Vertiv Liebert HPW Series User manual

Liebert® HPW
Outdoor Package Cooling System for
Mobile Network Access Nodes
User Manual
English, cod. 265883, rev. 31.01.2019


12 3
45 6
78 9
10 11
12 13
14
15
16
17
18
19 20
21 22
23
24
25
26
27
Caution
Recommendations:
S the manual is retained for the entire service life of the machine;
S the user reads the manual carefully before carrying out any operations on the machine;
S the machine is used exclusively for the purpose for which it is intended; incorrect use of the machine shall release
the
manufacturer from any liability.
This manual has been prepared to enable the end---user to carry out only the operations that can made with the
panels closed. Any operations that require the opening of doors or equipment panels must be carried out only by
qualified personnel.
Each machine is equipped with an electric isolating device which allows the operator to work in conditions of safety.
This device must always be used to eliminate risks during maintenance (electric shocks, scalds, automatic restarting,
moving parts and remote control).
The panel key supplied with the unit must be kept by the person responsible for maintenance.
For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, read the
identification label placed on the outside and inside of the unit.
IMPORTANT:This manual may be subject to modification; for complete and up---to---date information the user should
always consult the manual supplied with the machine.
Attention: data relevant to the unit
supplied is indicated on the inboard label (see the blank
facsimi-le below).
Data in the manual is referred to standard
conditions and can be modified without any advance
notice.
POS. DESCRIPTION
1Compressor Full Load Ampere [A]
2Compressor Locked Rotor Ampere [A]
3Compressor quantity
4Evaporator fan Full Load Ampere [A]
5Evaporator fan Locked Rotor Ampere [A]
6Evaporator fan quantity
7Condenser fan Full Load Ampere [A]
8Condenser fan Locked Rotor Ampere [A]
9Condenser fan quantity
10 Electrical heating Ampere
11 Electrical heating steps
12 Humidifier Ampere
13 Steam production capacity
14 Max. unit AC Ampere
15 Max. unit DC Ampere
16 Rated peak withstand current
17 Rated short---time current
18 Refrigerant type
19 High pressure switch Stop
20 High pressure switch Restart
21 Low pressure switch Stop
22 Low pressure switch Restart
23 Min. room operation temperature
24 Max. room operation temperature
25 Min. room operation humidity
26 Max. room operation humidity
27 Max. refrigeration circuit pressure

Index
1 -- Preliminary operations ............................................................... pag. 1
pag. 11.1 --- Foreword ......................................................................................
pag. 11.2 --- Check operating limits ...........................................................................
pag. 11.3 --- Check sound pressure levels ......................................................................
pag. 11.4 --- Site preparation .................................................................................
pag. 11.5 --- Conditioner inspection ...........................................................................
pag. 11.6 --- General description ..............................................................................
pag. 11.7 --- Transport ......................................................................................
pag. 11.8 --- Positioning of air conditioner ......................................................................
pag. 11.9 --- Service area ....................................................................................
pag. 12 -- Mounting ............................................................................
pag. 23 -- Electrical connections ................................................................
pag. 23.1 --- Cautions .......................................................................................
pag. 23.2 --- Electrical supply ................................................................................
pag. 23.3 --- User interface ...................................................................................
pag. 23.4 --- Emergency cooling version (EFC 48 VDC and EFC 230 VAC) ..........................................
pag. 23.5 --- Electrical protection ..............................................................................
pag. 24 -- Starting and stopping ................................................................
pag. 24.1 --- First start---up (or after a long halt) .................................................................
pag. 24.2 --- Start---up with low outside temperature .............................................................
pag. 25-- Operation............................................................................
pag. 35.1 --- Adjustment of the condenser fan speed (optional) ....................................................
pag. 35.2 --- Emergency cooling (optional) .....................................................................
pag. 36-- Operatinglogics .....................................................................
pag. 36.1 --- Cooling only unit ................................................................................
pag. 36.2 --- Unit with electrical heating ........................................................................
pag. 36.3 --- Unit with freecooling .............................................................................
pag. 46.4 --- LAN local network management: Stand---by and Cascade modes ......................................
pag. 46.5 --- Alarm control ...................................................................................
pag. 46.6 --- Alarm board (optional) ...........................................................................
pag. 47-- Calibrations .........................................................................
pag. 47.1 --- Environment protection ..........................................................................
pag. 58 -- Maintenance / Spare parts ............................................................
pag. 58.1 --- Routine maintenance ............................................................................
pag. 58.2 --- Extraordinary maintenance .......................................................................
pag. 68.3 --- Dismantling the unit .............................................................................
pag. 68.4 --- Spare parts ....................................................................................
pag. 68.5 --- Regulation (EC) no. 517/2014 (F ---gas) .............................................................
Tables ............................................................... ..................... pag. 8
Drawings ................................................................................. pag. 16
Diagrams ................................................................................. pag. 26

