Tamas Z-Block User manual

Installaon and Assembly Guide
Z-Block
Hydronic Zoning Block
www.tamashydronic.com
Tamas Hydronic Systems
User Guide

Z-Block Manual version 1.3
Page 2
Tamas Hydronic Systems
Table of Contents
Introduction 3
Components 4
Operation 5
Technical Data 6 - 7
Applications 8 - 13
Assembly 14 - 17
Included Components 18
Optional Accessories 19
Limited Warranty 20
Table of Contents
* Note:
The following parts lists and applicaon drawings are general samplings. Each
conguraon dictates the required components. See the Technical Data secon of the
manual for specic informaon on each part in your parcular variaon of the Tamas
Zone Block.
This User Guide is Applicable to:
Tamas Z-Block
025-0050 Z-Block ( Tamas Zone Block Kit) Box Product

Tamas Hydronic Systems Inc. Page 3
Tamas Hydronic Systems
Overview
The Tamas Z-Block is a device combining a hydraulic separator and
distribuon manifold pump header used in heang systems. The Z-Block
is an expandable zone pumping system, designed to work as a boiler
pump, injecon pump, or as a zoning pump.
It can be expanded with other Zone Blocks to suit a variety of residenal,
commercial and Industrial applicaons. The Z-Block is easy to assemble
and install, making it suitable for all skill levels. This unique design allows
the Z-Block to be installed in a variety of small spaces for new installaons
or retro-ts.
Main Features
• Fully customizable, with the opon to add pieces to accommodate
for specic job requirements
• Expandable for any residenal applicaon
• Adaptable, the 1 ¼” diameter manifold can accomodate large ow
rates
• Flexible, it can be used as an injecon pump, boiler pump, zone pump
• ETL approved
Introduction

Z-Block Manual version 1.3
Page 4
Tamas Hydronic Systems
Components
1
6
89
10
7
34
2
5
1UPS 15-58 Three Speed Pump
2Supply/Return Manifold
3Built-in Autovent
4Pressure & Temperature Sensor
(Oponal)
51 1/4” High Flow Rate Adapter with
Sweat Connecons
6Z-Block Expansion Connecons
7End Cap with Sensor Port
83/4” Sweat Connecons
9Bult-in Purge Valve
10 Built-in Check Valve
Components

Tamas Hydronic Systems Inc. Page 5
Tamas Hydronic Systems
Operation
System
Supply
System
Return
Zone Return
In
Zone Supply
Out
1
2
3
4
System
Supply
System
Return
Zone Return
In
Zone Supply
Out
1
2
3
4
Operation
The Z-Block distribuon manifold works in the following way: The heang uid
from the heat emier enters via connecon 1, and returns via connecon 2.
Delivery to the zone system is via the lower right connecon on the Z-Block. The
uid returning from the zone system (connecon 3) ows towards the pump
(connecon 4).

Z-Block Manual version 1.3
Page 6
Tamas Hydronic Systems
Technical Data
Zone/Boiler Pump
Technical Data
Speed Number: 3
Max-Flow: 17.2 US gpm
Head Max: 19.36
Max. Operang Pressure: 45 psi
Max. Temperature: 203°F (95°C)
Pumped Liquid: Water or Ethylene Glycol up to 50% Concentrate
Electrical Data
Main Frequency: 60 Hz
Rated Voltage: 1 x 115 V
Current in Speed 1: 0.55 A
Current in Speed 2: 0.66 A
Current in Speed 3: 0.75 A
*Dimensions are in Inches [Millimeters]
[130]
5.118
[115]
4.528
[35]
1.378
[40]
1.575
[56]
2.205
[198.80]
7.827
[200.45]
7.892
Performance
HI
MED
LOW
20
18
16
14
12
10
8
6
4
2
0
0 2 4 6
GPM
Ft
8 10 12

Tamas Hydronic Systems Inc. Page 7
Tamas Hydronic Systems
Technical Data
Mixed OutHigh Temp
In
Low Temp
In
Low Temp
Out
Pressure drop [kPa]
100
50
20
10
5
00300200105015 20
Flow
[m3/h] [l/min] [l/s] Kvs m 3/h
2
1
0.5
0.2
0.1
0.05
5
2
1
0.5
0.2
10
4.5 – 4.8*
1.5 – 1.6
1.2 – 1.3
2.2 – 2.5
3.4 – 3.6
3.0 – 3.2
CAPACITY DIAGRAM
* Only underfloor heang applicaons
Technical Data
Temperature Range: 45°C - 65°C
Kvs: 3.5
Flow Diagram
3-Way Mixing Valve (Optional)

