t.a.c. Satchwell Climatronic CSC5252 User manual

Satchwell Climatronic
CSC5252 & CSC5352 Compensator User’s Guide
SatchwellTM

Copyright Notice
We at TAC have tried to make the information contained in this manual as accurate and reliable as
possible. Nevertheless, TAC disclaims any warranty of any kind, whether express or implied, as to any
matter whatsoever relating to this manual, including without limitation the merchantability or fitness for
any particular purpose. TAC will, from time to time, revise the product(s) described in this manual and
reserves the right to make such changes without obligation to notify the purchaser. In no event shall TAC
be liable for any indirect, special, incidental, or consequential damages arising out of purchase or use of
this manual or the information contained herein.
Do not use the product for any other purposes than those indicated in this manual.
Only licensed users of the product and the document are permitted to use this manual or any
information therein. Distribution, disclosure, copying, storing or use of the product, the information or
the illustrations in this manual on the part of non-licensed users, in electronic or mechanical form, as a
recording or by other means, including photocopying or information storage and retrieval systems,
without the express written permission of TAC, will be regarded as a violation of copyright laws and is
strictly prohibited.
© 2008, TAC. All rights reserved.

CONTENTS
1. INTRODUCTION 5
2. INSTALLATION AND COMMISSIONING 6
2.1. LOCATION OF CONTROLLER 6
2.2. WIRING PRECAUTIONS 6
2.3. COMPATIBLE SENSORS 7
2.4. CHANGING SENSORS 7
2.5. USING ADJUSTABLE SPACE TEMPERATURE SENSORS 7
2.6. COMMISSIONING 8
2.7. RELOADING THE DEFAULT VALUES 11
3. APPLICATIONS 12
3.1. COMPENSATED VALVE CONTROL 12
3.1.1. Basic Wiring Diagrams for Compensated Valve Control 13
3.2. COMPENSATED BOILER CONTROL 14
3.2.1. Basic Wiring Diagram for Compensated Boiler Control 15
3.3. DISTRICT HEATING SYSTEMS 16
3.3.1. Basic Wiring Diagram for District Heating Applications 18
3.4. ACTUATOR OVERRIDE FOR MAINS OUTPUT APPLICATIONS 19
3.5. ACTUATOR OVERRIDE FOR 24VAC OUTPUT APPLICATIONS 19
4. FACIA AND DISPLAY 20
4.1. MANUAL OVERRIDE SWITCH 21
4.2. CONTROLLER MODES 22
4.2.1. Review Mode 22
4.2.2. Quick Set Mode 22
4.2.3. Fine Tune Mode 22
4.2.4. Setting the Time Schedule (CSC 5352 Only) 22
4.3. FACIA PRINTING, REVIEW AND QUICK SET MODE 23
4.3.1. Review Mode 23
4.3.2. Setting the Default Display for Review Mode 23
4.4. ACCESSING AND EXITING QUICK SET MODE 24
4.4.1. How to Set Values 25
4.4.2. To Select the Economy Mode (CSC 5352 Only) 26
CSC USER GUIDE October, 03
3 of 42

4.5. OVERLAY CARD PRINTING, FINE TUNE MODE ONLY 26
4.5.1. Entering and Exiting the Fine Tune Mode 27
4.5.2. To Adjust the Economy Mode (CSC 5352 Only) 30
5. SPECIFICATION 31
5.1. CHANGING THE BATTERY 32
6. FREQUENTLY USED FUNCTIONS AND USER SETTING
RECORD TABLES 32
6.1. MANUAL OVERRIDES 32
6.2. REVIEW MODE 33
6.3 HOW TO ENTER QUICK SET MODE 33
6.3.1. Economy Mode (CSC 5352 Only) 35
6.4. ENTERING AND EXITING THE FINE TUNE MODE 35
6.5. TIME SCHEDULE 40
October, 03 CSC USER GUIDE
4 of 42