pag. 1
1 --- Preliminary operations
1.1 --- Foreword
The following manual describes the installation, operation and
maintenance of Air Conditioners, series Liebert HPW.
Important:
Also consult the manual for the microprocessor control sup-
plied with the machine (if installed).
1.2 --- Check operating limits
The units are designed to operate within working ranges (see
from Tab. 1 to Tab. 6). These limits are referred to new
ma-chines or for those that have been correctly installed and
ser-viced. The warranty clauses are no longer valid for any
dam-age or malfunction that may occur during or due to
operation outside the application values.
1.3 --- Check sound pressure levels
From Tab. 1 to Tab. 6 shows, for the internal and the
external side, the sound pressure levels of the units in
standard config-uration, in continuous operation, at 2 m from
the front surface of the machine, at 1 m height in free field
conditions.
1.4 --- Site preparation
Liebert HPW shall be mounted on a flat vertical surface.
Prepare cut---outs on the wall for air supply and intake, electric-
al connections and unit fixing, according to the attached
tem-plate (see Fig. 7 and Fig. 8). Wall cut outs shall be
taped or sealed to prevent air or moisture entering the wall
cavity.
1.5 --- Conditioner inspection
On receiving the equipment immediately inspect its condition;
report any damage to the transport company at once.
1.6 --- General description
Liebert HPW canbeconfiguredinoverflow(Liebert HPW --- -
O) or down flow (Liebert HPW---D) version, resulting as
ex-tremely adaptive to different site layout; whatever is the
chosen delivery air version wall cuts are the same, the
condenser sec-tion is always positioned on the top part of
the unit reducing critical environment impact on condenser
efficiency and per-mitting easier and more effective
maintenance activities.
Liebert HPW, equipped withe the Emergency Cooling feature,
does not stop the operation even in case of mains failure:
fed by 48 V DC emergency supply from back up systems,
Liebert HPW autosets its parameters to ventilate and
maximise the freecooling to keep the indoor temperature
below the shut down limit, reliablity of the site means also
reliability of the unit. Downflow model allows to start the
Emergengy Freecooling at a higher external temperature,
reducing the site shut down risks.
No piping or refrigeration work is requested on site: just pre-
pare cut---outs in the wall, according to the template, andmake
power available. As soon the unit is fixed and sealed on
the wall, place the remote display in a suitable position and
feed the unit.
Installation can be further speeded up using the fast plug con-
nector option (available on request): no wiring is requested on
site and the connection can be performed even by non skilled
personnel. In case of unit replacement, the fast plugs allow
re-placement ina few minutes.
The unit is designed to be installed outdoor, coping with the
worst weather conditions.
The self ---supporting cabinet is made of heavy gauge galva-
nised steel panels, painted on both sides with RAL7035 poly-
ester powder, insulated with polyurethane foam, fire---proof
class 1. Fixed panels are secured by water---tight, aluminum
rivets. All external screws are anti---vandalism type, to be
opened with a special tool supplied with the unit. Metal safety
grids rated IP20 --- protect the machine and prevent contact
with sensitive/dangerous components.
The refrigeration compressor is a hermetic, scroll type, com-
plete with internal protection against over heating. A crankcase
heater maintains a minimum refrigerant temperature to
allow reliable start---up and operation even in very cold
climate. Thecircuitispre---
chargedwithrefrigerantandincludesather-mostatic expansion
valve, filter dryer and sight glass, low pres-sure and high
pressure switches and two access valves. The compressor is
housed in a compartment separated from the air flow and
protected by an insulated panel closed with anti---vandalism
screws, accessible from the front side for complete
maintenance.
The electrical board is housed in a compartment isolated from
the air stream and closed by a screwed on panel. It is built in
accordance with EN 60204---1 recommendations.
1.7 --- Transport
Always keep the unit vertically upright.
If possible transport the unit using a fork lift truck;
otherwise use a crane with belts or cables, avoiding the
exerting of pressure on the top edges of the packing.
Unpack the unit as close as possible to its installation posi-
tion. Once unpacked, avoid stress being transmitted to its
internal components.
For lifting the unit, the eyebolts available as accessory can
be used.
Attention:
--- use eyebolts with thread M10;
--- screw the eyebolt completely;
--- always use 4 eyebolts at the same time.
1.8 --- Positioning of air conditioner
S The air Conditioner shall be installed in any
environment
not affected by chemical agents (i.e. acid vapours).
Position the air conditioner so as to optimise the indoor air
distribution and avoid hot spots.
1.9 --- Service area
The unit must be provided with a suitable Service Area, as
fol-lows (see Fig. 5):
All ordinary maintenance can be performed from the
front.
Avoid possible obstacles hindering the air flows on the unit
outer side.
2 --- Mounting
For a correct installation proceed as follows:
Apply an insulating anti---vibration rubber between the unit
and the wall (see Fig. 9).
Before installing the unit open the integrated ducts for
the air distribution (fins) in the openings of the rear panel,
as in-dicated in the following points (1) and (2) and in
Fig. 10.
12
Secure the unit to the wall with 5+5 fasteners, flat---
head type with washer and nut on the indoor side (see
from Fig. 1 to Fig. 4). Hallow wall anchors or lag bolts
are suit-able as dictated by the wall constructions.
Seal the external boundary of the unit as preference
(see Fig. 9).
Caution: The units are designed to keep the room to be
conditioned as plenum, to prevent external dirt and
con-taminating agents from entering.
Plenum may reach high values in very sealed sites or if
the filters are not correctly serviced. In this way, doors and
win-dows are less functional and the unit efficiency is
de-

pag. 2
creased.
In these cases, Vertiv recommends a plenum damper
sized 600 x 400 mm (Vertiv code 134992) to be wall
or window mounted.
3 --- Electrical connections
3.1 --- Cautions
Before performing any operations on the electric parts, make
sure that:
all electrical components are undamaged;
allterminalscrewsare tight;
the supply voltage and frequency are as indicated on the
unit;
the automatic switch QF1 is in open position (OFF), for
units in “no emergency cooling version”.
the automatic switches QF1 and QF3 are in open position
(OFF), for units in “emergency cooling version”.
there are no components under voltage.
3.2 --- Electrical supply
Let the electrical power supply (not powered) pass through the
holes placed in the back panel of the air conditioner (see from
Fig. 1 to Fig. 4).
Caution: use screened cables for high voltage power supply,
with suitable section, and route them to the electrical panel.
Use copper conductors only.
Connect the power supply cable to the main switch QF1 inside
the electrical panel. Connect the earth cable to the yellow---
-green clamp. The alarm contacts available in the different
ver-sions are located inside the electrical panel. For the
alarms de-scription see chapter 6.5 and manual of the
installation control.
3.3 --- User interface
The control microprocessor board is inside the electric board
and is connected with the user interface (remote display) that
can be positioned inside the room as wished. The user
interface (remote display), on a painted metal box, connected
with the conditioner through a multi---pole screened cable,
standard supplied.
The user interface is graphic type (with graphic display and
keypad).
3.4 --- Emergency cooling version
(EFC 48 VDC and EFC 230 VAC)
When this option is available let pass the supply cable as
de-scribed in par. 3.2 and connect them to switch QF3
according to the diagram.
In the 48---VDC units respect the polarity “+” and “---”.
In the EFC 230 Vac units the emergency electrical line has to
be always present.
3.5 --- Electrical protection
Caution: For the electrical protection of the conditioner an
adequate switch with current protection must be installed in
the power supply line. For the selection of the disconnect
switch please refer to the Tab. 7.
4 --- Starting and stopping
4.1 --- First start---up (or after a long halt)
Before starting the air conditioner do check if the power supply
voltage and frequency comply with those indicated on the
identification plate of the unit. After this, it is possible to power
the unit operating on the main switches QF1 and QF3
(only QF1 for units in “no emergency cooling version”), that
can be reached removing the front middle panel. For
the units equipped with microprocessor control, and after
having operated on the switches to ensure a suitable power
supply, it is possible to start and stop the unit following the
instructions here below.
On the user interface:
-check that the fans are working correctly;
-make sure that the temperature is guaranteed
and the compressor and the heaters (optional) work
when re-quired;
-make sure that the speed adjuster of the fan of the
con-densing section controls the fan operation (see chap.
7).
Note: turn the main switches QF1 and QF3 OFF (only QF1 for
units in “no emergency cooling version”) only if the unit is
stopped for a long time.
4.2 --- Start---up with low outside temperature
In case of low outside temperature (<0_C), the unit start---up is
helped by the delay time of the low pressure alarm
activation, within which the pressures in the refrigerating
circuit reach the standard operation values.
5 --- Operation
The unit operation is completely automatic. The below se-
quence explains (with the assistance of Fig. 11 and Fig. 12--- -
Operation diagram) how the unit operates (see also Fig. 13
--- Refrigerating diagram):
1) The temperature sensor, positioned inside the conditioned
room, informs the control about the condition of the air to
be conditioned.
2) The control compares the information received with the set
values of Set Point (= wished min. inner temperature)
and Proportional Band (and differential in the versions
with
Freecoolingoption),settingthe conditioner for theair
treatment in the following modes:
Cooling (Fig. 11 and Fig. 12)
After switching the unit on, the evaporating fan is
immediately started while the compressor is started when the
temperature of the room to be conditioned exceeds the set
value. The con-densing fan is automatically started when
the condensing pressure changes. The air taken in by the
centrifugal fan enters the unit through the suction inlet,
immediately passes through the filter and then the evaporator.
The cold refrigerant flows in-side the pipes of the evaporator,
thus cooling the air crossing it. The treated air is conveyed in
the conditioned room through the delivery inlet. The heat
taken from the room and the one generated by the
conditioner motor operation are disposed through the
condenser placed in the lower part of the unit and hit, thanks
to the fan, by the outside air. The fan operation is managed
with Variex, see par. 5.1 as a function of the con-design
pressure. For the operation logics of the control see chapter 6
Pressing the On/Off Key ( ) the Unit ON/OFF window will
appear. The unit is switched ON or OFF pressing the
Increase ( ) or Decrease ( ) Key for 3 seconds.;
Important! Itisextremelyimportanttoconsider the status of
the digital input of the microprocessor control managing the
unit ON ---OFF (see relevant handbook and wiring diagram).
Indeed, for the unit to start the digital input must be bridged
(see wiring diagram).
Check that there are no active alarms; wait until
the system reaches the standard operation and then make
the following checks:

