.209 10.34 9.19 8.27 7.52 6.89 6.36 5.91
60 0.228 11.30 10.05 9.04 8.22 7.53 6.95 6.46
10 0.119 5.91 5.26 4.73 4.30 3.94 3.64 3.38
20 0.169 8.37 7.44 6.69 6.08 5.58 5.15 4.78
30 0.207 10.25 9.11 8.20 7.45 6.83 6.31 5.86
40 0.239 11.83 10.51 9.46 8.60 7.88 7.28 6.76
50 0.267 13.23 11.76 10.58 9.62 8.82 8.14 7.56
60 0.293 14.50 12.89 11.60 10.55 9.67 8.92 8.29
10 0.149 7.36 6.54 5.89 5.35 4.91 4.53 4.21
20 0.210 10.38 9.23 8.31 7.55 6.92 6.39 5.93
30 0.257 12.70 11.29 10.16 9.24 8.47 7.82 7.26
40 0.296 14.67 13.04 11.74 10.67 9.78 9.03 8.39
50 0.332 16.43 14.60 13.14 11.95 10.95 10.11 9.39
60 0.363 17.96 15.96 14.37 13.06 11.97 11.05 10.26
10 0.218 10.78 9.58 8.62 7.84 7.18 6.63 6.16
20 0.307 15.20 13.51 12.16 11.05 10.13 9.35 8.69
30 0.376 18.62 16.55 14.89 13.54 12.41 11.46 10.64
40 0.435 21.51 19.12 17.21 15.64 14.34 13.24 12.29
50 0.486 24.05 21.38 19.24 17.49 16.03 14.80 13.74
60 0.532 26.33 23.40 21.06 19.15 17.55 16.20 15.04
10 0.351 17.39 15.46 13.91 12.65 11.59 10.70 9.94
20 0.496 24.57 21.84 19.66 17.87 16.38 15.12 14.04
30 0.608 30.09 26.75 24.08 21.89 20.06 18.52 17.20
40 0.702 34.74 30.88 27.79 25.26 23.16 21.38 19.85
50 0.785 38.86 34.54 31.08 28.26 25.90 23.91 22.20
60 0.859 42.53 37.81 34.03 30.93 28.36 26.18 24.31
10 0.506 25.06 22.27 20.05 18.22 16.70 15.42 14.32
20 0.715 35.39 31.46 28.32 25.74 23.60 21.78 20.23
30 0.876 43.37 38.55 34.69 31.54 28.91 26.69 24.78
40 1.009 49.94 44.39 39.95 36.32 33.29 30.73 28.54
50 1.133 56.07 49.84 44.86 40.78 37.38 34.51 32.04
60 1.239 61.33 54.51 49.06 44.60 40.88 37.74 35.04
10 0.686 33.95 30.18 27.16 24.69 22.63 20.89 19.40
20 0.973 48.19 42.83 38.55 35.04 32.12 29.65 27.53
30 1.186 58.70 52.18 46.96 42.69 39.13 36.12 33.54
40 1.372 67.90 60.35 54.32 49.38 45.27 41.78 38.80
50 1.531 75.78 67.36 60.63 55.12 50.52 46.64 43.30
60 1.681 83.23 73.98 66.58 60.53 55.49 51.22 47.56
Brown
(41)
Green
(110)
Orange
(46)
Maroon
(52)
Red (63)
Blue (80)
Yellow
(95)
MPH
Pink (24)
Gray (30)
Black (35)
Gal/Min
28-0-0
Orifice
Color
(Approx
Size)
30” Spacing
Colored Disc Orifice assembles under
the check valve cap in most cases.
(Drop the orifice with the hole down
into the cap, then put the gasket on top
of it.) The orifice can also be installed
in a manifold (common on grain drills).
Disc Orifice
Gasket
FLOW 1/4 Turn Cap is Outlet
This manual suits for next models
3
Table of contents
Popular Water Pump manuals by other brands

WIKA
WIKA CPP 700-H operating instructions

Pentair Jung Pumpen
Pentair Jung Pumpen US Series instruction manual

Robot Pumps
Robot Pumps RW-R-SERIES Operation & maintenance manual

EINHELL
EINHELL NGP 70 Original operating instructions

BUSCH
BUSCH Seco SV 1010 C instructions

EINHELL
EINHELL GC-DW 1045 N operating instructions