1. INTRODUCTION
The CSC controller is designed to be simple to install and easy to use. The
controller is used in simple plants typically in schools, libraries and large domestic
installations. It may be installed either within a control panel or can be wall mounted.
The user can recall, display and adjust parameters quickly and easily, prompted by
the controller display. The facia has clearly labelled push-buttons for use when
setting the controller. There is an overlay card which must be placed over the
controller display for use in the Fine Tune Mode. A rotary selector switch is provided
to enable overrides to be quickly and easily applied.
The CSC controls the temperature of air in ducts or water flowing to radiators
throughout the building or zone. Each independent zone will need its own CSC
controller and associated equipment.
A 3 way mixing valve is normally used to control the water temperature by mixing the
cooler return water with the hot water from the heat source. Because boilers are
used to supply heat to the domestic hot water as well as heating radiators the CSC
must be used with a mixing valve. Where the heating system is independent the
boiler may be directly controlled by turning it on and off to control the output or flow
temperature.
The temperature of the flow water is monitored to ensure that desired value is
maintained to maximise energy savings. The hot water can be supplied by a boiler
or non-storage calorifier on a district heating system. The set point of the flow water
is determined mainly by the outside air temperature. As the outside air temperature
decreases the radiator water temperature is increased to compensate for heat loss.
This is the basic principal of how a compensator works. A space temperature
sensor can be connected to influence the flow temperature if required. The space
sensor allows the set point of the flow water to be increased or reduced as the space
temperature changes.
The CSC can only control one item of plant (either a valve or a boiler).
The CSC is shipped with standard (defaults) values for parameters. These default
settings are used so that in most cases only a minimal number of parameters need
to be amended to get the best out of the controller. It is important, however, that you
tune the CSC to your control system to get the best out of it. Typical default values
that should be checked/set are:-
•Current time and Time-schedule (CSC 5352 only).
•Valve/Boiler application selection.
•Room Influence Operation.
•Night Set Back Operation (CSC 5352 only).
•Frost Logic and Set Point (CSC 5352 only).
•Pump Exercise (CSC 5352 only).
•Pump Overrun (CSC 5352 only).
•Controller tuning.
CSC USER GUIDE October, 03
5 of 42

2. INSTALLATION AND COMMISSIONING
The CSC should be installed and commissioned by a competent technician.
DO NOT SWITCH ON THE POWER SUPPLY UNTIL THE COMMISSIONING
PROCEDURES HAVE BEEN COMPLETED.
2.1. LOCATION OF CONTROLLER
The controller must be installed in a position which is fairly clean and free from damp
and condensation.
Temperature and humidity limits must be obeyed.
Ambient Operating Temperature: 0°C to 50°C
Operating Humidity: 0 to 95% RH non condensing
A minimum of 150 mm clearance is required around the controller to allow access
for mounting, wiring, servicing and to avoid electrical interference from other devices
such as contactors.
2.2. WIRING PRECAUTIONS
•On new installations all sensor cables must be screened with the screens
connected separately to the 0V earth point provided. An MICC earth plate is
provided for use if MICC cable is used.
•When upgrading a CSC or CXC installation it is usually possible to use the
existing unscreened sensor wiring as long as the cable run is less than 100
metres and is sited more than 75mm from mains wiring runs.
•The mains supply, 24Vac output, relay and triac output wiring must be run
separately from all the controller sensor and override inputs.
•The controller must be located as far away as possible (minimum 150mm) from
any contactors or switches and their cables. This is to avoid any interference to
the controller.
•No connections to the controller should be made whilst power is applied.
October, 03 CSC USER GUIDE
6 of 42