pag. 3
Freecooling -- (Fig. 11 and Fig. 12)
When the outdoor temperature is lower than the indoor one,
the integrated modulating damper does open/close to cool the
room with external air: compressor is off. The exhaust warmer
air is automatically rejected outside through the unit, without
any additional louver (e.g. overpressure damper). The para-
meters can be adjusted. A dedicated temperature sensor is
present in the air delivery section to prevent the air from
enter-ing the room at too low temperatures (adjustable
parameter). The unit is further equipped with a washable
metal filter next to the outside air suction inlet. When the
expected conditions oc-cur, the servocontrol, managed by the
microprocessor control, opens the movable damper
separating the flows of the inside and outside air. In this way
the outside air, sucked by the fan, flows inside the room and
is discharged through the openings of the freecooling
compartment. The opening degree of the damper is
determined as a function of the set point value to be kept and
of the intake air temperature (see Chap. 6).
5.1 --- Adjustment of the condenser fan
speed (optional)
A sensor is positioned so as to detect constantly the
condens-ing pressure of the refrigeration gas. On the basis
of this in-formation, an electronic device (Variex) modulates
the fan ro-tation speed in order to keep the condensing
pressure within the allowed values. In this way, besides
optimizing the com-pressor operation, you can have a
remarkable reduction of the sound pressure level (mainly
during the night), an easier start---up of the compressor at
low temperatures and some en-ergy saving.
For the calibration of the speed adjuster refer to chap. 7.
5.2 --- Emergency cooling (optional)
5.2.1 -- Emergency cooling 48VDC
The 48 VDC emergency cooling provides for the evaporating
fans, the freecooling damper and the control to be always sup-
plied at 48 VDC, while the compressor, the condensing fan
and the heaters are connected with the AC mains. If the AC
main supply fails, the conditioner does not stop but
continues to ventilate, activating the integrated Freecooling
as soon as the relevant conditions are reached,
automatically optimized in emergency.
Important! For proper operation, the unit must be always
fed by 48VDC.
CAUTION: For safety reasons disconnect the QF1 and
QF3 switches (only QF1 for units in “no emergency cooling
ver-sion”) when you want to stop the unit.
5.2.2 -- Emergency cooling 230VAC-- 50Hz
In case of AC mains failure, the treating fans, the control
and the damper servomotor are supplied by the second
line at 230V/1Ph/50Hz arranged by the user (UPS/generator),
ensur-ing the operation as in the 48 VDC version.
6 --- Operating logics
The units, in the different versions, are featured by the auto-
matic operating logics specified here below.
6.1 --- Cooling only unit
6.1.1 -- Control logic
The control algorithm is based on a one---step adjustment for
the mechanical cooling with compressor: the control manages
all the activation delays, so as to ensure the correct
operation and extend the operating life as much as possible.
Fig. a) Operation of the cooling only unit
Set Cooling °C
Cooling only unit
PBand
6.2 --- Unit with electrical heating
6.2.1 -- Control logic
For the hot and cold version the control algorithm is based on a
one---step adjustment for the compressor---aided electric
heating and mechanical cooling. The control manages all its
lags in the activation of the compressor, as previously de-
scribed, so as to guarantee its correct operation and to make it
function as long as possible.
6.2.2 -- Dead band
In this version the parameter “Dead band”, in the “optional
devices” menu of themicroprocessor control is very important,
and enables to transfer the heating semi---band inserting a
non---sensitive area (ventilation only) between the set point
temperature and the start of the heating semi---bands (see
Fig. b). In this way, without having to modify the proportional
band, the electric heating can be activated at lower temperat-
ures (according to the value set for the dead band) compared
to the standard setting, consequently reducing the power con-
sumption of the heaters and optimizing their operation accord-
ing to the site requirements.
Fig. b) Unit operation with electrical heating
Heating Cooling °C
PBand
Dead Band
Set point CoolingHeating °C
1/2 Band 1/2 Band
1/2 Band 1/2 Band
Set point
Cooling and
heating unit
Cooling and
heating unit
with Dead
band
6.3 --- Unit with freecooling
6.3.1 -- Control logic
The control algorithm is based on a single---stage adjustment
for the heating and cooling with the compressor and on an
ad-justmentof theproportional---
integrativetypeforthecoolingin the Freecooling mode, with
setting of the set point and propor-tional band (P) (Fig. c).
The control manages all activation delays of the compressor,
as we have seen in the 2 previous cases, in order to
guarantee the proper operation and to extend its life as much
as possible. The activation of the Freecooling mode occurs as
a function of thedifference(thatcan beset)between
theinsidetemperature and the outside temperature.
This means that if the difference between the two temperatures
increases beyond a certain value, the unit automatically
passes to the Freecooling function: the compressor is de---
ac-tivated and the analog output controls the 3---point
servomotor of the damper. The damper opening is
determined as a functionof thedifferencebetween
theoutsideand insidetemperat-ures and as a function of the
intake air temperature, which can-not be lower than a preset
safety value. If the inside temperat-ure exceeds the
proportional band by more than 20% for over 10 minutes, the
unit shifts to the compressor---aided cooling and the
Freecooling mode remains de---activated for 1/2 hour. If the
inside temperature exceeds the proportional band by

pag. 4
more than 50% for over 2 minutes, the Freecooling mode
is de---activated for 1 hour, and the unit shifts to cooling by
means of the refrigerating compressor.
Fig. c) Compressor, heater and damper opening
operation
Set CoolingHeating _C
Set CoolingHeating _C
Freecooling
mode
Compressor
cooling mode
PBand
PBand
6.4 --- LAN local network management:
Stand---by and Cascade modes
The control of the units in stand---by is completely automatic,
thanks to the possibility of connection with the microprocessor
control. A unit in stand---by is automatically activated in case of
alarm locking the main unit; this occurs even if the main unit is
switched off or disappears from the system due to a failure on the
control connecting network (bus). The hourly rotation of the
stand---by units occurs automatically every 24 hours, so as to en-
able an even wear of the system components.
If the system is connected with the graphic interface, it is possible
to set a different rotation control. Activating the Cascade function, if
several units are simultaneously on with the same Set Point, the
temperature used for the control is the average of the detected
ones: in cooling mode, the proportional band is divided in as
many parts as the double of units belonging to the system, so as
to shut the total available refrigerating capacity.
The activation of the Freecooling mode (if installed) is sequential
on the different units forming the system, and precedes the pos-
sible activation of the cooling with compressor.
TheFig. d),shownasanexample,representsthe operationof
a system formed by three units.
Fig. d) System with 3 units in cascade---microprocessor
control
Set _C
CoolingHeating
31
2
311
223
Freecooling mode
PBand
Set
Compressor cooling mode
PBand
_C
CoolingHeating
6.5 --- Alarm control
The two alarm contacts available on the terminal board of the
electric board are:
1) General alarm (highest priority), including:
-compressor low pressure
-compressor high pressure (reset on the pressure switch)
-sensor fault
-memory fault
-fan fault
2) General warning (lowest priority), including:
Shigh temperature
Slow temperature
Note:
-An alarm causes the unit to stop and the unit in stand---
by (if available) to intervene.
-A warning does not stop the unit.
-Both the alarm and the warning activate sight and
sound signals.
-Both the alarm and the warning must be reset manually
on the microprocessor control.
In case the safety heater thermostat intervenes, the reset
must be carried out on the thermostat, following the same
instruc-tionsasbefore.
6.6 --- Alarm board (optional)
Besides the components described for the standard configur-
ation, an alarm card --- which can be supplied as optional
---there are relay contacts which have the following alarms:
1) compressor high and low pressure
2) High temperature
3) Low temperature
4) Indoorairclogged filteralarm
5) Fan fault
These alarms control unit in the same way as described in
the previous paragraph.
For the detailed description of the alarms, see the
micropro-cessor manual enclosed.
7 --- Calibrations
-The air conditioner has already been factory ---tested
and calibrated as described below (see Tab. 8).
-For the Microprocesso Control calibrations refer to the rel-
evant manual (to avoid wrong operations do not use
tem-perature and rel. humidity set points/proportional
bands which differ excessively from the standard
settings).
7.1 --- Environment protection
A misuse or an incorrect calibration of the unit leads to
in-creased energy consumption, resulting in an economic
and environmental damage. Use the freecooling function, if
avail-able.

