Vortex 727 Use and care manual

WARNING: COMPRESSED AIR COULD CAUSE DEATH, BLINDNESS
OR INJURY
1. Do not operate the Cold Air Gun at air pressures above 150 psig (10.3 Bar).
2. Do not operate the Cold Air Gun at line temperatures above 110°F (43°C).
3. Avoid direct contact with compressed air.
4. Do not direct compressed air at any person.
5. When using compressed air, wear safety glasses with side shields.
Introduction
A Vortex Cooler is designed to use filtered compressed air to cool industrial cabinets without the use
of any refrigerants. An internal Vortex tube lowers the temperature and pressure of the compressed air
supplied to the enclosure. Hot air in the cabinet is vented to the surroundings through a built in relief valve
in the Vortex Cooler.
Vortex Coolers can be used with or without electric thermostats and solenoid valves.
Compressed Air Supply
The compressed air supply must be filtered to remove water and dirt using a 5 micron or smaller filter.
Failure to use a filter may cause clogging (and freezing) of the compressed air paths inside the Vortec
product. Filter recommendations are given in Table 1.
Filter elements must be changed on a regular basis. Frequency of change is determined by the condition
of the compressed air supply. Filters should be installed in the compressed air supply line as close as
possible to the Vortec product.
The appropriate size of compressed air supply line should be selected to ensure optimal performance of
the Vortec product. Please refer to Table 2 to determine what supply line size is recommended for your
application. Contact Vortec at 1-800-441-7475 for further assistance.
Installation and Operation
Type 4 or 4X Vortex Coolers must be installed in a vertical orientation on a flat horizontal surface at the
top of the cabinet.
Type 12 Vortex Coolers should be installed in a vertical orientation on a flat horizontal surface at the top
of the cabinet, or in a horizontal orientation on a flat vertical surface on the side of the cabinet.
Vents in the cabinets must be covered and sealed to ensure cooling efficiency and to keep out ambient air.
When a thermostat is supplied with a Vortex Cooler system for Type 4/4X/12 enclosures, the thermostat
can be easily readjusted using the temperature indicator dial. All wiring must be installed in an approved
conduit.
GENERAL SAFETY CONSIDERATIONS

Installation Procedures:
1. For Type 4 or 4X units: Cut 1-15/16” (49 mm) (1-1/2” knockout size) hole(s) in the enclosure.
For Type 12 units: Cut 1-1/8” (29 mm) (3/4" knockout size) hole(s) in the enclosure.
2. Insert Vortex Cooler(s) into cut-out(s) and secure with the locknut(s).
3. For Type 4 or 4X units: Attach the cold air muffler(s) to the outlet of the V ortex Cooler(s).
4. Perforate the ducting kit(s) with several 1/8” holes and secure to the interior of enclosure.
5. For dual cooler units: Attach the ducting kits to the cold outlets of the Vortex Coolers.
For all other models: Attach the ducting kit(s) to the cold air muffler(s).
6. If installing a solenoid valve and thermostat, connect pipe from Vortex Cooler to solenoid valve,
then pipe from solenoid valve to compressed air filter. The thermostat should be placed inside the
enclosure cabinet, and connected to the solenoid valve with conduit.
If not installing a solenoid valve and thermostat, connect piping from Vortex Cooler directly to
compressed air filter. The compressed air filter and solenoid valve should be installed as close as
possible to the Vortex Cooler, in a location where the temperature does not exceed 125 F (52 C).
Conduit and compressed air pipe are not provided.
7. Connect the compressed air supply to the filter.
Maintenance
Vortec Cooler systems have no moving parts and can be disassembled for cleaning.
Troubleshooting
Insufficient airflow may be caused by the following:
1. Undersized compressed air line size.
2. Compressed air pressure too low.
3. Partial or complete blockage of internal compressed air path, due to dirt.
Insufficient cold air temperature may be caused by:
1. Compressed air line temperature too high.
2. Water vapor in the compressed air supply.
3. Loose cold cap. This may occur if not tightened properly after disassembled for cleaning.
If trouble persists, please contact Vortec at 1-800-441-7475.
Limited Warranty
Vortec compressed air products manufactured by ITW Air Management will be replaced or repaired if
found to be defective due to manufacture defect within ten years from the date of invoice.
Refer to our website www.vortec.com for full warranty details and limitations. ITW Air Management
makes no specific warranty merchantability or warrant of fitness to a particular purpose.

Vortex Cooler Assembly – Type 4/4X, Single Cooler
(Drawings shown below are not to scale)
Models 727, 727-15H, 727-35H, 737, 747, 787, 797, 787-35H, 797-35H, 727SS,
727SS-15H, 727SS-35H, 737SS, 747SS, 787SS, 797SS, 787SS-35H, 797SS-35H
Solenoid valve
NEMA 4/4X
120VAC/60 Hz
110VAC/50Hz
Air Filter
Thermostat
Plug end of tubing if holes are
punched in length of tubing
(as shown)
Ducting Kit
Cold Air
Cold Air
Muffler
1-15/16" Hole
1/4" NPT (F)

Vortex Cooler Assembly - Type 4/4X, Dual Cooler
(Drawings shown below are not to scale)
Models 7875, 7975, 7875SS, 7975SS
Solenoid valve NEMA 4/4X
120VAC/60 Hz 110VAC/50Hz
1/2" pipe nipple (2 supplied)
3/4 x 1/2"
pipe reducer
(supplied)
1/2" tee
1/2 x 1/4" pipe reducer (2 supplied)
Air Filter
Thermostat
Ducting Kit
Cold Air
Cold Air
Cold Air
Muffler
1-15/16"
Hole
1-15/16"
Hole
1/4" piping or 3/8" inside diameter hose
(keep as short as possible - user supplied)
1/4" NPT (F)