2.3. COMPATIBLE SENSORS
There are a large number of sensors that are compatible with the CSC.
It is not possible to mix old generation and ‘T’ type sensors on the CSC.
The compatible sensors are listed below along with their resistance type number’s.
The first time the CSC is powered up it will automatically configure itself to the
sensor type connected (“old generation” or “T Type”).
2.4. CHANGING SENSORS
If a CSC connected to old generation sensors is subsequently equipped with a set of
“T Type” sensors it is necessary to manually select the sensor type as 5 (T Type).
Remember that you cannot mix “T Type” and old generation sensors on the same
CSC. “T Type” sensors should be used on all new installations.
2.5. USING ADJUSTABLE SPACE TEMPERATURE SENSORS
Adjustable room sensors do not change the CSC controllers programmed set point,
they fool the controller into believing that the space temp is above or below the ideal
space temperature. The CSC is primarily a water temperature controller and the
space sensor only provides an influence over the flow temperature as a way to
modify the actual space temperature. Where these sensors are used the controller
may be forced into a Frost condition is adjustment is to great, e.g. asking for 30°C in
the space the controller may think its 10°C or less. For this reason it is
recommended that the low limit space setting is reduced to its minimum when using
adjustable sensors to avoid confusion. Non adjustable space sensors will allow
automatic frost protection to take place.
"T TYPE" SENSORS
Sensor Sensor Type Resistance Type Temperature
Range
DRT 3451, 3453 Room 5 –5 to +40°C
DWT 1701, 1702 Water 5 –10 to +120°C
DST 1601, 1603 Water (strap on) 5 +5 to +120°C
DOT 2301 Outside 5 –40 to +40°C
CSC USER GUIDE October, 03
7 of 42

2.6. COMMISSIONING
ENSURE THE MAINS POWER SUPPLY IS OFF AND THAT ANY OTHER POWER
SUPPLIES TO AND FROM THE CSC ARE ISOLATED.
1. Undo the central case fixing screw and separate the case to gain access to the
terminals.
2. Check that all wiring is correctly connected to the terminals. This should be
done using the connection or application diagram for reference.
3. The battery supplied should now be fitted.
4. Reassemble the controller case and securely tighten the central fixing screw.
5. Apply mains power to the controller, the display will show “reset” followed by the
controller firmware number:
6. The controller will then go into review mode.
7. Set the real time clock. (See the Quick Set mode for details on setting the clock).
8. Complete the configuration via the Quick-Set and Fine-Tune parameters.
Which Parameters to Change
The CSC is programmed with typical defaults to suit most applications. These
should always be checked to maximise energy savings and comfort. Depending on
the model being used the following table show which parameters are most likely to
be in need of adjustment to allow correct and safe operation.
CSC
5352
CSC
5252
Why Do You Need to Alter?
Quick
Set
Mode
Time & Day üTo enable correct plant time
switching.
Low Outside
Temperature
üTo protect the plant from low
outside temperatures if required.
Flow High
Limit
üThis setting sets the highest
possible flow temperature that the
CSC will allow. Must be used in
sensitive applications such as
under floor heating.
October, 03 CSC USER GUIDE
8 of 42

CSC
5352
CSC
5252
Why Do You Need to Alter?
Fine
Tune
Mode
IA Integral
Action
üüAllows the CSC to react to
temperature deviations.
PB Proportional
Band
üAllows the CSC to position the
value according to the error.
NSB Action üDo you want heating during the
relaxed periods:
0 = (No Heating)
1 = (Yes both periods)
2 = (Yes to 1st Off period, No to
2nd Off period)
INF Room
Influence
Mode
üHow do you want the Space
Temperature to influence the Flow
Temperature.
Frost Logic üDo you want to use UK or
European Frost Logic.
Valve or
Boiler
üAre you controlling a valve or boiler.
SVd Set Value
Day Origin
üIf you have a Space Sensor what
will be your target Space
temperature for the Day Period.
SVn Set Value
Night Origin
üIf you have a Space Sensor what
will be your target Space
temperature for the Night Period.
Low Space
Temperature
üIf you have a non-adjustable Space
Sensor what is the lowest
permissible Space Temperature.
Stroke Actuator
Stroke
üHow long does the actuator take to
run from fully closed to fully open in
seconds.
OTHER SETTINGS - CSC 5352
Set the time schedule to complete the basic commissioning procedure.
NOTE:
If you have set the above they should not need further adjustment given your
application. Always check periodically as a part of ongoing maintenance program.
Ratios and ECO functionality must be set to maximise energy savings.
CSC USER GUIDE October, 03
9 of 42