pag. 5
8 --- Maintenance / Spare parts
F-or safety reasons, clear the unit opening the switch QS1 before performing any maintenance operatios
If installed:
AS THE MICROPROCESSOR CONTROL FEATURES
AUTOMATIC RESTART (AFTER A SUPPLY INTERRUPTION)
IT IS ADVISED TO DISABLE AUTORESTART AND OPEN THE
SWITCH QF1 FOR UNITS IN “NO EMERGENCY COOLING
VERSION, QF1+QF3 SWITCHES FOR UNITS IN
“EMERGENCY COOLING VERSION” WHEN PERFORMING
ANY MAINTENANCE.
SEvery day check the microprocessor control readings for
temperature and, if shown, ambient relative humidity.
SThe Maintenance Programme described below should be
carried out by a skilled technician, preferably working un-
der a maintenance contract.
8.1 --- Routine maintenance
Maintenance program -- Monthly check
FANS
Check that the fan motor rotates freely without any abnormal noise, and ensure that the
bearings are not running hot.
Also check the current absorption.
AIR FILTERS
Check the filter conditions; if necessary clean or replace them.
How to replace:
Sopen the middle panel and remove filter cover
Svertically pull the metal pre ---filter out and blow carefully
Sextract the filter from its seat horizontally
Sintroduce the spare part
Sclose the panel
In very dusty environments perform this check more frequently.
CONTROL Verify the operation of the CONTROL’s LEDs, display and alarms.
ELECTRICAL CIRCUIT SCheck the power supply on all phases.
SEnsure that all electrical connections are tight.
REFRIGERATION CIRCUIT
SCheck the evaporating pressures (to be done by a refrigeration technician).
SCheck the compressor current absorption, its head temperature and the presence of
any unusual noise.
SEnsure that there is no ice formation on the evaporator.
ATTENTION: To move manually the damper (unit check, damper movement check), press the clutch (yellow button) on the ac-
tuator and then move the damper.
Do not press the clutch (yellow button) when the actuator is powered!
8.2 --- Extraordinary maintenance
8.2.1 -- Check of the system vacuum and leaks.
Note:
Before proceeding, recover all the refrigerant, according to the
local laws.
1) Switch the unit off (outer switch on OFF) and cut off open-
ing the switch QF1 for units in “no emergency cooling ver-
sion” and QF1+QF3 for units in “emergency cooling ver-
sion”.
2) Remove the panels necessary for inspecting the refrigerat-
ing circuit.
3) Connect a high efficiency vacuum pump to the needle
valves (Schräder) on the gas and liquid lines; also arrange
a connection with a nitrogen bottle.
4) Load the circuit with nitrogen (7 bar/700 kPa). Find pos-
sible leaks in the circuit by soapy water or other specific
product (foaming agents), and repair as necessary.
5) Drain the circuit by a vacuum of 0.3 mbar absolute .
6) After 3 hours check not to have exceeded 1.3 mbar abso-
lute; this condition ensures a humidity lower than 50 ppm
inside the system. If the vacuum is not kept there are still
leaks; repeat the operations from point 4.
8.2.2 -- Refrigerant charge operations.
After having eliminated the humidity from the refrigerating cir-
cuit (see 8.2.1), proceed as follows:
1) Make sure all the unit components are in operating order.
2) By a charge hose, connect the charge cylinder to the liquid
line of the circuit. Drain the substances that cannot be con-
densed from the hose.
Charge the circuit exclusively with the
refrigerant indicated on the identification
label.
Charge the quantity of refrigerant indicated in Tab. a.
3) Close the main switch QS1 for units in “no emergency
cooling version” and QF1+QF3 for units in “emergency
cooling version” and position the outer switch on ON.
4) Start the compressor.
5) The charge operation can be considered finished when,
keeping the condensation temperature at a steady level
(~ 50°C, if necessary partially clog the condensing coil),
no more bubbles appear for at least ten minutes. Check if
the overheating in these conditions is 7÷8 degrees.
Overheating calculation
a) With the unit operating in standard conditions,
measure the temperature of the suction line in the point
where the bulb of the thermal expansion valve is
fastened.
b) Detect the evaporation pressure gauge temperature
from a pressure gauge placed on the compressor
suction.
c) Subtract the just obtained temperature value from the
one measured in point a). The difference is the
overheating value.
8.2.3 -- R407C refrigerant units
8.2.3.1 --Features of the refrigerating fluid R407C
At standard temperature and pressure it is a colourless gas with
low toxicity, non---flammable, and it has an allowed exposure limit
value (AEL/TLV) corresponding to 1000 ppm (average value
measured on 8 hours/day). In the event of leakage, air the room
before use.

