TDK-Lambda EVS300W Series User manual

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
BEFORE USING THE PRODUCT
Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before
using this product. Incorrect usage could lead to an electrical shock, damage to the product or a fire hazard.
DANGER
・Never use this product in locations where flammable gas or ignitable substances are present.
INSTALLATION WARNING
・When installing, ensure that work is done in accordance with the instruction manual. When installation is improper, there is
risk of electric shock and fire.
・Installation shall be done by Service personnel with necessary and appropriate technical training and experience. There is a
risk of electric shock and fire.
・Do not cover the product with cloth or paper etc. Do not place anything flammable around. This might cause damage,
electric shock or fire.
WARNING on USE
・Do not touch this product or its internal components while circuit in operation, or shortly after shutdown. You may receive a
burn.
・While this product is operating, keep your hands and face away from it as you may be injured by an unexpected situation.
・For products with no cover, do not touch them as there are highvoltage and high temperature parts inside. Touching them
might cause injury such as electric shock or burn.
・There are cases where high voltage charge remains inside the product. Therefore, do not touch even if they are not in
operation as you might get injured due to high voltage and high temperature. You might also get electric shock or burn.
・Do not make unauthorized changes to this product nor remove the cover as you might get an electric shock or might damage
the product. We will not be held responsible after the product has been modified, changed or disassembled.
・Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc. Please stop
using it immediately and shut off the product. It might lead to fire and electric shock. In such cases, please contact us. Do
not attempt repair by yourself, as it is dangerous for the user.
・Do not operate and store these products in environments where condensation occurs due to moisture and humidity. It might
lead fire and electric shock.
・Do not drop or apply shock to this product. It might cause failure. Do not operate these products mechanical stress is
applied.
CAUTION on MOUNTING
・Confirm connections to input/output terminals are correct as indicated in the instruction manual before switching on.
・Input voltage, Output current, Output power, ambient temperature and ambient humidity should be kept within
specifications, otherwise the product will be damaged.
・Input line, please use the wires as short and thick as possible.
・Do not use this product in special environment with strong electromagnetic field, corrosive gas or conductive substances and
direct sunlight, or places where product is exposed to water or rain.
・Mount this product properly in accordance with the instruction manual, mounting direction and shall be properly be
ventilated.
・Please shut down the input when connecting input and output of the product.
・When mounted in environments where there is conductive foreign matter, dust of liquid, there is possibility of product
failure or malfunction. Such as install filter, please consider that a conductive foreign matter, dust and liquid do not invade
inside the product.
CAUTION on USE
・Product individual notes are shown in the instruction manual. If there is any difference with common notes individual notes
shall have priority.
・Before using this product, be sure to read the catalog and instruction manual. There is risk of electric shock or damage to the
product or fire due to improper use.
・Input voltage, Output current, Output power, ambient temperature and ambient humidity should be kept within
specifications, otherwise the product will be damaged, or cause electric shock or fire.
1/22 A2690401B
EVS300W/600W Series
Instruction Manual