2.7. ADDITIONAL CONTROL LOGIC INFORMATION
Room Influence Operation.
If a room sensor is used you can choose how it influences the flow temperature. If
you select 0 there is no influence. If you select 1 then room influence will adjust the
flow temp up and down during the day but only down during the off periods. If you
select 2 the flow temp is only influenced to lower the set point during both day and
night periods. The fixed ratio is 3:1, both day and night have set points for space
temperature.
Night Set Back Operation (CSC 5352 Only).
When the CSC turns off you can select what happens to the heating. If you set to “0”
the heating will turn off during both “off” periods. This means that there will be no
heating during the relaxed periods, the pump will turn off and the valve, if used, will
close. If you set the value to “1” this means that the heating will run during both off
periods with the flow temp reduced by the setting. If the setting = 2 then the
heating will control to NSB during the 1st off period but turn off for the 2nd off period.
The controller can be externally overridden to Night Set Back by the use of an
external contact if required.
•Frost Logic and Set Point (CSC 5352 Only).
The CSC has three stages of frost. Stage 1 is outside air temperature. This value is
adjustable by you. The CSC is constantly monitoring the outside air temp and if it
falls below the limit when the heating is off then the CSC will a) turn the pump on
(UK Logic) b) turn on the pump and control to the NSB requirement. During the
event of frost out of hours the controller will display “Auto 1” to indicate that the
controller is working correctly.
Low Flow Temperature (Stage Two Frost)
If the flow water temperature falls below 5°C then the valve will open and the boiler
and pump will start. The plant will remain in Boost control for a 1⁄2hour period. This
should ensure a sufficient rise in return water temperature and remove the frost
condition. In the event of another frost condition the control will cycle as stated. The
controller will display “Auto 2” during this frost period.
Low Space Temperature (Stage Three Frost)
If a space temperature sensor is fitted then this will also provide the third stage frost
protection in addition to room influence. The low space temp setting will open the
valve and energise the pump until the space temperature has increased above the in
built hysteresis of 2°C (not adjustable) under boost conditions. The default low space
temperature setting is set to 10°C and this will be adjustable (–10 to 30°C). Whilst in
this condition display will show “Auto 3”. An example of this occurrence could be a
window being broken/left open in the area being controlled. As the space
temperature can increase the flow temperature during the day this alarm should only
occur when the plant is off or in the NSB mode. The low space temperature setting
can be adjusted to –10 to remove the function if required. This will allow the input to
be used for other influence applications if required.
Pump overrun will be in operation for the programmed period after any of the frost
conditions have cleared.
October, 03 CSC USER GUIDE
10 of 42

The CSC 5252 does not include any frost protection as the controller does not
directly control the pump. Frost protection must be provided by external controls
such as thermostats and interlocked accordingly to the plant and actuator.
•Pump Exercise (CSC 5352 Only)
If the plant has not been used for any 7 day period then the plant will be exercised to
prevent pump and valve seizure. This period setting is not adjustable but can be
turned off by putting the controller into the off condition or any other manual position
by using the rotary knob. Exercise will only take place when the controller is in the
Auto or Standby condition.
•Pump Overrun (CSC 5352 Only)
Used to dissipate residual heat in the non-storage calorifier or directly controlled
boiler after firing. The pump run on time is adjustable to suit plant types and needs to
be set to avoid nuisance high limit tripping.
•Controller Tuning
Adjust the Proportional Band and Integral Action to ensure the most accurate and
efficient response. Check control loop stability at frequent intervals as a part of an on
going maintenance program. This will ensure maximum energy savings and
component life.
•Flow High Limit
Depending on your application it may be necessary to limit the maximum water
temperature that the CSC will provide to the heat emitting elements. This feature
should be employed on non-storage calorifier applications and under floor heating
applications.
2.8. RELOADING THE DEFAULT VALUES
This procedure only needs to be carried out if you need to reload the controller
default values. The controller will also automatically configure itself to the sensors
connected to it.
The following procedure will reload the CSC default values.
THIS WILL DELETE ALL YOUR EXISTING USER SETTINGS.
1. Switch OFF the power.
2. Press and hold the “Enter” key. Switch the power ON.
3. The controller display will show “reset” followed by the firmware number.
4. The controller will now display “dflts”. Release the “Enter” key.
5. The controller display will show “reset” again followed by the firmware number.
6. The controller will then go into review mode.
7. Enter your new Parameters and update your setting record sheet in the back of
this guide.
CSC USER GUIDE October, 03
11 of 42