pag. 6
Tab. a --- R407C refrigerant charge
MODELS
HPW WM05S WM06S WM06M WM08M
Kg 2.35 2.35 3.0 3.0
HPW WM10M WM13M WM15M ---
Kg 3.0 3.55 3.55 ---
The oil to be used when topping up is EMKARATE RL
32---3MA or MOBIL EAL ARTIC 22CC, if it’s unavailable use
an oil with the same characteristics (see Tab. b and Tab. c).
NEVER MIX DIFFERENT OILS TOGETHER. CLEAN THE
PIPING COMPLETELY BEFORE CHANGING THE TYPE OF
OIL USED.
Ta b . b --- E M K A R A T E R L 3 2 --- 3 M A o i l
viscosity at 40_C
viscosity at 100_C
viscosity index (ISO Grade)
:
:
:
31.2 cST
5.6 cST
32
Tab. c --- MOBIL EAL ARTIC 22CC oil
approx. specific weight (at 15_C)
flash point (C.O.C.)
pour point
viscosity index
viscosity at 40_C
viscosity at 100_C
:
:
:
:
:
:
0.99 kg/l
245 _C
< --- 5 4 _C
116
23.6 cST
4.7 cST
8.3 --- Dismantling the unit
The machine has been designed and built to ensure continu-
ous operation. The working life of some of the main compon-
ents, such as the fan and the compressor, depends on their
maintenance.
The unit contains substances and components
hazardous for the environment (electronic com-
ponents, refrigerating gases and oils). At the end of
the useful life, when the unit is dismantled, the op-
eration must be carried out by specialized refriger-
ating technicians. The unit must be delivered to suitable cen-
ters specialized for the collection and disposal of equipment
containing hazardous substances. The refrigerating fluid and
the lubricating oil inside the circuit must be recovered accord-
ing to the laws in force in the relevant country.
8.4 --- Spare parts
We recommend the use of original spare parts. When placing
an order please refer to “Component List” enclosed with the
machine and specify the unit model and serial no.
8.5 --- Regulation (EU) no. 517/2014 (F-gas)
Stationary air conditioners placed into the European Com-
munity market and operating
with fluorinated greenhouse gases (F- gas, such as R407C,
R134a, R410A), they have to comply
since Jan 1, 2015 with the F- gas Regulation (EU) No.
517/2014. It replaces the Re. (EU) no.
342/2006, applied since July 4, 2007.
By the way, the refrigerants as R22 are not F- gas
and their relevant regulation is Reg. (EU) no. 2037/2000.
Following notes have to be considered when
operating with the above mentioned equipments:
No 842/2006
•Fluorinated greenhouse gases are covered by the Kyoto
Protocol.
•The uorinated greenhouse gases in this equipment
should not be vented to the atmosphere.
•Referring to the value noted in Annex I and Annex IV of Regu-
lation (EU) No 517/2014 here below the global warming poten-
tial (GWP) of some major F- gases or mixtures:
R-R- GWP 1430
R-R- GWP 1774
R- GWP 2088
•Operators of the above mentioned applications, which contain
uorinated greenhouse gases, shall, using all measures which are
technically feasible and do not entail disproportionate cost:
a. Prevent leakage of these gases and as soon as possible
repair any detected leakage.
b. Ensure that they are checked for leakage by certied per-
sonnel.
c. Ensure for putting in place arrangements for the proper
recovery by certied personnel.
d. In case of applications containing 5 tons CO2equiva-
lent, i.e. 2.4 kg of R410A (10 tons in case of hermetically
sealed system) or more of F- gases: certied personnel
and Companies (according to Reg. 303/2008) provides
regular leak testing (according to Reg. 1516/2007 and
Reg. 1497/2007) and maintain records of maintenance
activities in a dedicated log book.
e. Recovery for the purpose of recycling, reclamation
or destruction of the uorinated greenhouse gases,
pursuant to Art. 8 of the Regulation shall take place
before the nal disposal of that equipment and, when
appropriate, during its servicing and maintenance.
•Operator, according to Regulation Article 2, point 8, means
the natural or legal person exercising actual power over the
technical functioning of products and equipment covered by
this Regulation. The State may, in dened, specic situations,
designate the owner as being responsible for the operator’s
obligations. Where large installations are involved, service
companies are contracted to carry out maintenance or servic-
ing. In these cases the determination of the operator depends
on the contractual and practical arrangements between the
parties.
•Direct methods of leakage checking approved by the
manufacturer (Reg. 1516/2007 and Reg. 1497/2007)
a. Gas detection device adapted to the refrigerant in the
system;the sensitive of portable gas detection devices (as a
direct test method) shall be at least ve grams par year.
b. Proprietary bubble solutions / soapsuds.
•Additional information located into a dedicated label of
unit (Reg. 1494/2007)
a. Where uorinated greenhouse gas is foreseen to be add-
ed to the equipment outside of the manufacturing site at the
point of installation, a dedicated label accommodates notation
of both the quantity (kg) pre-charged in the manufacturing
plant and of the quantity charged at the installation site as well
as the resulting total quantity of f-gas as a combination of the
above mentioned quantities, in a manner which conforms to
the legibility and indelibility.
Our split units are usually not pre-charged on factory, in this
case the total quantity of refrigerant charged in the unit has
to be written in the relevant label, during the commissioning
operation at the installation site.
b. Our packaged units (not split) operating with f - gas are
usually full charged on factory and the total amount of refrig-
erant charge is already reported on the label. In this case, the
label has no need of further written information.
c. In generally, the above mentioned information has been
located in the main nameplate of relevant unit.

pag. 7
d. For equipment with double refrigeration circuits, in re-
gards to differentiates requirements on the basis of the quan-
tity of f-gas contained, the required information about refrig-
erant charge quantities has to be listed separately for each
individual circuit.
e. For equipments with separate indoor and outdoor sec-
tions connected by refrigerant piping, the label information
will be on that part of the equipment which is initially charged
with the refrigerant. In case of a split system (separate indoor
and outdoor sections) without a factory pre-charge of refriger-
ant, the mandatory label information will be on that part of the
product or equipment which contains the most suitable service
points for charging or recovering the uorinated greenhouse
gas(es).
•Safety data sheets of f-gases used in the products are avail-
able on demand.

pag. 8
Tab. 1 -- 50Hz Technical data for “48Vdc EMERGENCY FREECOOLING” unit versions (EFC-- DC)
Model: HPW WM05SD WM05SO WM06SD WM06SO
Operating limits
Main power supply voltage 230V ±10% / 1Ph / 50Hz
Emergency power supply voltage 48Vdc ±17%
(with emergency cooling) (*)
Outdoor conditions
from 10°C(**)
from --- 3 0 °C(***)
to 49°C(****) 49.5°C(****) 47°C(****) 47.5°C(****)
Indoor conditions with compressor running (*****) from 20°C , 3 0 ---
80% R.H. 21°C, 30---80% R.H. 22°C , 3 0 ---
80% R.H.
to 35°C, 40% R.H.
Storage conditions from --- 4 0 °C, 5% R.H.
to 55°C, 90% R.H.
Sound pressure level
Outdoor sound pressure level (1) dB(A) 52.5 52.5 54.0 54.0
Indoor sound pressure level (1) dB(A) 57.0 57.0 57.0 57.0
Standard electrical features
Compressor --- AC power input (2) kW 1.26 1.25 1.63 1.63
Compressor --- AC operative current (OA) (2) A5.8 5.7 7.6 7.6
Compressor --- AC max. current (FLA) A10.0 10.0 11.4 11.4
Compressor --- AC starting current (LRA) A35.0 35.0 47.0 47.0
Condenser fan --- AC power input (2) kW 0.24 0.24 0.24 0.24
Condenser fan --- AC max. power input kW 0.24 0.24 0.24 0.24
Condenser fan --- AC operative current (OA) (2) A1.1 1.1 1.1 1.1
Condenser fan --- AC max. current (FLA) A1.4 1.4 1.4 1.4
Condenser fan --- AC starting current (LRA) A1.6 1.6 1.6 1.6
Evaporator fan --- DC power input (2) kW 0.10 0.10 0.10 0.10
Evaporator fan --- DC operative current (OA) (2) A2.6 2.6 2.6 2.6
Evaporator fan --- DC max. current (FLA) (3) A2.6 2.6 2.6 2.6
Evaporator fan --- DC starting current (LRA) A0.1 0.1 0.1 0.1
Electric heating (optional)
Heating capacity kW 1.5
H e a t i n g --- m a x . c u rr e n t A6.5
Weight kg 170 175
OA: Standard Operating Ampère
FLA: Full Load Ampère
LRA: Locked Rotor Ampère
Notes:
(*) The emergency cooling option (EFC) is required.
(**) If ON/OFF condensing fan control option has been chosen.
(***) If modulating condensing fan control (Variex) option has been chosen.
(****) Maximum outdoor temperature referred to:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM05---06SD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM05---06SO models.
(*****) Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min. outdoor
temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.
(1) Measured with 35° C outdoor temperature at 2m far from the unit; free field conditions.
(2) Electrical features are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM05---06SD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM05---06SO models.
(3) It refers to nominal speed (Factory setting).

