Veris Industries Hawkeye H-8000 Series User manual

Installation In struc tions
Hawkeye 8051/8053
PULSE OUTPUT kWH TRANSDUCERS
OPERATION
The H-8000 Series combines a microprocessor based kWh transducer and high ac-
curacy split-core in stru ment grade current transformers (CTs) in a single unit. Because
the electronics are integral to the CT(s), hard ware and installation costs are greatly
reduced. Split-core design eliminates the need to remove conductors.
solution for
local or remote
electrical metering
and submetering
in commercial
buildings!
P/N Z101659-0D
The
solution for
10831 S.W. CASCADE BLVD.
PORTLAND, OREGON 97223
(503) 598-4564 FAX (503) 598-4664
1-800-354-8556
VERIS INDUSTRIES
Applications
Tenant submetering for commercial tenants
Energy management & performance contracting
Departmental costing in manufacturing facilities
Cooling plant optimization
Easy cost-e ective installation
Precision transducer electronics and high accuracy instrument grade CT's in a single
easy to install package...reduces the num ber of installed com po nents
Unique split-core design eliminates the need to remove conductors
Fits easily into distribution panels...lowest total installed cost
Automatically detects phase reversal...eliminates the need to be concerned with CT load
orientation
Economical single-CT version available for balanced loads (H8051)
High accuracy and resolution
± 1% accuracy conforms to ANSI C12.1 metering standards (H8053)
0.1 to 1.0 kWH/pulse selectable
• This product is not intended for life or safety applications
• Potential electrocution hazard exists. Installing sen sors in an en er gized electrical
enclosure or on any en er gized con duc tor can be haz ard ous.
• Read instructions thoroughly prior to install
Severe injury or death can result from electrical shock during contact with high
voltage conductors or related equip ment. Dis con nect and lock-out all power
sources during installation and service. Applications shown are sug gest ed means
of installing sensors, but it is the re spon si bil i ty of the installer to ensure that the
in stal la tion is in com pli ance with all national and local codes. In stal la tion should
be at tempt ed only by in di vid u als familiar with codes, stan dards, and proper safety
pro ce dures for high-voltage installations.
WARNING--REFER SERVICING TO
QUALIFIED PER SON NEL ONLY!

2
3
A: Voltage Leads
B: Fuses
C: Pulse Output Connector
D: STATUS LED
E: Pulse Rate Switches
F: External CTs
VOLTAGE LEADS
Connect the leads to the three-phase source to be monitored. Input range is
208 to 480VAC.
MANDATORY FUSE PER NEC
Maximum current draw is 60 mA. Fuses provided by factory are rated 1/2A,
600 VAC, 200 KAIC.
PULSE OUTPUT CONNECTOR
Please refer to wiring diagram on page 4.
STATUS LED
The LED blinks green when the product is functioning normally. It will blink
slowly, approximately one second on, then one second o.
If the LED is red and blinking slowly, it may indicate incorrect wiring or a
power factor that is less than 0.5. If the LED is red and blinking fast the CT's
maximum current rating has been exceeded or the pulse rate switches are
incorrectly set.
PULSE RATE SWITCHES
These switches set the pulse output rate. Please refer to Figure 4 for settings.
EXTERNAL CTs (3 phase versions only)
These external CTs are permanently attached and must not be disconnected or
used with other power meters.
PRODUCT DIAGRAM
A
B
C
D
E
F
FIGURE 1
Color match CTs and voltage leads! Example: Clamp the red label CT around
the power conductor connected to the red voltage wire.

2
3
277V
Black
Red
Yellow
Neutral
Neutral
277V
PULSE OUTPUT LIN
E
120
Neutral
120
PULSE OUTPUT LIN
E
PULSE OUTPUT LINE
PHASE
PHASE
PHASE
WIRING DIAGRAMS
TYPICAL 208/480 VAC 3Ø, 3,4 WIRE INSTALLATION
Model 8053 Model 8051
NOTE: Multiply output pulses by
3 for proper kWH indication
Model 8053 Model 8051
TYPICAL 240/120 VAC 1Ø, 3-WIRE INSTALLATION
TYPICAL 277 VAC 1Ø, 2-WIRE INSTALLATION
Model 8051
FIGURE 2
*
*Assuming a balanced load.
NOTE: Wires are crossed through
the CT, each entering from the
opposite direction. Assuming
the voltages are equal, this does
not require a balanced load.
NOTE: Multiply output pulses by
2 for proper kWH indication
Model 8053
Cap This
Cap This
Cap This
PULSE OUTPUT LINE
PHASE
PHASE
PHASE
120V
120V
Black
Red
Yellow
Neutral
Cap This