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
・If the builtin fuse is blown, do not use the product even after replacing the fuse as. There is risk of abnormality inside.
Be sure to request repair to our company.
・For products without builtin protection circuit (element, fuse, etc.), insert fuse at the input to prevent smoke, fire during
abnormal operation. As for products with builtin protection circuit, depending on usage conditions, builtin protection
circuit might not work. It is recommended to provide separate proper protection circuit.
・For externally mounted fuse do not use other fuses aside from our specified and recommended fuse.
・As our product is standard industrial use product that was manufactured by purpose that is used to an general electronics
equipment etc., it is not products that to designed for High Safety uses (Uses extremely high reliability and safety are
required, if reliability and safety has not been secured, with significant dangerousness for directly life or body) is expected.
Please consider a fail safe (Systems that was provided with protection circuit protective devices or systems that redundant
circuit was mounted so that was not unstable in single failure) design enough.
・When used in environments with strong electromagnetic field, there is possibility of product damage due to malfunction.
・When used in environment with corrosive gas (hydrogen sulfide, sulfur dioxide, etc.) , there is possibility that they might
penetrate the product and lead to failure.
・When used in environments where there is conductive foreign matter or dust, there is possibility of product failure or
malfunction.
・Provide countermeasure for prevention of lightning surge voltage as there is risk of damage due to abnormal voltage.
・Connect together the frame ground terminal of the product and the ground terminal of the equipment for safety and noise
reduction. If these ground is not connected together, there is risk of electric shock.
・Parts with lifetime specifications (builtin fan, electrolytic capacitor) are required to be replaced periodically. Set the
overhaul period depending on the environment of usage and perform maintenance. Also, note that there are cases when EOL
products cannot be overhauled.
・Take care not to apply external abnormal voltage to the output. Especially, applying reverse voltage or overvoltage more
than the rated voltage to the output might cause failure, electric shock or fire.
・Do not use this product in special environment with strong electromagnetic field, corrosive gas or conductive substances and
direct sunlight, or places where product is exposed to water or rain.
・The product on this instruction manual are PC Board Type (300W) and Unit Type (600W), which have surfacemounted
components on the solder side of PCB. PCB stress such as bending, twisting etc. could cause damage. Therefore, please
handle with care.
・When handling EVS300W, hold the board edge and take care not to touch the component side. When installing this product
in apparatus or equipment, mount it on spacers.
・The outputs of this product may, under fault conditions, exceed SELV voltage limits. Therefore the outputs must be
protected in the end equipment to maintain SELV.
・This product has used power thermistor to protect the circuit from inrush current. Frequent repetition of input might cause
damage to internal components because of generating surge current.
・The output power is considered to be a hazardous energy level (The voltage is 2V or more and the power is 240VA or
more). It must not be made accessible to users. Protection must be provided for Service Engineers against indirect contact
with the output terminals and/or to prevent tools being dropped across them. While working on this product, the AC input
power must be switched off and the input and output voltage should be zero.
・EVS600W has a builtin fan for aircooling. Do not block air intake and exhaust. It might cause fire.
Note
・Consider storage of the product at normal temperature and humidity avoiding direct exposure to sunlight at environment
with minimal temperature and humidity changes. Storage of product at high temperature, high humidity and environments
with severe changes in temperature and humidity might cause deterioration, and occurrence of condensation in the product.
・When disposing product, follow disposal laws of each municipality.
・Published EMI (CE, RE) or immunity is the result when measured in our standard measurement conditions and might not
satisfy specification when mounted and wired inside enduser equipment.
Use the product after sufficiently evaluating at actual enduser equipment.
・If products are exported, please register the export license application etc. by the Government of Japan according to Foreign
Exchange and Foreign Trade Control Law.
・The Information in the catalog or the instruction manual is subject to change without prior notice. Please refer to the latest
version of the catalog or the instruction manual.
・No part of this document may be copied or reproduced in any form without prior written consent of TDKLambda.
Note : CE MARKING
CE Marking, when applied to a product covered by this handbook, indicates compliance with the low voltage directive.
2/22 A2690401B

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
1. Model name identification method
EVS 18 –16R7 /□(*1)
EVS300W,EVS600W common options
Blank : Standard
/R : With remote ON/OFF control model.
EVS300W only
/A : With chassis and cover model.
/RA : With chassis and cover and Remote
ON/OFF control model.
2. Terminal Explanation
■EVS300W
L : Input terminal (Live line) (M4 screw)
(Fuse in line)
N : Input terminal (Neutral line) (M4 screw)
: Earth terminal (M4 screw)
Mounting hole (hole diameter : φ3.5mm)
These holes are connected to terminal of TB1.
Must be connected to electrically conductive spacer. The mounting surface of the spacer should be within Maxφ8mm.
Mounting hole (hole diameter : φ3.5mm)
These holes are not connected to terminal of TB1.
+ : + Output terminal (M4 screw)
- : Output terminal (M4 screw)
V.ADJ : Output voltage adjustment trimmer. The output voltage rises when a trimmer is turned clockwise.
Remote ON/OFF control terminal (Option“/R”,“/RA”)
I.ADJ : Output constant current adjustment rotary switch
(Refer to “47. Output Constant Current Adjustment Method”for usage)
This adjustment trimmer is for factory setting only. Do not touch this trimmer.
EVS300W Option /R , /RA
*Remote ON/OFF control terminal:Option“/R”,“/RA”
Hand Crimping Tool :YC110R(JST)or YRS110(JST)
Use maker recommended crimping tool.
Housing and terminal pin are not included in the product.
3/22
1
2
3
9
8
7
6
5
4
10
11
Ref.No. Connector Housing Terminal Pin Maker
JSTB2BXHAM XHP2
BXH001TP0.6
or
SXH001TP0.6
CN52
Input
Output
1
2
3
4
5
5
5
8
9
6
7
4
11 10
TB1
TB51
CN52
VR51
S1VR1
Component side
Option (*1)
Rated Output Current
Rated Output Voltage
Series Name