pag. 9
Tab. 2 -- 50Hz Technical data for “48Vdc EMERGENCY FREECOOLING” unit versions (EFC-- DC)
Model: HPW WM06MD WM06MO WM08MD WM08MO WM10MD WM10MO
Operating limits
Main power supply voltage 230V ±10% / 1Ph / 50Hz 400V ±10% / 3Ph+N+PE / 50Hz
Emergency power supply voltage 48Vdc ±17%
(with emergency cooling) (*)
Outdoor conditions
from 10°C(**)
from --- 3 0 °C(***)
to 52°C(****) 50.5°C(****) 50°C(****)
Indoor conditions with compressor running (*****)
from 21°C , 3 0 ---
80% R.H.
22°C , 3 0 ---
80% R.H. 20°C, 30---80% R.H. 21°C, 30---80% R.H.
to 35°C, 40% R.H. 34°C,
40% R.H.
33°C,
40% R.H.
35°C,
40% R.H.
33°C,
40% R.H.
Storage conditions from --- 4 0 °C, 5% R.H.
to 55°C, 90% R.H.
Sound pressure level
Outdoor sound pressure level (1) dB(A) 50.0 49.5 52.0 52.0 55.0 55.0
Indoor sound pressure level (1) dB(A) 57.0 57.0 60.0 64.0 64.0 64.0
Standard electrical features
Compressor --- AC power input (2) kW 1.46 1.49 1.90 1.93 2.66 2.68
Compressor --- AC operative current (OA) (2) A6.8 7.0 3.5 3.5 4.8 4.9
Compressor --- AC max. current (FLA) A11.4 11.4 5.1 5.1 7.0 7.0
Compressor --- AC starting current (LRA) A47.0 47.0 32.0 32.0 46.0 46.0
Condenser fan --- AC power input (2) kW 0.20 0.20 0.22 0.22 0.72 0.72
Condenser fan --- AC max. power input kW 0.23 0.23 0.23 0.23 0.78 0.78
Condenser fan --- AC operative current (OA) (2) A1.1 1.1 1.1 1.1 3.5 3.5
Condenser fan --- AC max. current (FLA) A1.4 1.4 1.4 1.4 3.5 3.5
Condenser fan --- AC starting current (LRA) A1.6 1.6 1.6 1.6 7.4 7.4
Evaporator fan --- DC power input (2) kW 0.10 0.10 0.28 0.45 0.45 0.45
Evaporator fan --- DC operative current (OA) (2) A2.6 2.6 5.8 9.4 9.5 9.5
Evaporator fan --- DC max. current (FLA) (3) A2.6 2.6 9.6 9.6 9.6 9.6
Evaporator fan --- DC starting current (LRA) A0.1 0.1 0.1 0.1 0.1 0.1
Electric heating (optional)
Heating capacity kW 1.5 3.0
H e a t i n g --- m a x . c u rr e n t A6.5 6.5
Weight kg 195 205 220
OA: Standard Operating Ampère
FLA: Full Load Ampère
LRA: Locked Rotor Ampère
Notes:
(*) The emergency cooling option (EFC) is required.
(**) If ON/OFF condensing fan control option has been chosen.
(***) If modulating condensing fan control (Variex) option has been chosen.
(****) Maximum outdoor temperature referred to:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MO models.
(*****) Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min. outdoor
temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.
(1) Measured with 35° C outdoor temperature at 2m far from the unit; free field conditions.
(2) Electrical features are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MO models.
(3) It refers to nominal speed (Factory setting).

pag. 10
Tab. 3 -- 50Hz Technical data for “48Vdc EMERGENCY FREECOOLING” unit versions (EFC-- DC)
Model: HPW WM13MD WM13MO WM15MD WM15MO
Operating limits
Main power supply voltage 400V ±10% / 3Ph+N+PE / 50Hz
Emergency power supply voltage 48Vdc ±17%
(with emergency cooling) (*)
Outdoor conditions
from 10°C(**)
from --- 3 0 °C(***)
to 51°C(****) 48.5°C(****)
Indoor conditions with compressor running (*****) from 22°C, 30--- 80% R.H. 24°C, 30---80% R.H.
to 32°C, 40% R.H.
Storage conditions from --- 4 0 °C, 5% R.H.
to 55°C, 90% R.H.
Sound pressure level
Outdoor sound pressure level (1) dB(A) 55 55 58 58
Indoor sound pressure level (1) dB(A) 59 64 63 67
Standard electrical features
Compressor --- AC power input (2) kW 2.56 2.60 3.29 3.30
Compressor --- AC operative current (OA) (2) A4.8 4.9 6.1 6.1
Compressor --- AC max. current (FLA) A 7 7 10 10
Compressor --- AC starting current (LRA) A46 46 50 50
Condenser fan --- AC power input (2) kW 0.68 0.68 0.69 0.72
Condenser fan --- AC max. power input kW 0.78 0.78 0.78 0.78
Condenser fan --- AC operative current (OA) (2) A3.4 3.5 3.3 3.5
Condenser fan --- AC max. current (FLA) A3.5 3.5 3.5 3.5
Condenser fan --- AC starting current (LRA) A7.4 7.4 7.4 7.4
Evaporator fan --- DC power input (2) kW 0.45 0.45 0.82 0.78
Evaporator fan --- DC operative current (OA) (2) A9.5 9.5 17.2 16.3
Evaporator fan --- DC max. current (FLA) (3) A9.6 9.6 19.2 19.2
Evaporator fan --- DC starting current (LRA) A0.1 0.1 0.1 0.1
Electric heating (optional)
Heating capacity kW 3.0 6.0
H e a t i n g --- m a x . c u rr e n t A6.5 13.0
Weight kg 250 260
OA: Standard Operating Ampère
FLA: Full Load Ampère
LRA: Locked Rotor Ampère
Notes:
(*) The emergency cooling option (EFC) is required.
(**) If ON/OFF condensing fan control option has been chosen.
(***) If modulating condensing fan control (Variex) option has been chosen.
(****) Maximum outdoor temperature referred to:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM13---15MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM13---15MO models.
(*****) Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min. outdoor
temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.
(1) Measured with 35° C outdoor temperature at 2m far from the unit; free field conditions.
(2) Electrical features are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM13---15MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM13---15MO models.
(3) It refers to nominal speed (Factory setting).