3. APPLICATIONS
3.1. COMPENSATED VALVE CONTROL
This compensator application operates a 3 port mixing valve to control the flow
temperature of the system based on the outside temperature. A room sensor is
optional and is used to trim the flow temperature and not to control it. The way room
influence works can be selected to suit your needs. It need not be used. The flow
temperature can be adjusted by 3ºC for every 1ºC the room temperature is above or
below the daytime space temp set value (SVd).
If the CSC 5352 is used then the clock determines whether the compensator
operates in day or Night Set-Back (NSB) mode. The CSC can be set to allow the
heating i.e. pump, valve etc. to run at reduced set points or turn off during the off
periods. When in NSB mode the action of Room Influence is adjusted to work only in
a negative fashion as to reduce the flow temperature. The flow temperature will be
lowered by 3°C for every 1°C the room temp is above the relaxed set point (SVn).
The compensator has 2 compensation ratios and a high limit function to prevent
excessive set points occurring.
Out of hours, If the outside temperature drops below an adjustable frost setting,
defaulted to 0°C, the pump is enabled and “Auto 1” is displayed on the controller.
The CSC will resume normal operation when the outside temperature increases by
2°C. If a space sensor is used then this will also provide frost protection to protect
the building fabric. The low space temperature is adjustable but is normally set to
10°C. If this limit is passed then the heating will come on in boost to ensure the
fastest possible relief. “Auto 3” will be displayed on the CSC during this period. The
frost condition will be removed when the space temperature has risen by 2°C. If for
any reason, the flow temperature should fall below 5°C the CSC will act to remove
the possibility of frost. The controller will start the pump and open the valve to raise
the water temperature of the system, the CSC will remain in this condition for 30
minutes. When this event occurs during a standby period if not day or NSB, the
CSC will display "Auto 2" for the period. If your CSC doesn’t have a time clock, then
Frost Protection is not included as the controller does not control the pump. All Frost
Protection must be provided by other interlocked devices such as thermostats.
If under floor heating is used, please remember to check the high limit setting so as
not to allow excessive flow temperatures.
Pump
Time switch
version only
(Optional)
(Flow
Temp)
Boiler
Fig.1
* A control and safety high limit thermostat
must be used on the boiler
October, 03 CSC USER GUIDE
12 of 42

3.1.1. Basic Wiring Diagrams for Compensated Valve Control
Ensure that 34 is
always hard wired to
35, for all 24Vac
actuators only
Links 7-8 and/or 9-10 must
be removed if Set-up
and/or Night Set Back is
used.
Set-Up/Boost
Night Set-Back
Pump
Time-switch
version only
230Vac Actuator
ARM Mk 2 Actuator
1 = Red
2 = Blue
3 = Black
Links 7-8 and/or 9-10 must
be removed if Set-up
and/or Night Set Back is
used.
Set-Up/Boost
Night Set-Back
Pump
Time-switch
version only
24Vac Actuator
Fig.2
Fig.3
ARX Mk 2 Actuator
1 = Red
2 = Blue
3 = Black
CSC USER GUIDE October, 03
13 of 42