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
EVS600W
N : Input terminal (Neutral line) (M3.5 screw)
L : Input terminal (Live line) (M3.5 screw)
(Fuse in line)
: Earth terminal (M3.5 screw)
-V : Output terminal (M5 screw)
+V : + Output terminal (M5 screw)
V.ADJ : Output voltage adjustment trimmer.
The output voltage rises when a trimmer is turned clockwise.
Output monitoring indicator (Green LED)
Remote ON/OFF control terminal (Option“/R”)
I.ADJ : Output constant current adjustment trimmer
(Refer to “47. Output Constant Current Adjustment Method”for usage)
EVS600W Option /R
*Remote ON/OFF control terminal:Option“/R”
Hand Crimping Tool :YRS620(SPHD002TP0.5)(JST)or YC610R(SPHD001TP0.5)(JST)
Use maker recommended crimping tool.
Housing and terminal pin are not included in the product.
4/22
+V+V V V LN
8
4
1
2
3
5
7
6
I.ADJ
H
No. Configuration Function
1 NC No connection.
2 NC No connection.
3+R Remote ON/OFF control terminal.
4-RRemote ON/OFF control terminal.
5 NC No connection.
6 NC No connection.
7 NC No connection.
8 NC No connection.
9 NC No connection.
10 NC No connection.
13579
246810
CN81
Ref.No.
JSTS10BPHDSS PHDR10VS
SPHD002TP0.5
or
SPHD001TP0.5
CN81
Connector Housing Terminal Pin Maker
1
2
3
7
6
5
4
8
9

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
3. Connecting method
Pay attention to the input wiring. If it is connected to wrong terminal, the product will be damaged.
•Input must be off when making connections.
•Connect terminal to earth (frame ground of the equipment etc.) by thick wire for safety and improvement
of noise sensitivity.
• The output load line and input line shall be separated to improve noise sensitivity.
• Do not apply stress to PCB, when connecting or removing connector.
EVS300W EVS300W Option /R , /RA
EVS600W EVS600W Option /R
Recommended torque :
M3.5 screw 1.0N·m(10.2kgf·cm)~ 1.6N·m(16.3kgf·cm)
M4 screw 1.2N·m(12.3kgf·cm)~ 1.6N·m(16.3kgf·cm)
M5 screw 2.2N·m(22.4kgf·cm)~ 2.8N·m(28.6kgf·cm)
5/22
Connect external voltage between " +R" terminal
(Pin No.1) and "R" terminal (Pin No.2) of CN52
for remote ON/OFF control.
(ON/OFF control lines shall be twisted.)
Connect external voltage between " +R" terminal
(Pin No.3) and "R" terminal (Pin No.4) of CN81
for remote ON/OFF control.
(ON/OFF control lines shall be twisted.)
Component side
Input
Output Load
TB1
TB51
CN52
VR51
S1
VR1
Component side
Input
Output
TB1
TB51
CN52
VR51
S1
VR1
Load
+V+V V V
V.ADJ L N
H
+
Load
-
+V+V V V L N
+
Load
-
13579
246810

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
4. Explanation of Functions and Precautions
41. Input Voltage Range
EVS300W:Input voltage range is single phase 85265VAC (4763Hz) or 120370VDC.
EVS600W:Input voltage range is single phase 85265VAC (4763Hz) or 120330VDC.
Input voltage, which is out of specification, might lead the product damage. For cases where conformance to
various safeties required, described as 100240VAC (5060Hz).
EVS300W:Output derating is required for AC input voltage less than 90VAC.
EVS600W:Output derating is required for AC input voltage less than 110VAC.
42. Output Voltage Range
Output voltage is set at the rated value. Output voltage within the range specified can be adjusted by V.ADJ
trimmer. Please set output voltage within specified adjustable range.
Turning the trimmer clockwise, the output voltage will be increased. Take note when the output voltage is
increased. excessively, over voltage protection (OVP) function may trigger and voltage will be shut down.
Furthermore, when increasing the output voltage, reduce the output current as not to exceed the maximum
output power.
When the trimmer turns quickly at no load condition, the output voltage might become unstable. To maintain
the output voltage stable, flow the output current, or remove the input of the product until the output be shut
down, and then reinput. Please turn the trimmer slowly during the output voltage adjustment.
43. Inrush Current
Inrush current is suppressed by power thermistor for EVS300W. Higher current will flow at higher ambient
temperature or input return on condition. Please select input switch or external fuse carefully. The inrush
current value specified in the specification is under cold start condition (at 25oC).
Inrush current is suppressed by thyristor for EVS600W. Higher current may flow when input turn on interval is
short. First inrush current and second inrush current flow. The inrush current value in the specification is first
inrush current. Please select input switch and external fuse carefully.
44. Over Voltage Protection (OVP)
The OVP function is inverter shut down method and manual reset type. OVP function operates within 110130%
of nominal output voltage.
When OVP triggers, the output will be shut down. To reset OVP, remove the input of the product for a few
minutes, and then reinput. In addition, the setting value of OVP is fixed and not adjustable. Never apply higher
voltage externally to the output terminal to avoid the product Failure. In case of inductive load, put protective
diode in series to the output power line.
45. Battery Charger Applications
It is possible to set constant current value of the product and use it for battery charger applications.
Connect our reverse prevention module "EVSRP" or an ORingdiode to the output side of the product.
Use a protective circuit with a fuse or a breaker etc. to prevent the situation that severe electric current
drifts from the battery to the product side.
When connecting ORingdiode, heat will be generated by power losses due to diode forward voltage Vf
and output current Io (Pd = Vf × Io). Therefore, the diodes must be cooled.
In addition, please use the product within the rated output voltage and output power specification.
6/22
Specification of reverse prevention module
Model : EVSRP6020 (TDKLambda)
Input Voltage Range:7 –60 [VDC]
Maximum Input Current:20 [A]
Voltage drop:200 [mV]
Reverse Current:50 [uA]
Size:50×26×77.5 [mm]
loss: Pd = Vf × Io
-
+
Output
Terminal
+
-
load
Io
Vo Vo Vf
◆When connecting ORingdiode