pag. 11
Tab. 4 -- 50 Hz Technical data for “NO FREECOOLING”, “FREECOOLING” and “230V/1Ph/50Hz
EMERGENCY FREECOOLING” unit versions (NO FC, FC and EFC-- AC)
Model: HPW WM05SD WM05SO WM06SD WM06SO
Operating limits
Main power supply voltage 230V ±10% / 1Ph / 50Hz
Emergency power supply voltage 230V ±10% / 1Ph+PE / 50Hz
(with emergency cooling) (*)
Outdoor conditions (**)
from 10°C(**)
from --- 3 0 °C(***)
to 49°C(****) 49.5°C(****) 47°C(****) 47.5°C(****)
Indoor conditions with compressor running (*****) from 20°C , 3 0 ---
80% R.H. 21°C, 30---80% R.H. 22°C , 3 0 ---
80% R.H.
to 35°C, 40% R.H.
Storage conditions from --- 4 0 °C, 5% R.H.
to 55°C, 90% R.H.
Sound pressure level
Outdoor sound pressure level (1) dB(A) 52.5 52.5 54.0 54.0
Indoor sound pressure level (1) dB(A) 56.0 56.0 56.0 56.0
Standard electrical features
Compressor --- AC power input (2) kW 1.26 1.25 1.63 1.63
Compressor --- AC operative current (OA) (2) A5.8 5.7 7.6 7.6
Compressor --- AC max. current (FLA) A10.0 10.0 11.4 11.4
Compressor --- AC starting current (LRA) A35.0 35.0 47.0 47.0
Condenser fan --- AC power input (2) kW 0.24 0.24 0.24 0.24
Condenser fan --- AC max. power input kW 0.24 0.24 0.24 0.24
Condenser fan --- AC operative current (OA) (2) A1.1 1.1 1.1 1.1
Condenser fan --- AC max. current (FLA) A1.4 1.4 1.4 1.4
Condenser fan --- AC starting current (LRA) A1.6 1.6 1.6 1.6
Evaporator fan --- AC power input (2) kW 0.14 0.14 0.14 0.14
Evaporator fan --- AC operative current (OA) (2) A0.7 0.7 0.7 0.7
Evaporator fan --- AC max. current (FLA) (3) A0.7 0.7 0.7 0.7
Evaporator fan --- AC starting current (LRA) A1.2 1.2 1.2 1.2
Electric heating (optional)
Heating capacity kW 1.5
H e a t i n g --- m a x . c u rr e n t A6.5
Weight kg 170 175
OA: Standard Operating Ampère
FLA: Full Load Ampère
LRA: Locked Rotor Ampère
(*) The emergency cooling option (EFC) is required.
(**) If ON/OFF condensing fan control option has been chosen.
(***) If modulating condensing fan control (Variex) option has been chosen.
(****) Maximum outdoor temperature referred to:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM05---06SD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM05---06SO models.
(*****) Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min. outdoor
temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.
(1) Measured with 35° C outdoor temperature at 2m far from the unit; free field conditions.
(2) Electrical features are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM05---06SD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM05---06SO models.
(3) It refers to nominal speed (Factory setting).

pag. 12
Tab. 5 -- 50 Hz Technical data for “NO FREECOOLING”, “FREECOOLING” and “230V/1Ph/50Hz
EMERGENCY FREECOOLING” unit versions (NO FC, FC and EFC-- AC)
Model: HPW WM06MD WM06MO WM08MD WM08MO WM10MD WM10MO
Operating limits
Main power supply voltage 230V ±10% / 1Ph / 50Hz 400V ±10% / 3Ph+N+PE / 50Hz
Emergency power supply voltage 230V ±10% / 1Ph+PE / 50Hz
(with emergency cooling) (*)
Outdoor conditions (**)
from 10°C(**)
from --- 3 0 °C(***)
to 52°C(****) 50.5°C(****) 50°C(****)
Indoor conditions with compressor running (*****)
from 21°C , 3 0 ---
80% R.H.
22°C , 3 0 ---
80% R.H. 20°C, 30---80% R.H. 22°C, 30---80% R.H.
to 35°C, 40% R.H. 33°C, 40% R.H. 35°C,
40% R.H.
33°C,
40% R.H.
Storage conditions from --- 4 0 °C, 5% R.H.
to 55°C, 90% R.H.
Sound pressure level
Outdoor sound pressure level (1) dB(A) 50.0 49.5 52.0 52.0 55.0 55.0
Indoor sound pressure level (1) dB(A) 56.0 56.0 60.0 60.0 60.0 60.0
Standard electrical features
Compressor --- AC power input (2) kW 1.46 1.49 1.90 1.93 2.66 2.68
Compressor --- AC operative current (OA) (2) A6.8 7.0 3.5 3.5 4.7 4.9
Compressor --- AC max. current (FLA) A11.4 11.4 5.1 5.1 7.0 7.0
Compressor --- AC starting current (LRA) A47.0 47.0 32.0 32.0 46.0 46.0
Condenser fan --- AC power input (2) kW 0.20 0.20 0.22 0.22 0.71 0.72
Condenser fan --- AC max. power input kW 0.23 0.23 0.23 0.23 0.78 0.78
Condenser fan --- AC operative current (OA) (2) A1.1 1.1 1.1 1.1 3.5 3.5
Condenser fan --- AC max. current (FLA) A1.4 1.4 1.4 1.4 3.5 3.5
Condenser fan --- AC starting current (LRA) A1.6 1.6 1.6 1.6 7.4 7.4
Evaporator fan --- AC power input (2) kW 0.15 0.15 0.47 0.48 0.48 0.48
Evaporator fan --- AC operative current (OA) (2) A0.7 0.7 2.3 2.3 2.3 2.3
Evaporator fan --- AC max. current (FLA) (3) A0.7 0.7 2.4 2.4 2.4 2.4
Evaporator fan --- AC starting current (LRA) A1.2 1.2 9.6 9.6 9.6 9.6
Electric heating (optional)
Heating capacity kW 1.5 3.0
H e a t i n g --- m a x . c u rr e n t A6.5
Weight kg 195 205 220
OA: Standard Operating Ampère
FLA: Full Load Ampère
LRA: Locked Rotor Ampère
Notes:
(*) The emergency cooling option (EFC) is required.
(**) If ON/OFF condensing fan control option has been chosen.
(***) If modulating condensing fan control (Variex) option has been chosen.
(****) Maximum outdoor temperature referred to:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MO models.
(*****) Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min. outdoor
temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.
(1) Measured with 35° C outdoor temperature at 2m far from the unit; free field conditions.
(2) Electrical features are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM06 --- 08 --- 10MO models.
(3) It refers to nominal speed (Factory setting).