Vortex Cooler Assembly - Type 12, Single Cooler
(Drawings shown below are not to scale)
Models 711, 750, 760
Solenoid valve
NEMA 12
120VAC/60 Hz
110VAC/50Hz
Air Filter
Thermostat
Plug end of tubing if holes are
punched in length of tubing
(as shown)
Cold Air
1-1/8" Hole
1/4" NPT (F)
Ducting Kit

Vortex Cooler Assembly - Type 12, Single Cooler
(Drawings shown below are not to scale)
Models 721, 730, 740, 780, 785, 790, 795
1/4" NPT (F)
Solenoid valve
NEMA 12
120VAC/60 Hz
110VAC/50Hz
Air Filter
Thermostat
Plug end of tubing if holes are
punched in length of tubing
(as shown)
Ducting Kit
Cold Air
1-1/8" Hole

Vortex Cooler Assembly - Type 12, Dual Cooler
(Drawings shown below are not to scale)
Models 7870, 7970
Solenoid valve
NEMA 12
120VAC/60 Hz
110VAC/50Hz
1/2" pipe nipple
(2 supplied)
3/4 x 1/2"
pipe reducer
(supplied)
1/2" tee
1/2 x 1/4" pipe reducer
(2 supplied)
Air Filter
Thermostat
Ducting Kit
Cold Air
Cold Air
1-1/8" Hole 1-1/8" Hole
1/4" piping or 3/8" inside diameter hose
(keep as short as possible - user supplied)
1/4" NPT (F)

Table 1: Filter Recommendations
FILTER AND REPLACEMENT PART ITEM NUMBERS
Vortec Model Oil Removal
Filter
Valve and Thermostat Kit
(120 VAC)
Valve and Thermostat Kit
(240 VAC)
Replacement
Generator Kits (5 pcs)
727-15H, 737 701S-48 721T-70 721T-80 208GK-15H
727, 787 701S-48 721T-70 721T-80 208GK-25H
727-35H, 787-35H 701S-54 721T-100 721T-100 208GK-35H
747 701S-48 - 721T-80 208GK-15H
797 701S-48 - 721T-80 208GK-25H
797-35H 701S-54 - 721T-110 208GK-35H
727SS-15H, 737SS 701S-48 721T-70 721T-80 208GK-15H
727SS, 787SS 701S-48 721T-70 721T-80 208GK-25H
727SS-35H, 787SS-35H 701S-54 721T-100 721T-110 208GK-35H
747SS 701S-48 - 721T-80 208GK-15H
797SS 701S-48 - 721T-80 208GK-25H
797SS-35H 701S-54 - 721T-110 208GK-35H
7875, 7875SS 701S-54 721T-120 721T-130 208GK-35H
7975, 7975SS 701S-54 - 721T-130 208GK-35H
750, 711 701S-48 - 721T-80 106GK-8H
760, 711 701S-48 721T-70 721T-80 106GK-8H
740, 721-15H 701S-48 - 721T-80 208GK-15H
730, 721-15H 701S-48 721T-70 721T-80 208GK-15H
780, 721 701S-48 721T-70 721T-80 208GK-25H
790, 721 701S-48 - 721T-80 208GK-25H
785, 721-35H 701S-54 721T-100 721T-110 208GK-35H
795, 721-35H 701S-54 - 721T-110 208GK-35H
7870 701S-54 721T-120 721T-130 208GK-35H
7970 701S-54 - 721T-130 208GK-35H

LIT0164
Table 2: Determining Compressed Air Line Size
1. Calculate total product compressed air consumption (SCFM, SLPM).
2. Determine length of compressed air line required for connection to main supply.
3. Locate pipe length in left column and read to the right to find the compressed air requirements.
4. Locate pipe size at top of column.
MAXIMUM AIRFLOW (SCFM) THROUGH PIPE AT 5 PSIG PRESSURE DROP (100 PSIG AND 70OF)
Pipe
Length
(Feet)
Pipe Size (Nominal) - Schedule 40
1/4 3/8 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2
10 29 65 120 254 480 978 1483 2863 4536
20 21 46 85 180 340 692 1049 2024 3208
30 17 37 70 147 277 565 856 1653 2619
40 15 32 60 127 240 489 792 1431 2268
50 13 29 54 114 215 437 663 1280 2029
60 12 26 49 104 196 399 606 1169 1852
70 11 25 46 96 181 370 561 1082 1715
80 10 23 43 90 170 346 524 1012 1604
90 10 22 40 85 160 326 494 954 1512
100 9 21 38 80 152 309 469 905 1435
MAXIMUM AIRFLOW (SLPM) THROUGH PIPE AT 0.3 BAR PRESSURE DROP (6.9 BAR AND 21OC)
Pipe
Length
(Meters)
Pipe Size (Nominal) - Schedule 40
1/4 3/8 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2
3 821 1840 3396 7188 13584 27677 42117 81023 128369
6 594 1302 2406 5094 9622 19584 29687 57279 90786
9 481 1047 1981 4160 7839 15990 24225 46780 74188
12 425 906 1698 3594 6792 13839 20999 40497 64184
15 368 821 1528 3226 6085 12367 18763 36224 57421
18 340 736 1387 2943 5547 11292 17150 33083 52412
21 311 708 1302 2717 5122 10471 15877 30621 48535
24 283 651 1217 2547 4811 9792 14829 28640 45393
27 269 623 1132 2406 4528 9226 13980 26998 42790
31 255 594 1075 2264 4302 8745 13273 25612 40611
Rubber hose maximum airflow rating: 1/2” I.D. rubber hose = 3/8” pipe; 3/4” I.D. rubber hose = 1/2” pipe
This manual suits for next models
17
Table of contents