4
5
Remove the terminal block and attach the pulse output wires. Positive,
negative and Shield wires must be connected as shown in Figure 3.
If necessary, insulate any exposed wiring. Ensure that insulation
complies with local and national electrical codes.
Approximate check of output:
1. Check actual current with Amp clamp.
Expected power is:
kW = Volts x Amps x 1.732 x PF ÷ 1000
kW = Horsepower x .746
2. Calculate approximate seconds per pulse:
S=kWh
Pulse Setting
seconds/pulse = 3600 x S
kW
Note: Since these calculations are approximate, there may be some
variation.
NOTES
1. DO NOT GROUND THE SHIELD INSIDE THE ELECTRICAL PANEL.
All wires, including the shield should be insulated to prevent accidental contact to high voltage conductors.
2. The cable should be mechanically secured where it enters the electrical panel.
3. The cable should be shielded twisted pair wire BELDEN 1120A or similar
WARNING: After wiring the cable, remove all scraps of wire or foil shield from the electrical panel.
This could be DANGEROUS if wire scraps come into contact with high voltage wires!
Set the switches for the desired pulse-rate as shown in Figure 4. Note that
some settings are not allowed.
Disconnect power and lock-out all power sources during installation.
DO NOT CONNECT VOLTAGE INPUTS LIVE!
Connect the voltage leads to the 3-phase conductors, as shown in Figure
2. Becaue the meter requires voltage to communicate, connect the leads to
a location which is not normally switched o. Connect the red lead to the
conductor most convieniently located to physically mount the CT with pulse
output connector. After selecting the conductor for the red lead, the black
and yellow leads may be attached to the other two conductors in any order.
Attach CTs to conductors. Each CT must be attached to the same conductor
as the correspondingly colored voltage lead. (See wiring diagram above) The
unit will automatically detect phase reversal, so it is not important to orient a
particular side of each CT towards the load.
1
2
3
4
5
6
The H8000 series is NOT intended to be connected to the load side of variable frequency drives. Damage to the unit will result from
such a connection.
INSTALLATION - WIRING DIAGRAM continued
FIGURE 3

4
5
TROUBLESHOOTING
Problem: STATUS LED does not blink.
Solution: Check fuses and voltage connections. STATUS LED should blink
regardless of CTs, pulse output connections and DIP switch setting.
Problem: Readings seem highly inaccurate.
Solution: • Check that each CT is installed on the conductor with the
corresponding color voltage input lead attached. In most cases,
incorrect wiring will cause the STATUS LED to blink RED (slowly).
However, a Power Factor lower than 0.5 could cause the LED to blink
this way, even if the unit is installed properly.
• It does not matter which side of the CTs face towards the load.
• If current is below 7% of full scale maximum for the CT, a smaller
CT should be used for very low currents. An alternative is to wrap each
wire through each CT multiple times and divide the output reading
by the number of turns through the CT window.
• If using a single-phase CT model 8051, ensure that all 3 phases are
passing approximately the same current by testing each phase with
an amp-clamp. If phases are unbalanced, you should use the model
8053.
SPECIFICATIONS
Input primary voltage ...................................................208 to 480 V AC
Input frequency............................................................. 47-70 Hz.
Number of phases monitored........................................ One or Three
Frequency ..................................................................... 50/60 Hz
Maximum primary current............................................ 2400 amps cont. per phase*
Internal isolation........................................................... 2000 VAC rms
Case insulation .............................................................. 600 VAC
Temperature range........................................................ 0 to 60o C
Humidity range ............................................................. 0 - 95 % non-condensing
Accuracy ........................................................................±1.0 % (H8053-ANSI C12.1)†
Current transformer ...................................................... Split core, 100 to 2400 amps
Pulse output type ......................................................... Normally open Opto-Fet
Maximum output current.............................................. 100mA@24VAC/DC
Pulse width.................................................................... 200msec
* Larger sizes available, consult factory
† Meter accuracy specied with conductors centered in CT window
PULSE-RATE SELECTION SWITCHES
FIGURE 4
Problem: Meter o-line when load is switched o.
Solution: Voltage leads must be connected on the Line side of the conductor.
The power meter cannot communicate without voltage.
Problem: STATUS LED blinks red.
Solution: • If the LED blinks quickly, approximately 5 blinks in 2 seconds, either
the pulse-rate switch settings are incorrect OR the CT used is too
small. First check the switch settings. Ensure that an incorrect setting
has not been selected by comparison to Figure 4. Note that some
settings are not available on some models. If switch settings are OK,
then the CT used is too small. A CT with a larger current rating is
required.
• If the LED blinks slowly, approximately. 1 blink in two seconds,
the CTs are not installed on the correct conductors, or the loads Power
Factor is less than 0.5. The meter can accurately measure these low
PFs, but few loads operate normally at such a low power factor.
kWh/pulse
0.1 KWH PER PULSE
Not allowed on 1600A
and 2400A models
0.10
0.25
0.50
1.00
kWh/pulse
0.25 KWH PER PULSE
Not allowed on
2400A model
0.10
0.25
0.50
1.00
kWh/pulse
0.50 KWH PER PULSE
All models
0.10
0.25
0.50
1.00
kWh/pulse
1 KWH PER PULS
E
All models
0.10
0.25
0.50
1.00
This manual suits for next models
2
Table of contents
Popular I/O System manuals by other brands

Telic
Telic STD35 user manual

Meilhaus Electronic
Meilhaus Electronic ME-1400 Electronic manual

M-system
M-system R80DAT16A2 instruction manual

Contec
Contec F&eIT Series user manual

Digital Electronics Corporation
Digital Electronics Corporation Pro-face Flex Network GLC100-FN11 user manual

M-system
M-system R7D-DC16B instruction manual

Industrial Shields
Industrial Shields PLC Arduino ARDBOX user guide

Acces I/O products
Acces I/O products PCIE-ADIO16-16F Hardware manual

Helm
Helm C Series installation instructions

M-system
M-system R7G4HML-6-SVF8N instruction manual

Siemens
Siemens Simatic 6DL2804-0 Series installation manual

Axis
Axis 01160-001 user manual