Z-Block Manual version 1.3
Page 8
Tamas Hydronic Systems
Applications
CLIENT
:
Date
Checked
:
Drawan
:
Fernando
Tom
Tom
19
/
004
/
2017
19
/
04
/
2017
19
/
04
/
2017
Size
B
DWG
.
No
.
Scale
:
Rev
.
1
2
Sheet
1
of
1
Boiler Pump
Approvals
Approved
:
Proprietary Information
:
The information contained in this document is the property of Thamas hydronic Systems
Inc
.
except as specifically authorized in writing Tamas Hydronic Systems Inc
.
The holder
document
:
(
1
)
Shall keep all information contained herein confidential and shall protect same in
whole or in part from disclosure and dissemination to all third parties
.
(
2
)
Shall use same for operation and maintenance purposes only
.
Applications
The Tamas Z-Block is designed to be assembled and installed in mulple
conguraons and orientaons.
1) Boiler Pump
As a boiler pump in a mulple zone applicaon. You must use oponal part
#025-0005 180° End Connecon for creang primary/secondary piping
arrangement. See page 9 for Z-Block inverted pump conguraon.
Zone Pumps
Boiler Pump
with 180° End
Connector

Tamas Hydronic Systems Inc. Page 9
Tamas Hydronic Systems
Applications
Rotang the Pump Head
When using the Z-Block as boiler/injecon pump, connect the Z-Block to the
manifold in an inverted posion. In this posion, the pump head (Part #025-
0010) will need to be inverted 180° as well. To do this, remove the 4 pump
bolts and turn the pump head to the desired locaon. Replace the screws when
nished.
Do not spin the pump base.
Remove pump head screws
and rotate pump head 180°
1
Final Configuraon, shown
on right
2

Z-Block Manual version 1.3
Page 10
Tamas Hydronic Systems
Applications
CLIENT
:
Date
Checked
:
Drawan
:
Fernando
Tom
Tom
19
/
004
/
2017
19
/
04
/
2017
19
/
04
/
2017
Size
B
DWG
.
No
.
Scale
:
Rev
.
1
1
Sheet
1
of
1
Injection Pump
&
Hi
-
Low Temp
.
Zones
Approvals
Approved
:
Proprietary Information
:
The information contained in this document is the property of Thamas hydronic Systems
Inc
.
except as specifically authorized in writing Tamas Hydronic Systems Inc
.
The holder
document
:
(
1
)
Shall keep all information contained herein confidential and shall protect same in
whole or in part from disclosure and dissemination to all third parties
.
(
2
)
Shall use same for operation and maintenance purposes only
.
2) Injecon Pump
As an injecon pump in a Tamas mulple zone applicaon, to temper the water
temperature. You must use oponal part #025-0005 180° End Connecon for
creang primary/secondary piping arrangement. Injecon pump controller not
supplied. See page 9 for Z-Block inverted pump conguraon.
Zone Pumps
Zone Pumps
Boiler Pump
with 180° End
Connector
Mixing Pump
with 180° End
Connector

Tamas Hydronic Systems Inc. Page 11
Tamas Hydronic Systems
Applications
CLIENT
:
Date
Checked
:
Drawan
:
Fernando
Tom
Tom
19
/
004
/
2017
19
/
04
/
2017
19
/
04
/
2017
Size
B
DWG
.
No
.
Scale
:
Rev
.
1
4
Sheet
1
of
1
Proprietary
Information
:
Two
3
-
Way Valves
&
High Temp
Zones
The information contained in this document is the property of Thamas hydronic Systems Inc
.
except as specifically authorized in writing Tamas Hydronic Systems Inc
.
The holder document
:
(
1
)
Shall keep all information contained herein confidential and shall protect same in whole or in
part from disclosure and dissemination to all third parties
.
(
2
)
Shall use same for operation and maintenance purposes only
.
Approvals
Approved
:
3) Zone Pump
Zoning in a hydronic system for individual or mulple zones. The maximum
amount of connected Z-block modules is 10 in a single supply to the manifolds.
See page 9 for Z-Block inverted pump conguraon.
Zone Pumps
DHW Pump
Mixing Valve
Boiler Pump
with 180° End
Connector

