5.2 Startup:
When the power is switched on, the screen will be fully light for 3 seconds, the device code will be displayed,
and then it will enter the normal working state. When the screen is locked, only the button will
light up; Press and hold for more than 3 seconds, other buttons will all light up. The screen will
automatically lock up when there is no operation for more than 1 minute and the brightness of the screen
is reduced by 1/3 of the normal display. Short press to wake up the screen and observe the relevant
operating parameters.
5.3 Self-priming
When switched on for the first time after installation, the pump will start self-priming automatically and
followed by self-learning.
l Self-priming:
When the system performs self-priming, it will count down from 1500s and stop automatically when the
system detects the pump is full of water, then the system will recheck for 30s again to make sure the self-
priming is completed.
User can exit self-priming manually by pressing for more than 3 seconds. The pump will start self-
learning process for 180s and then enter the default Manual-Inverter mode if the user exits the first self-
priming manually. If the user exits the self-priming after the following start up, the pump will run as per
the mode and setting before the last shut-down.
l Self-learning:
After the first self-priming is completed, the system will perform the first time self-learning for 180s, and
redefine the adjustable flow range of the pump by detecting the pipeline pressure.
eg: the default adjustable flow range of InverPro IP25 is 5-25 m³/h, after self-learning, the range may be
redefined to 7-22 m³/h. User can still set 25 m³/h in this situation, the pump will adjust the running capacity
automatically to reach the current reachable max. flow rate (22 m³/h), and the flow display on the controller
will turn back to 22 m³/h after 3 seconds.
The default adjustable flow range for InverPro is as below:
Default adjustable flow rate range