3.2. COMPENSATED BOILER CONTROL
This compensator application switches the boiler to control the flow temperature of
the system based on the outside temperature. A room sensor is optional and is used
to trim the flow temperature and not to control it. The way room influence works can
be selected to suit your needs. It need not be used. The flow temperature can be
adjusted by 3ºC for every 1ºC the room temperature is above or below the daytime
space temp set value (SVd).
If the CSC 5352 is used then the clock determines whether the compensator
operates in day or Night Set-Back (NSB) mode. The CSC can be set to allow the
heating i.e. pump, valve etc., to run at reduced set points or turn off during the off
periods. When in NSB mode the action of Room Influence is adjusted to work only in
a negative fashion as to reduce the flow temperature. The flow temperature will be
lowered by 3°C for every 1°C the room temp is above the relaxed set point (SVn).
The compensator has 2 compensation ratios and a high limit function to prevent
excessive set points occurring.
Out of hours, If the outside temperature drops below an adjustable frost setting,
defaulted to 0°C, the pump is enabled and “Auto 1” is displayed on the controller.
The CSC will resume normal operation when the outside temperature increases by
2°C. If a space sensor is used then this will also provide frost protection to protect
the building fabric. The low space temperature is adjustable but is normally set to
10°C. If this limit is passed then the heating will come on in boost to ensure the
fastest possible relief. “Auto 3” will be displayed on the CSC during this period. The
frost condition will be removed when the space temperature has risen by 2°C. If for
any reason, the flow temperature should fall below 5°C, the CSC will act to remove
the possibility of frost. The controller will start the pump and open the valve to raise
the water temperature of the system, the CSC will remain in this condition for 30
minutes. When this event occurs during a standby period if not day or NSB, the
CSC will display "Auto 2" for the period. If you are using the CSC 5252 then Frost
protection is not included as the controller does not control the pump. All frost
protection must be provided by other interlocked devices such as thermostats.
If under floor heating is used please remember to check the high limit setting as not
to allow excessive flow temperatures.
Pump
Time-switch
version only
(Optional)
(Flow
Temp)
Boiler
Fig.4
* A safety high limit thermostat
must be used on the boiler
October, 03 CSC USER GUIDE
14 of 42

3.2.1. Basic Wiring Diagram for Compensated Boiler Control
Fig.5
Fig.6
Links 7-8 and/or 9-10 must
be removed if Set-up
and/or Night Set Back is
used.
Set-Up/Boost
Night Set-Back
Pump
Time-switch
version only
230Vac Boiler Output
Boiler
Links 7-8 and/or 9-10 must
be removed if Set-up
and/or Night Set Back is
used.
Set-Up/Boost
Night Set-Back
Pump
Time-switch
version only
24Vac Boiler Output
Boiler
CSC USER GUIDE October, 03
15 of 42