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
46. Output Constant Current Setting Accuracy
Output constant current of EVS300W can be set to preset value by output constant current adjustment rotary
switch. Output voltage droops with constant current within ±10% accuracy of rated output current.
Output constant current of EVS600W can be set to preset value by output constant current adjustment trimmer.
Output voltage droops with constant current within ±10% accuracy of rated output current.
47. Output Constant Current Adjustment Method
EVS300W
Rotary switch S1 can set output constant current value.
During setting the output constant current adjustment rotary switch, power off the product.
Do not touch the adjust trimmer VR1 next to the rotary switch because the trimmer is fixed. Output constant
current adjustment rotary switch is primary side component.
When the product is installed into equipment, the installation should be done by staff, who is instructed on
safety standard and has experiences in adjustment works.
Method of Constant Current Setting
(1)Power off the product and set constant current to required value by output constant current adjustment
rotary switch.
Refer to “■EVS300W Output Constant Current Value Setting” to set the position of the rotary switch.
Refer to “■EVS300W Output Constant Current Set List” on the relation between the rotary switch position
and constant current value.
Set rotary switch to the position which corresponds to required constant current value.
Confirm the direction of arrow groove which indicates position No..
(2)Increase load than output constant current set value and confirm output constant current value become same
as set value. In addition, the output voltage decreases at constant current operation.
The location for EVS300W Output Constant Current Value Setting
S1 : Output constant current adjustment rotary switch.
Minimum Position “No.2”
Maximum Position “No.9”
S1 is set at position No.9
VR1 : Adjust trimmer VR1 for factory setting only.
Do not touch adjust trimmer VR1 because this is for factory setting only. If the adjust trimmer is
forced to be rotated, the product may get some damages.
(Adjust trimmer is fixed with adhesive.)
7/22

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
EVS300W Output Constant Current Set List
The output constant current values in the table below are reference values.
Select constant current value, which is close to your target value, by the rotary switch.
Use the product with the position No.2 ~ No.9 of rotary switch.
Factory default setting of the rotary switch is position No.9.
EVS1816R7
EVS368R4
EVS575R3
※1 This case is out of specified range and may cause the product operation unstable.
※2 When the rotary switch position is set at No.9 and output voltage is set at the minimum output voltage,
output current may exceed the limit of the allowable output current range.
If the output voltage decreases to 50% or less of the rated output voltage in constant current operation, it will be
outside specified range. Furthermore, if it decreases to 15% or less, the output current may increase excessively
and damage the product, or you may hear abnormal noise from the product.
When the product is used outside of specified range, safety standard will not be complied.
If you use the product outside of specified range, contact your nearest TDKLambda sales office with the details
of usages and conditions.
8/22
No. 0 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9
9.0 10.1 11.2 12.4 13.5 14.7 15.6 16.7
9.3 10.4 11.5 12.7 13.8 15.0 15.9 ※2
Output constant current (A)
Output Voltage 18V ※1
Output Voltage 12V
the position number of the rotary switch
No. 0 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9
2.9 3.2 3.6 3.9 4.2 4.6 4.9 5.3
3.0 3.3 3.7 4.0 4.3 4.7 5.0 ※2
※1
the position number of the rotary switch
Output Voltage 57V
Output Voltage 48V
Output constant current (A)
No. 0 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9
4.4 5.0 5.5 6.1 6.7 7.3 7.8 8.4
4.6 5.2 5.7 6.3 6.9 7.5 8.0 ※2
※1
the position number of the rotary switch
Output Voltage 36V
Output Voltage 24V
Output constant current (A)
No.2
No.3
No.4
No.5
No.6
No.7
No.8
No.9
11
12
13
14
15
16
17
18
19
0 2 4 6 8 10 12 14 16 18
Outp ut voltage (V)
Outp ut current (A)
No.2
No.9
No.5
No.2
No.3
No.4
No.5
No.6
No.7
No.8
No.9
22
24
26
28
30
32
34
36
38
0 1 2 3 4 5 6 7 8 9
Output voltage(V)
Output current (A)
No.2
No.9
No.5
Output constant current set range:4.2~8.4A
Output constant current set range:8.35~16.7A
No.2
No.3
No.4
No.5
No.6
No.7
No.8
No.9
47
49
51
53
55
57
59
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6
Output voltage (V)
Output current(A)
No.2
No.9
No.5
Output constant current set range:2.65~5.3A