Z-Block Manual version 1.3
Page 12
Tamas Hydronic Systems
CLIENT
:
Date
Checked
:
Drawan
:
Fernando
Tom
Tom
19
/
004
/
2017
19
/
04
/
2017
19
/
04
/
2017
Size
B
DWG
.
No
.
Scale
:
Rev
.
1
3
Sheet
1
of
1
Low Temp
.
Zones
Approvals
Approved
:
Proprietary Information
:
The information contained in this document is the property of Thamas hydronic Systems
Inc
.
except as specifically authorized in writing Tamas Hydronic Systems Inc
.
The holder
document
:
(
1
)
Shall keep all information contained herein confidential and shall protect same in
whole or in part from disclosure and dissemination to all third parties
.
(
2
)
Shall use same for operation and maintenance purposes only
.
Supply Return
4) Vercal Arrangement
The Z-Block can be installed in a vercal conguraon. When installing mulple
Z-Block modules vercally, the sensor & vent ng (Part#025-0021) for the air
vent must be installed on the topmost end cap.
Applications
Zone Pumps

Tamas Hydronic Systems Inc. Page 13
Tamas Hydronic Systems
Applications
CLIENT
:
Date
Checked
:
Drawan
:
Fernando
Tom
Tom
19
/
004
/
2017
19
/
04
/
2017
19
/
04
/
2017
Size
B
DWG
.
No
.
Scale
:
Rev
.
1
2
Sheet
1
of
1
Boiler Pump
Approvals
Approved
:
Proprietary Information
:
The information contained in this document is the property of Thamas hydronic Systems
Inc
.
except as specifically authorized in writing Tamas Hydronic Systems Inc
.
The holder
document
:
(
1
)
Shall keep all information contained herein confidential and shall protect same in
whole or in part from disclosure and dissemination to all third parties
.
(
2
)
Shall use same for operation and maintenance purposes only
.
5) Vercal Arrangement with a Boiler Pump
The Z-Block can be installed in a vercal conguraon. When installing mulple
Z-Block modules vercally with a boiler pump, two oponal parts must be
used: the 180° end connector (Part#025-0005) and the sensor & vent ng
(Part#025-0021) for the air vent or thermistor sensor.
Note: For vercal installaon with a Z-Block as a boiler pump, it is
necessary to use the 180° End Connector for venng purposes. See page
17 for assembly instrucons, and page 15 for vent ng instrucons.
Zone Pumps
Boiler Pump
with 180° End
Connector

Z-Block Manual version 1.3
Page 14
Tamas Hydronic Systems
End Cap Installation
Autovent Installation
Apply a pea-sized amount of Silicon
Grease to O-Rings on Autovent.
A line film of lubricaon
can avoid rolling the O-ring.
1
Push firmly in the vercal direcon unl
it reaches the end stop in the Z-Block.
2
3Push and twist Air Vent clockwise to
seal the connecon.
Apply a pea-sized amount of Silicon
Grease to O-Rings on End Cap.
A line film of lubricaon
can avoid rolling the O-ring.
1
Push End Cap firmly in the axial direcon
unl it reaches the end stop in the Z-Block
2
3
When connected, turn both levers on
fings up or down to lock and seal
Assembly

Tamas Hydronic Systems Inc. Page 15
Tamas Hydronic Systems
Drill 5mm hole through
center of end cap
1
Insert Purge Valve into
end cap port, secure with
valve clip.
2
Sensor fings can also be
installed. Drill out 5mm (0.2”) hole in
boom of fing before installaon.
Insert Purge Valve into
Z-Block port
(part #025-0014)
1
Push Valve Clip into Z-Block
to secure the Valve
(part #025-0015)
2
1. Insert the purge valve unl it
reaches the end stop in the
Z-Block
2. Once the purge valve ng
is fully seated, slide the
ng clip into the groove in
the port, securing the ng
to the block.
Purge/Drain Valve Installation
Purge/Drain Valve Installaon in End Cap
Depending on the orientaon of the Z-Block distribuon manifold, the purge
valve can be installed in one of the end caps. To do this, drill a 5 mm (02”) hole
through the center opening on the end cap, and insert the purge valve. Once
the purge valve ng is fully seated, slide the ng clip into the groove in the
port, securing the ng to the block.
Assembly

