2
• If replacing an existing Room Controller label wires before
removal of Controller.
• Electronic controls are static sensitive devices. Discharge
yourself correctly before manipulating and installing Room
Controller.
• A short circuit or wrong wiring may permanently damage
Controller or equipment.
• All VT8600 series controls are designed for use as operating
controls only and are not safety devices. Tampering with the
devices or unintended application of the devices will result
in a void of warranty.
• This device must be installed to provide a separation
distance of at least 8in (20cm) from all persons and must
not be collocated or operating in conjunction with any other
antenna or transmitter.
Figure-1 Open cover
Figure-2 Install base
Figure-3 Reinstall cover
INSTALLATION
Location
• Do not install on outside wall.
• Do not install in areas with direct heat source.
• Do not install near any air discharge grill.
• Do not install in areas exposed to direct sunlight.
• Ensure Room Controller has sufficient air circulation.
• Ensure wall surface is flat and clean.
Installation
1. Remove security screw (if any) on bottom of Room Controller
cover.
2. Open unit by pulling on bottom side of Room Controller (Figure 1).
3. Read FCC ID and IC label installed in cover before installing any
wireless product.
4. Ensure correct side of base faces up.
5. Pull cables 6in ( 15cm ) out from wall.
6. Align base and mark location of two mounting holes on wall (Figure 2).
7. Install anchors in wall.
8. Insert cable in central hole of base.
9. Insert screws in mounting holes on each side of base.
10. Strip each wire 1/4in ( 0.6cm) from end.
11. Insert each wire and screw according to wiring chart (next page).
12. Gently push excess wiring back into hole.
13. Gently align cover to top of base and snap in place from bottom
(Figure 3).
14. Install security screw.