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
EVS600W
Output constant current adjustment trimmer can adjust output constant current value.
Please do not set output constant current value more than a maximum output current. Might cause damage of
the product.
Output constant current adjustment trimmer is primary side component.
Output constant current adjustment trimmer should be adjusted by skilled person once this product to be
installed into the equipment.
Method of Constant Current Setting
(1)Check the output voltage and the output current are normal after the product power on.
Set the load current with your target current value within 50100% of the maximum rated output current.
(2)Turn output constant current adjustment trimmer I.ADJ counterclockwise until output voltage starts to fall.
Refer to “■EVS600W Output Constant Current Set Point” on positions of output constant current adjust
trimmer.
Refer to “■EVS600W Output Constant Current Set List” on constant current value.
(3)Increase load than output constant current set value and confirm output constant current value stays same
as set value. In addition, the output voltage decreases at constant current operation.
EVS600W Output Constant Current Set Point
The output current falls The output current rises
when a trimmer is turned counterclockwise. when a trimmer is turned clockwise.
EVS600W Output Constant Current Set List
Please set constant current value in the following range.
9/22
10.0~10.6A
5.3~9.7A
5.3~10.6A
Input Voltage conditionClassification EVS3616R7
15.8~16.7A
8.35~15.3A
8.35~16.7A
100VAC
200VAC
EVS5710R6
200VAC
I.ADJ
H
I.ADJ
H
I.ADJ
H
Factory setting
Adjustable range

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
48. Output Ripple & Noise
The specified maximum ripple & noise value is measured according to measurement circuit specified by
JEITARC9131B. When load lines are longer, ripple will becomes larger. In this case, electrolytic capacitor, film
capacitor, etc. might be necessary to be used across the load terminal.
The output ripple cannot be measured accurately if the probe ground lead of oscilloscope is too long.
49. Series Operation
For series operation, either method (A) or (B) is possible.
In series operation, the actual voltage between output and must be less than withstand voltage
(500VAC).
In addition, take note that using the product with total output voltage 60V or more does not comply with SELV
in safety standard. In series operation, the rising waveform may have steps.
When connecting with a battery, connect an ORingdiode to the output side of the product.
(A) (B)
Note :Series operation also can be used without bypass diode. But ensure that all products must be in operation.
(Never use in condition that one of the product is not operated.)
10/22
Coaxial Cable
1.5 m 50Ω
C2
+Load
A
Product
+
-
150mm
C1
R1
C3
Oscilloscope
Bandwidth:100MHz
C1:0.1uF Film Cap.
C2:100uF Electrolytic Cap.
C3:4700pF Ceramic Cap.
R1:50Ω
-
+
-
+
+
-
+
-
Bypass Diodes
-
+
-
+
+
-
load
Output
Terminal
Output
Terminal load
load
Output
Terminal
Output
Terminal

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
410. Parallel Operation
For parallel operation, either method (A) or (B) is possible.
(A) Operation to increase the Output Current
(1)Adjust each product output to same voltage. (The difference of each product output voltage should
be within ±5%.) If the difference of each product output voltage is too big, the output
current becomes uneven and the products may be damaged.
(2)Connection wires between the product and load should be same type and same length.
(3)Parallel connection is acceptable up to 5 units maximum.
(4)The purpose of parallel operation is to increase the static maximum output current.
There is a possibility that output voltage dips at dynamic load change.
(5)There might be a step in the output rise waveform during parallel operation.
(B) Operation as a Backup System
(1)Adjust each product output to same voltage. (The difference of each product output voltage should
be within ±5%.)
(2)Adjust the output voltage higher by the value of the voltage drop (90mV typ.) of EVSRP or the forward
voltage drop (Vf) of ORingdiode.
(3)Output voltage and output power should be used within specifications.
(4)When using EVSRP, output load current should be used within specifications. When using
ORingdiode, current rating must be more than output load current.
(A) (B)
411. Isolation Test
Isolation resistance between Output terminal is more than 100MΩ at 500VDC. For safety operation, voltage
setting of DC isolation tester must be done before the test. Ensure that the product is fully discharged after
the test.
■ Output terminal : 500VDC More than 100M
11/22
AC(L)
+
AC(N)
-
+ R
R
Isolation
Tester
-
+
-
+
+
-
Output
Terminal
Output
Terminal
load
-
+
-
+
+
-
Output
Terminal
Output
Terminal
load
EVSRP
EVSRP
For more information about EVSRP,
please refer to “45. Battery Charger Applications”or
“EVSRP Instruction Manual”.
EVSRP can be replaced by ORingdiode. In such
case, please take care of ORingdiode temperature.