Z-Block Manual version 1.3
Page 16
Tamas Hydronic Systems
Z-Block Distribution Manifold Assembly
The Z-block modules with bayonet connecon are manually assembled to
produce distribuon manifolds with the necessary number of connecons. The
operaon is extremely simple, but it’s important to check that the machined
end parts are clean and free of impuries, and to lightly lubricate the O-ring
with silicone grease if necessary.
The bayonet connecon system does not require the use of tools, and as such,
there is no need to place twisng or crushing force on the modules; this could
deform or damage these parts, thereby aecng their operaon.
Apply a pea-sized amount of Silicon
Grease to O-Rings on Connecon
Fing. A line film of lubricaon
can avoid rolling the O-ring.
1
Push locking tabs down or up to
seal the connecon.
4
2Insert Connecon Fings
and push unl it stops.
3Align Z-Blocks, and push
second block onto connecon
Fings unl they stop.
Assembly

Tamas Hydronic Systems Inc. Page 17
Tamas Hydronic Systems
180° End Connector Assembly
1. Add silicone grease to the O-ring, a line lm of lubricaon can assist and
avoiding rolling the O-ring
2. Posion the Z-block and the connecon ng (Part #025-0003) side by
side.
3. Push rmly in the axial direcon unl it reaches the end stop.
4. Repeat the same procedure with the second connecon ng as shown
below.
5. To enable the bayonet connecon between Z-Block modules and the 180
end connecon, posion the Z-block with the 180 end connecon ng
side by side. Push rmly in the axial direcon unl it reaches the end stop.
Apply Silicon Grease to O-Rings
on Connecon Fing. a line film of
lubricaon can assist and avoiding
rolling the O-ring.
1
2Insert Connecon Fings
and push unl it stops.
Push locking tabs down or up to
seal the connecon.
4
3Align Z-Block and 180° Connector,
and push the Connector onto
Connecon Fings unl they stop.
Assembly

Z-Block Manual version 1.3
Page 18
Tamas Hydronic Systems
x 1
Z-Block Base
#025-0001
x 2
End Cap
#025-0002
x 2
Connecting
Nipple
#025-0003
x 2
1 G Fitting
#025-0004
x 4
O-ring
#025-0006
x 2
1” Nut
#006-0306
x 2
3/4” Tail
Piece
#006-0311
x 2
1” Nut Seal
#006-0310
x 2
11/4” Nut
#006-0325
x 2
1” Tail Piece
#006-0331
x 2
11/4” Nut Seal
#006-0332
x 1
Silicon
Grease
#025-0007
x 1
Sensor &
Purge Valve
Clip
#025-0015
x 1
Auto Vent
#025-0013
x 1
Purge Valve
#025-0014
x 1
Check Valve
#025-0018
x 2
5mm Mount
Screws
#025-0008
x 2
Pump Mount
Screws
#025-0022
x 1
Pump Base
#025-0009
x 1
Pump Head
#025-0010
x 1
Pump Base
Large O-ring
#025-0011
x 1
Pump Base
Small O-Ring
#025-0012
x 1
Pump Power
Cable
#025-0020
Included Components

Tamas Hydronic Systems Inc. Page 19
Tamas Hydronic Systems
Optional
Tamas Slip
Fitting
#006-0313
Optional
Tamas Ball
Valves
#025-0049
Optional
22 x 32mm
Slip Adapter
Fitting
#006-0315
Optional
180 End
Connector
#025-0005
Optional
Sensor &
Vent Fitting
#025-0021
Optional
Sensor
Cable
#025-0017
Optional
Pressure &
Temp Sensor
#025-0016
Accessories available from Tamas Hydronic Systems INC.
Phone: +1(403) 279 0020
Fax: +1 (403) 279 0747
Email: info@tamashydronic.com
Optional Accessories