pag. 13
Tab. 6 -- 50 Hz Technical data for “NO FREECOOLING”, “FREECOOLING” and “230V/1Ph/50Hz
EMERGENCY FREECOOLING” unit versions (NO FC, FC and EFC-- AC)
Model: HPW WM13MD WM13MO WM15MD WM15MO
Operating limits
Main power supply voltage 400V ±10% / 3Ph+N+PE / 50Hz
Emergency power supply voltage 230V ±10% / 1Ph+PE / 50Hz
(with emergency cooling) (*)
Outdoor conditions (**)
from 10°C(**)
from --- 3 0 °C(***)
to 51°C(****) 48.5°C(****)
Indoor conditions with compressor running (*****) from 23°C, 30--- 80% R.H. 25°C, 30---80% R.H.
to 33°C, 40% R.H.
Storage conditions from --- 4 0 °C, 5% R.H.
to 55°C, 90% R.H.
Sound pressure level
Outdoor sound pressure level (1) dB(A) 55.0 55.0 58.0 58.0
Indoor sound pressure level (1) dB(A) 56.0 60.0 59.0 63.0
Standard electrical features
Compressor --- AC power input (2) kW 2.56 2.60 3.27 3.30
Compressor --- AC operative current (OA) (2) A4.8 4.9 6.1 6.1
Compressor --- AC max. current (FLA) A7.0 7.0 10.0 10.0
Compressor --- AC starting current (LRA) A46.0 46.0 50.0 50.0
Condenser fan --- AC power input (2) kW 0.68 0.68 0.69 0.72
Condenser fan --- AC max. power input kW 0.78 0.78 0.78 0.78
Condenser fan --- AC operative current (OA) (2) A3.5 3.5 3.3 3.5
Condenser fan --- AC max. current (FLA) A3.5 3.5 3.5 3.5
Condenser fan --- AC starting current (LRA) A7.4 7.4 7.4 7.4
Evaporator fan --- AC power input (2) kW 0.49 0.49 0.78 0.80
Evaporator fan --- AC operative current (OA) (2) A2.4 2.4 3.9 3.9
Evaporator fan --- AC max. current (FLA) (3) A2.4 2.4 4.8 4.8
Evaporator fan --- AC starting current (LRA) A9.6 9.6 19.2 19.2
Electric heating (optional)
Heating capacity kW 3.0 6.0
H e a t i n g --- m a x . c u rr e n t A6.5 13.0
Weight kg 250 260
OA: Standard Operating Ampère
FLA: Full Load Ampère
LRA: Locked Rotor Ampère
Notes:
(*) The emergency cooling option (EFC) is required.
(**) If ON/OFF condensing fan control option has been chosen.
(***) If modulating condensing fan control (Variex) option has been chosen.
(****) Maximum outdoor temperature referred to:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM13---15MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM13---15MO models.
(*****) Conditions referred to the evaporating suction side; the min. indoor temperature is referred to 30% of indoor relative humidity and to the min. outdoor
temperature; for higher relative humidity and/or outdoor temperatures, the min. indoor temperature is lower than the table data.
(1) Measured with 35° C outdoor temperature at 2m far from the unit; free field conditions.
(2) Electrical features are referred to 35°C outdoor temperature, to nominal power supply and to the following Indoor conditions:
--- 30°C / 39.5% R.H. at the evaporating suction side, for WM13---15MD models;
--- 27°C / 47% R.H. at the evaporating suction side, for WM13---15MO models.
(3) It refers to nominal speed (Factory setting).

pag. 14
Tab. 7 -- Differential current protection switch
50Hz unit versions (”cooling only”,
“cooling+heating” and “freecooling”)
Differential current protection switch
Inn = 0.03A Minimum
cable sizing
2poles 4poles
Unit power supply 230V / 1Ph / 50Hz 400V / 3Ph+N / 50Hz
WM05S
WM06S 25A
(”C” curve)
--- 3G2.5mm2
(2 x 2.5mm2+Tx2.5mm
2)
WM06M ---
WM08M
WM10M
WM13M
--- 25A
(”C” curve)
5G2.5mm2
(4 x 2.5mm2+Tx2.5mm
2)
WM15M --- 32A
(”C” curve)
5G4.0mm2
(4 x 4mm2+Tx4mm
2)
230V/1Ph/50Hz
“Emergency freecooling” unit version
Differential current protection switch
Inn = 0.03A
Minimum
cable sizing
2poles 4poles
Main line power supply 230V / 1Ph / 50Hz 400V / 3Ph+N / 50Hz
Unit EFC---AC line power supply 230V / 1Ph+N / 50Hz
main line E F C --- A C
line main line E F C --- A C
line main line E F C --- A C
line
WM05S
WM06S 25A
(”C” curve)
10A
(”C” curve)
--- --- 3G2.5mm2
(2 x 2.5mm2+
T x 2.5mm2)
3G1.5mm2
(2 x 1.5mm2+
T x 1.5mm2)
WM06M --- ---
WM08M
WM10M
WM13M
--- --- 25A
(”C” curve)
10A
(”C” curve)
5G2.5mm2
(4 x 2.5mm2+
T x 2.5mm2)
WM15M --- --- 32A
(”C” curve)
5G4.0mm2
(4 x 4mm2+
Tx4mm
2)
48VDC
“Emergency freecooling” unit version
Differential current protection switch I nn = 0.03A
Minimum
cable sizing
2poles 4poles
Main line power supply 230V / 1Ph / 50Hz 400V / 3Ph+N / 50Hz
Unit EFC---DC line power supply 48VDC
main line E F C --- D C
line main line E F C --- D C
line main line E F C --- D C
line
WM05S
WM06S
25A
(”C” curve)
6A
(”C” curve) --- --- 3G2.5mm2
(2 x 2.5mm2+
T x 2.5mm2)2 x 2.5mm2
WM06M 20A
(”C” curve) --- ---
WM08M
WM10M
WM13M
--- --- 25A
(”C” curve)
20A
(”C” curve)
5G2.5mm2
(4 x 2.5mm2+
T x 2.5mm2)
WM15M --- --- 32A
(”C” curve)
25A
(”C” curve)
5G4.0mm2
(4 x 4mm2+
Tx4mm
2)
2 x 4.0mm2
Notes:
•The cables have to be sized in compliance with local standards and according to the type and characteristics (e.g. Amperes) of installation.
•The specific power of the user--- installed switch, must be lower than 300.000 (A2xs).
•Prescriptions on the differential relay required to the user:
--- for special places (healthcare facilities, etc.) comply with the local regulations;
--- for ordinary places, a low sensitivity is suggested (30 mA) coordinated with the value of the ground heater (IEC 364): Ra ≤50/la(Art. 413.1.4.1, CEI 64 --- 8);
--- in case of frequent over--- voltages with mains impulse, it is advisable to install a selective differential and to evaluate the need for adopting other devices.

pag. 15
Tab. 8 -- Settings
Component Setting Notes
Low pressure switch (LP)
STOP: 1.0 bar
START: 2.0 bar
(fixed settings)
Automatic reset
High pressure switch (HP)
STOP: 28.0 bar
START: 20.0 bar
(fixed settings)
Manual reset pressing
the push button
Fan speed controller (BV)
(optional)
S E T ( C U T --- O F F ) :
•21.2 bar (standard factory set)
•15.0 bar (optional set)
MAX. SPEED:
•25.0 bar (standard factory set)
•18.8 bar (optional set)
P. B A N D : 3 . 8 b a r
(for the adjustment refer to the
instructions supplied with the machine)

pag. 16
Fig. 1 -- Overall dimensions -- Liebert HPW models WM05--06SD
800
1690
791 370 118
50 450
60 740 60
460 1230
60 50
15 828 15
858
100 380 380 380 380 70
37045
TOP VIEW
FRONT VIEW REAR VIEWSX SIDE VIEW DX SIDE VIEW
450
N. 5+5 holes ø8 for conditioner fixing
Electrical supply
Conditioned air inlet Conditioned air outlet
Condensing air inlet
Freecooling air outlet
Freecooling air inlet
Condensing air outlet
50
This manual suits for next models
14
Table of contents
Other Vertiv Freezer manuals

Vertiv
Vertiv Liebert DSE User manual

Vertiv
Vertiv Liebert XDP Series User manual

Vertiv
Vertiv VRC1 Series User manual

Vertiv
Vertiv VRC1 Series User manual

Vertiv
Vertiv Liebert HPM User manual

Vertiv
Vertiv Liebert DSE060 Installation and maintenance instructions

Vertiv
Vertiv VRC100 Series Installation and maintenance instructions

Vertiv
Vertiv Liebert XDC User manual