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
412. Withstand Voltage
This series is designed to withstand 3.0kVAC between input and output, 2.0kVAC between input and terminal
and 500VAC between output and terminal each for 1 minute. When testing withstand voltage, set current limit
of withstand voltage test equipment at 10mA (Output terminal : 20mA).
The applied voltage must be gradually increased from zero to testing value and then gradually decreased for shut
down. When timer is used, the product may be damaged by high impulse voltage at switch on and off timing.
Connect input and output as follows.
■ Input Output (dotted line) : 3.0kVAC, 1min (10mA) ■ Output terminal : 500VAC, 1min (20mA)
Input terminal (solid line) : 2.0kVAC, 1min (10mA)
Note 1 : EVS600W has multilayer ceramic capacitor in secondary circuit to terminal.
Some of the withstand voltage tester may generate high voltage due to distortion of test voltage and
may cause the product damage.
So, please check the waveform of applied voltage.
Note 2 : In case of using external noise filter, capacitance between "Input and terminal" might be increased.
When testing withstand voltage between "Input and Output", there is a possibility exceeding withstand
voltage between "Output and terminal" (500VAC). Please check the voltage between
"Output and terminal". If the voltage exceeding withstand voltage, please add external capacitor to
"Output and terminal". It can decrease the voltage.
On the other hand, no need to check the voltage in case of "Output and terminal" is shorted.
The example of noise filter circuit that External capacitor adding point or short point.
may increase capacitance value between Even in the case of “+V and ”,
“Input and ”. there is a similar effect.
(Capacitance value in dashed line is added.)
12/22
AC(L)
+
AC(N)
-
+R
R
Withstand
Voltage
Tester
+V
V
AC(L)
AC(N)
AC(L)
AC(N)
Noise filter Product
Withstand Voltage Tester

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
413. Remote ON/OFF Control (Option /R , /RA )
Remote ON/OFF control function is provided on option model “/R”and “/RA”. Using this function allows the
user to turn the output on and off without having to turn the AC input off and on. It is controlled by the external
voltage applied to +R and R of remote ON/OFF terminal. This circuit is in the secondary side of the product.
Never connect to primary side.
5. Mounting Method
51. Mounting Direction
The standard mounting is direction (A).
EVS300W: Possible mounting directions are (A), (B),(C), (D) and (E) only. Do not mount the product in any
other directions.
EVS600W: Possible mounting directions are (A), (B),(C) and (D) only. Do not mount the product in any other
directions.
Do not exceed the derating of maximum load, which is limited by mounting direction and ambient temperature.
Refer to “52.Output Derating” for more information.
EVS300W
(A)Standard Mounting (B) (C) (D) (E) (F)Not Possible
EVS600W
(A)Standard Mounting (B) (C) (D) (E)Not Possible (F)Not Possible
13/22
INPUT TERMINAL
T B1(INPUT)
T B1
TB1
T B1
FIN T B1
FIN
T B1
Output
Voltage
Fan condition
(EVS600W)
ON Operate
OFF Not Operate
+R & R terminal condition
SW ON (Higher than 4.5V)
SW OFF (Lower than 0.5V)
Not required
1.5kΩ
External voltage level:E
4.5 ~12.5VDC
12.5 ~24.5VDC
External resistance:R
Product
+R
-R
SW
R
E
R:External resistance
E:External voltage level
EVS300W :
EVS600W :
1kΩ
780Ω

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
52. Output Derating
Refer to the output derating below, load (%) is percent of maximum output current value in a rated output
voltage.
(1)Convection Cooling
EVS300W
(Option /R included)
EVS300W/A (With chassis and cover model.)
(Option /RA included)
14/22
0
20
40
60
80
100
120
20 10 0 10 20 30 40 50 60 70 80
Load(%)
Ta(℃)
0
20
40
60
80
100
120
20 10 0 10 20 30 40 50 60 70 80
Load(%)
Ta(℃)
Ta
(°C)
20 +10
20
30
40
50
60
Load (%)
Mounting (D),(E)
100
84
68
52
36
20
◆Mounting (A),(B)
■Mounting (C)
▲Mounting (D)
●Mounting (E)
Ta
(°C)
20 +40
45
50
60
70
Ta
(°C)
20 +20
30
40
50
60
70
Load (%)
Mounting (A),(B) Mounting (C)
100
100 86
88 73
64 46
40 10
Load (%)
Mounting (D) Mounting (E)
100
84 82
68 64
52 46
36 28
20 10
◆Mounting (A)
■Mounting (B)
▲Mounting (C)
●Mounting (D),(E)
Ta
(°C)
20 +25
30
40
50
60
Load (%)
Mounting (A) Mounting (B) Mounting (C)
100
100 91 90
80 74 70
60 57 50
40 40 30