Z-Block Manual version 1.3
Page 20
Tamas Hydronic Systems
Limited Warranty
Tamas Hydronic Systems Inc. warrants each of its products to be free from defects in workmanship and materials under
normal use and service for a period of 24 months from date of purchase from a Tamas Hydronic Systems inc. authorized
Dealer.
If the product proves to be defecve within the applicable warranty period, Tamas Hydronic Systems inc. on its sole
discreon will repair or replace said product. Replacement product may be new or refurbished of equivalent or beer
specicaons, relave to the defecve product. Replacement product need not be of idencal design or model. Any repair
or replacement product pursuant to this warranty shall be warranted for not less than 90 days from date of such repair,
irrespecve of any earlier expiraon of original warranty period. When Tamas Hydronic Systems Inc. Provides replacement,
the defecve product becomes the property of Tamas Hydronic Systems Inc.
Warranty Service, within the applicable warranty period, may be obtained by contacng your nearest Tamas Hydronics
Systems inc. oce via the original Authorized Agent and requesng a Return Material Authorizaon Number (RMA #). Proof
of purchase in the form a dated invoice/receipt must be provided to expedite the issuance of a Factory RMA.
Aer an RMA number has been issued, the defecve product must be packaged securely in the original or other suitable
shipping package to ensure that it will not be damaged in transit. The RMA number must be visible on the outside of the
package and a copy included inside the package. The package must be mailed or otherwise shipped back to Tamas Hydronic
Systems Inc. with all costs of mailing/shipping/insurance prepaid by the warranty claimant.
Any package/s returned to Tamas Hydronic Systems Inc. without an approved and visible RMA number will be rejected and
shipped back to purchaser at purchaser’s expense. Tamas Hydronic Systems Inc. Reserves the right, if deemed necessary, to
charge a reasonable levy for costs incurred, addional to mailing or shipping costs.
Limitation of Warranties.
If the Tamas Hydronic Systems Inc. product does not operate as warranted above the purchasers sole remedy shall be, at
Tamas Hydronic Systems opon, repair or replacement. The foregoing warranes and remedies are exclusive and in lieu of
all other warranes, expressed or implied, either in fact or by operaon of law, statutory or otherwise, including warranes
of merchantability and tness for a parcular purpose/applicaon. Tamas Hydronic Systems Inc. neither assumes nor
authorizes any other person to assume for it any other liability in connecon with the sale, installaon maintenance or use of
Tamas Hydronic Systems Inc. products.
Tamas Hydronic Systems Inc. shall not be liable under this warranty; if its tesng and examinaon discloses that the alleged
defect in the product does not exist or was caused by the purchasers or third persons misuse, neglect, improper installaon
or tesng, unauthorized aempts to repair or any other cause beyond the range of intended use, or by accident, re,
lightning or other hazard.
Limitation of Liability.
In no event will Tamas Hydronic Systems Inc. be liable for any damages, including loss of data, loss of prots, costs of
cover or other incidental, consequenal or indirect damages arising out of the installaon, maintenance, commissioning,
performance, failure or interrupon of a Tamas Hydronic Systems Inc. product, however caused and on any theory of liability.
This limitaon will apply even if Tamas Hydronic Systems Inc. has been advised of the possibility of such damage.
Local Law.
This limited warranty statement gives the purchaser specic legal rights. The purchaser may also have other rights which
vary from state to state in the United States, from Province to Province in Canada and from Country to Country elsewhere in
the world.
To the extent this Limited Warranty Statement is inconsistent with local law, this statement shall be deemed modied to
be consistent with such local law. Under such local law, certain disclaimers and limitaons of this statement may not apply
to the purchaser. For example, some states in the United States, as well as some governments outside the United States
(including Canadian Provinces), may:
Preclude the disclaimers and limitaons in this statement from liming the statutory rights of a consumer (e.g. United
Kingdom); Otherwise restrict the ability of a manufacturer to enforce such disclaimers or limitaons; or
Grant the purchaser addional warranty rights which the manufacturer cannot disclaim, or not allow limitaons on the
duraon of implied warranes.
Limited Warranty
Other manuals for Z-Block
1
Table of contents
Popular Water Pump manuals by other brands

ULTIMATE SPEED
ULTIMATE SPEED UOP 12 B1 Translation of the original instructions

Varian
Varian TV 1001 SEM instruction manual

GORMAN-RUPP PUMPS
GORMAN-RUPP PUMPS 02K3-X2 Installation, operation, and maintenance manual with parts list

BUSCH
BUSCH COBRA NX 0450 A instruction manual

vacuubrand
vacuubrand VACUU-PURE 10C Instructions for use

Alcatel
Alcatel IPUP A100 instruction manual