3.3. DISTRICT HEATING SYSTEMS
This application operates a two or three port valve to control the secondary water
temperature of the heat exchanger based on the outside temperature. In
Scandinavian applications a DWT sensor can be connected to the CSC via the input
used for Room Influence. The CSC will use the DWT sensor to control the Primary
Return Temperature. This will ensure that the permitted limits will not be exceeded.
Space Frost Protection or room influence cannot be offered if the maximum return
sensor is used.
Where the primary medium could enable extremely high secondary water
temperatures, a dedicated safety circuit is required.
If a clock version CSC is used then the clock determines whether the compensator
operates in day or Night Set-Back (NSB) mode. The CSC can be set to allow the
heating i.e. pump, valve etc., to run at reduced set points or turn off during the off
periods. When in NSB mode the action of Room Influence is adjusted to work only
in a negative fashion as to reduce the flow temperature. The flow temperature will
be lowered by 3°C for every 1°C the room temperature is above the relaxed set point
(Svn). The compensator has 2 compensation ratios and a high limit function to
prevent excessive set points occurring.
Out of hours, if the outside temperature drops below an adjustable frost setting,
defaulted to 0°C, the pump is enabled and "Auto 1" is displayed on the controller.
The CSC will resume normal operation when the outside temperature increases by
2°C. If a space sensor is used then this will also provide frost protection to protect
the building fabric. The low space temperature is adjustable but is normally set to
10°C. If this limit is passed then the heating will come on in boost to ensure the
fastest possible relief. "Auto 3" will be displayed during this period. The frost
condition will be removed when the space temperature has risen by 2°C. If for any
reason, the flow temperature should fall below 5°C the CSC will act to remove the
possibility of frost. The controller will start the pump and open the valve to raise the
water temperature of the system, the CSC will remain in this condition for 30
minutes. If the water frost event occurs during a standby period, the CSC will
display "Auto 2".
If your CSC does not have a time clock then Frost Protection is not included as the
controller does not control the pump. All frost protection must be provided by other
interlocked devices such as thermostats.
If under floor heating is used please remember to check the high limit setting as not
to allow excessive flow temperatures.
The INF setting in Fine Tune Mode must be set to 3 to enable the max. return
application and settings.
October, 03 CSC USER GUIDE
16 of 42

† Room Influence or Max. Return Sensor.
Not both. Max. Return Sensor used for
controlling primary water temperature in
Scandinavian Public Systems.
Pump
Time switch
version only
(Optional)
(Flow
Temp)
Boiler
Fig.7
* A safety high
thermostat may need
to be used on the
secondary side to
operate the safety
valve.
†
(Optional)†
CSC USER GUIDE October, 03
17 of 42

3.3.1. Basic Wiring Diagram for District Heating Applications
Fig.8
Fig.9
Ensure that 34
is always hard
wired to 35, for
all 24Vac
actuators only
Links 7-8 and/or 9-10 must
be removed if Set-up
and/or Night Set Back is
used.
Set-Up/Boost
Night Set-Back
Pump (Clock
Version only)
230Vac Boiler Output
Links 7-8 and/or 9-10 must
be removed if Set-up
and/or Night Set Back is
used.
Set-Up/Boost
Night Set-Back
Pump (Clock
Version only)
24Vac Boiler Output
October, 03 CSC USER GUIDE
18 of 42

3.4. ACTUATOR OVERRIDE FOR MAINS OUTPUT APPLICATIONS
3.5. ACTUATOR OVERRIDE FOR 24VAC OUTPUT APPLICATIONS
When upgrading an old CSC or
CSC this method reproduces the
4-5 link override that was used.
Override Open Override Close
Single pole relay
or contact
Single pole relay
or contact
Fig.10
Open Close Open Close
When upgrading an old CSC or
CSC this method reproduces the
4-5 link override that was used.
Override Open Override Close
Single pole relay
or contact
Single pole relay
or contact
Fig.11
Open Close Open Close
CSC USER GUIDE October, 03
19 of 42

4. FACIA AND DISPLAY
The display will show the time, temperature and the values of various parameters.
The arrows point to the appropriate graphic on the facia to highlight the currently
active function(s).
The five push-buttons and an eight way rotary switch on the facia are for setting and
overriding the controller. The arrangement of the facia is as follows (time switch
version shown):
The five buttons have the following functions:
Calendar Button: Selects the mode that allows setting of the Time Switch
functions.
Tuning Button: Selects the mode that allows setting of the controller
parameters.
Enter Button: Enter button for confirming the entry of parameters.
Plus Button: To increase the value or move clockwise to the next
function. Holding the button down will cause it to auto
repeat.
Minus Button: To decrease the value or move anti clockwise to the next
function. Holding the button down will cause it to auto
repeat.
Fixing
Screw
Time-switch
version only
Liquid
Crystal
Display
Rotary
Override
Switch
Fig.12
Time-switch
version only
Setting
Buttons
October, 03 CSC USER GUIDE
20 of 42
This manual suits for next models
1
Table of contents
Other t.a.c. Thermostat manuals