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
(2)Forced Air Cooling
EVS300W
(Option /R included)
EVS300W/A (With chassis and cover model.)
(Option /RA included)
The entire component must be cooled. The maximum temperature of the electrolytic capacitor C6 and C52 must keep lower
than “Electrolytic capacitor allowable Max temperature” in the above table. As reference, set wind velocity at 1.4m/s.
15/22
◆Mounting (A) (E)
Ta
(°C)
20 +50
60
C6
C52
75
75
Load (%)
Mounting (A) (E)
100
70
Cooling : Wind velocity ≧1.4m/s
Electrolytic capacitor allowable Max temperature
Allowable Max temperature (℃)
0
20
40
60
80
100
120
20 10 0 10 20 30 40 50 60 70 80
Load(%)
Ta(℃)
0
20
40
60
80
100
120
20 10 0 10 20 30 40 50 60 70 80
Load(%)
Ta(℃)
C 51
C7
C6
(Input Terminal)
TB1
Component side
◆Mounting (A) (E)
Cooling : Wind velocity ≧1.4m/s
Ta
(°C)
20 +60
70
Electrolytic capacitor allowable Max temperature
C6
C52
Load (%)
Mounting (A) (E)
100
70
Allowable Max temperature (℃)
75
75
C52

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
EVS600W
EVS600W is forced air cooling type product with builtin fan. This product has ventilating holes.
53. Output Derating according to the Input Voltage
Load (%) is percent of maximum output current value in a rated output voltage.
EVS300W
EVS600W
16/22
Mounting (A) (D)
Ta
(°C)
20 +50
60
70 20
Load (%)
Mounting (A) (D)
100
60
◆
Load (%)
80
85
100
90 265
Input Voltage (VAC)
Input Voltage (VAC)
80
85 110
100
92
100 265
Load (%)
0
20
40
60
80
100
120
20 10 0 10 20 30 40 50 60 70 80
Load(%)
Ta(℃)
■
Mounting (A) (E)
Input Voltage
(VAC)
85
90265
80
Load (%)
Mounting (A) (E)
100
■Mounting (A) (D)
(VAC)
85
100
110265
Mounting (A) (D)
80
92
100
Load (%)
Input Voltage

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
54. Mounting Method
EVS300W
Insert the spacer (Maxφ8) of height more than 8mm to lift the product. And use all mounting holes A for the product
installation. The vibration spec is specified under this mounting condition. Please use mounting hole B as needed,
vibratility resistant improves.
(1)Mounting Holes size
5 holes φ3.5mm
Allowable area by metal pieces is 9mm from each PCB corners. Refer to figure below.
If the space is not enough, the specification of isolation and withstand will not be satisfied. Take the space in the product
surroundings and the upper area of components to keep enough for convection cooling.
(2)Condition to meet Isolation & Withstand Voltage standard
Keep 4mm space from the surfaces and sides of PCB.
Especially, 8mm space is necessary from the solder surface.
17/22
A
AA
A
B
Height more than 8mm spacer
9mm 9mm
9mm
9mm 9mm
More than
4mm
More than
4mm
More than
8mm
PCB
Component side
More than
4mm
More than
4mm
More than
4mm

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
(3)Earth terminal
terminal must be connected to the Protective earth terminal of the equipment. Also 2 mounting holes are
must be connected to the Chassis (Conductor) by Metal spacer. If not, the conducted noise, radiation noise
and output noise will increase. (The location of 2 mounting holes for Chassis connection is shown with
mark in below figure.)
EVS600W
(1)This model is forced air cooling type product. This product has ventilating holes. Keep a space more than
50mm between front side of the product and peripheral parts. Back side as well.
Also keep a space more than 5mm between other surfaces and the peripheral parts. Never use in the dusty
environment.
(2)The maximum allowable penetration of mounting screws is 6mm.
(3)Recommended torque for mounting screw(M4 screw): 1.27N·m(13.0kgf·cm)
18/22
Front side FanTop
Terminal
block
Air
flow
Back side
More than 5mm
Side Fan
Front side
Back side
Air
flow
Terminal
block
More than 5mm
More than 50mm More than 50mm
Chassis (Conductor)
Protective
earth terminal
Wire
Input
NL
Output
-+
Metal spacers

