Tools and Preparation Required for Installation
Installation Procedures
General Information
Warranty
Each carton contains the following items:
KoldLok Wave™ Grommets (10)
Self-Tapping #8 Screws (40)
Edge-Mount Foam Strips, 10-Piece Pad (1)
Installation Guide (1)
Cutout Template - available for download at www.KoldLokWave.com
™

Installation Guide
KoldLok Wave™ Split Integral Grommet
General Information
Eective Installation of Cables
In order to minimize any air loss from under the raised oor plenum, make sure to allow
for adequate slack in the cables. If the cables are under too much tension, the grommet
may be pulled apart, resulting in a gap that will cause an increase in the ow rate of air
escaping from under the raised oor.
Maintaining Proper Cooling of Equipment
Failure to follow computer manufacturer’s guidelines for maintaining proper cooling
may result in the overheating of equipment. Before sealing cable cutouts, ensure that
there is adequate air ow to the intake side of computer equipment or cabinets through
devices such as perforated oor tiles or grates. Achieving proper airow to the intake
side of computer equipment and/or cabinets is the responsibility of the customer.
Safety Requirements
Installers must be familiar with standard safety and risk management practices when
working in raised oor environments and when modifying oor tiles.
An optional cover is available to ensure greater safety before rack and cable installation.
Customer Support
If you have any questions, please contact us at:
(888) 982-7800, M–F, 9AM–5PM MST or email
Upsite Technologies, Inc.
8100 Lang Avenue NE, Suite 301
Albuquerque, NM 87109
P: (505) 798-0200 | F: (505) 798-0236

Installation Guide
KoldLok Wave ™ Split Integral Grommet
Tools and Preparation Required for Installation
Tools Required:
• Phillips head screwdriver or drill
• Cutting tool (per floor tile manufacturer recommendations)
• Tape measure
Cutting Raised Floor Tiles
Each raised floor tile manufacturer provides instructions to properly and safely
modify their products. Installers must be familiar with and observe tile
manufacturer’s recommendations with regard to applicable tools, cutting
procedures, the design load capacity of the cut tile, and any additional
underfloor support requirements for cut raised floor tiles.
Product Drawings
Long Side
1 / ”
/”
9 /”
Short Side
6 /”
1 /”
1 ⁄”
/”
11”
9 ”

Installation Procedures
Installation of KoldLok Wave™ on the Tile Interior
1. Make a 9 / x 6 / ” (± /”) cutout or 235mm x 171mm (± 3mm) in the floor
tile. A cutout template is available for download at www.KoldLokWave.com.
Ensure that any burrs that resulted from cutting the floor tile have been
removed. It is not necessary to dress the cutout when installing a KoldLok
Wave™ Split Integral grommet.
2. Test-fit KoldLok Wave™ to
the floor tile by making
the flange flush with the
top side of the floor tile.
Ensure there is no binding
and that the fit is even on
the grommet.
3. With the grommet
properly placed in the
floor tile, fasten it securely
to the floor tile using the
self-tapping screws. Do
not over-torque the
screws.
Assembling Grommet Around Cable Bundles
1. Separate KoldLok Wave™ unit at the seam by sliding the female side
up o of the male side.
2. Place male section on the oor, back edge rst.
3. Re-assemble unit at the seam around cables following the above
installation instructions.
Joining clip ts into matching
pockets on both halves
Tapered pin ts into tapered
hole on opposing part
Male Female

Installation of KoldLok Wave™ on the Tile Edge—Long Edge of Grommet
In the absence of a supporting oor tile ange, edge-mount installations require a
foam insert on the open side of the cut to serve as a gasket. If the hole in your oor tile
has been cut on three sides only, providing one open edge, the grommet must be
installed with the supplied foam strip inserted into the molded depression on its
underside.
1. Provide a 9 ⁄ x 7 ⁄ ” (± /”) cutout or 235mm x 200mm (± 2mm) in the oor
tile. Ensure that any burrs that resulted from cutting the oor tile have been
removed. A cutout template is available for download at
www.KoldLokWave.com. It is not necessary to dress the cutout when
installing a KoldLok Wave™ Split Integral Grommet.
2. Stretch the supplied foam
strip to ll the 9” depres-
sion on the underside of
the grommet.
3. Test-t KoldLok Wave ™ to
the oor tile, with ange
on the topside of the oor
tile. Ensure there is no
binding and that the t is
even on the grommet.
4. With the grommet
properly placed in the
oor tile, fasten it securely
to the oor tile using the
self-tapping screws. Do
not over-torque the screws.
Installation of KoldLok Wave™ on the Tile Edge—Short Edge of Grommet
The KoldLok Wave™ Split Integral Grommets may also be installed with the short side
mounted along the oor tile edge. Make a 10 ⁄ x 6 ⁄” (± /”) cutout or 257mm x
171mm (± 2mm). Follow the same cleaning and fastening steps as above.

U.S. Patent Pending Application #29/359, 108 and International Patents Pending | P/N 60195 Rev. A © 2011
Limited Warranty
Upsite Technologies, Inc. (the Company) warrants to the original purchaser that products delivered
hereunder will be free of defects in materials and workmanship for a period of twelve (12) months from the
date of purchase (the“Warranty Period”).
The Company shall, at its option, within the Warranty Period, either repair or replace free of charge, any
product or part thereof found, upon the Company’s inspection, to be defective in materials and workman-
ship, and will return the repaired or replaced product to the purchaser at Company’s expense.
For warranty service and shipping instructions, contact the Company at the telephone number shown below.
If the product is under warranty and the defect appears to be covered by this Limited Warranty, the Company
will issue to the purchaser a Notice of Authorization For Warranty Return. Products returned to the Company
for warranty service must be accompanied by a statement of defect, the Notice of Authorization for Warranty
Return provided by the Company, and proof of purchase.
This Limited Warranty is conditioned on the following:
1. The Company must be notied within 12 months of purchase and have been given the opportunity of
inspection by return of any alleged defective product free and clear of all liens and encumbrances to the
Company or its manufacturer; and
2. The product must not have been abused, misused, or improperly maintained, and/or repaired during such
period; and
3. Such defect has not been caused by corrosion or exposure to other than ordinary wear and tear.
The Company makes no other express or implied warranty or representation of any kind whatsoever
including any warranty of merchantability or tness for a particular purpose and all such other
warranties are hereby included.
The Company’s maximum liability hereunder is limited to the purchase price of the product. In no event shall
the Company be liable for any consequential, indirect, incidental, or special damages of any nature arising
from the sale or use of the product, whether based in contract, tort, strict liability, or otherwise.
Note: Some jurisdictions do not allow limitations on incidental or consequential damages or how long an
implied warranty lasts, so that the above limitations may not fully apply. This warranty gives specic legal
rights and you may also have other rights which may vary from jurisdiction to jurisdiction.
For complete warranty and repair information call (888) 982-7800.
Register your product online at www.upsite.com/warranty to extend your warranty to 28 months.
888.982.7800 upsite.com
Table of contents