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
6. Wiring Method
(1)The output load line and input line shall be separated, and use all lines as thick and short as possible to make
lower impedance. The output load line and input line shall be twisted or use shielded wire to improve noise
sensitivity.
(2)Remote ON/OFF control lines shall be twisted and separated from the output lines.
(3)Noise can be eliminated by attaching a capacitor to the load terminals.
(4)For safety and EMI considerations, connect between terminal and Frame Ground terminal of equipment firmly.
(5)The recommended wire type, torque and crimptype terminal :
Note 1 : When using separate loads, use of two pcs. of 0.8mm thick crimp
type terminal is recommended.
Note 2 : For recommended wire type, refer to wire maker recommended
allowable current and voltage drop.
Recommended wire type and crimptype terminal vary depending on
actual conditions. Choose most appropriate wire type and crimptype
terminal by refer to wire maker recommended
allowable current and voltage drop.
(6)Radiated Emission (EVS600W only)
It is recommended to use the clamp filter to meet EN55011/EN5502B, FCCClassB, VCCIB.
The product might meet the standard without using the clamp filter depend on wiring and mounting product
installed conditions (for example, by using other external input filter or using at light load etc.).
Evaluating well by the system before use is recommended.
Note :Recommended clamp filter is ZCAT30351330 (TDK).
Winding input wire around the clamp filter by 2 turns.
19/22
DtMounting
pieces
(MAX)
(MAX) (MAX)
M4 Screws
1.2N/m(12.2kgf/cm)~1.6N/m(16.3kgf/cm)
M4 Screws
1.2N/m(12.2kgf/cm) ~1.6N/m(16.3kgf/cm)
M3.5 Screws
1.0N/m(10.2kgf/cm) ~1.6N/m(16.3kgf/cm)
M5 Screws
2.2N/m(22.4kgf/cm)~2.8N/m(28.6kgf/cm)
AWG12 22
8.1mm
1.0mm 1 piece
0.8mm 2 pieces
EVS600W
EVS300W
Recommended crimptype terminal
8.1mm
1.0mm
0.8mm
1 piece
AWG12 22
2 pieces
Recommended torque
Recommended
Wire
Model
Clamp filter
+V
-V
Load
L
N

INSTRUCTION MANUAL
EVS300W/600W Series
TDKLambda
<Page>
7. Expected life
The life expectancy of the product is as follows.
The life expectancy is dependent on the lifetime of electrolytic capacitor and/or the fan.
The life expectancy is not a guaranteed value, please consider as a reference.
Do not use the product which passed over the life expectancy.
There is a risk of unexpected output shutdown or specifications may not be satisfied.
Please contact us for maintenance or exchange the product which passed over the life expectancy.
The life expectancy of the product is calculated in condition of rated input voltage and 24hour continuous
operation.
Load (%) is percent of maximum output current in a rated output voltage.
EVS300W
EVS300W/A (With chassis and cover model.)
EVS600W
20/22
10 years
8
years
9
years
6
years
Ta (oC)
100
50
045
40
Load (%)
Mounting (A)
100
50
045
40
100
50
040
30
100
50
020
Mounting (B) Mounting (C) Mounting (D),(E)
10 years 10 years
10 years
Load (%)
Load (%)
Load (%)
Ta (oC) Ta (oC) Ta (oC)
6
years
9
years
100
50
030
100
50
025
100
50
025
2010
100
50
010
Mounting (A) Mounting (B) Mounting (C) Mounting (D),(E)
10 years
10 years
10 years 10 years
Ta (oC) Ta (oC) Ta (oC) Ta (oC)
Load (%)
Load (%)
Load (%)
Load (%)
3
years
10 years
6
years
6
years
100
50
0504030
Mounting (A),(B),(C),(D)
Ta (oC)
Load (%)
This manual suits for next models
3
Table of contents
Popular I/O System manuals by other brands

National Instruments
National Instruments PCIe-7856 Getting started guide

Panasonic
Panasonic AV-HS04M1 operating instructions

Allen-Bradley
Allen-Bradley Compact 1769-IR6 user manual

Allen-Bradley
Allen-Bradley MicroLogix 1762-IF2OF2 installation instructions

Strand
Strand 53904-108 quick start guide

ADLINK Technology
ADLINK Technology NuDAQ 723 Series user manual

AccuEnergy
AccuEnergy Acuvim II AXM-IO1 user manual

Altec Lansing
Altec Lansing 1780A 1780AT SIGNAL PROCESSING manual

Rockwell Automation
Rockwell Automation Series C installation instructions

Measurement Computing
Measurement Computing PCI-DIO96 user guide

WAGO
WAGO 750-8207 manual

Advantech
Advantech APAX-5000 Series user manual