manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Worcester Bosch
  6. •
  7. Boiler
  8. •
  9. Worcester Bosch Highflow 3.5 RSF User guide

Worcester Bosch Highflow 3.5 RSF User guide

Other Worcester Bosch Boiler manuals

Worcester Bosch Danesmoor Utility 12/14 User guide

Worcester Bosch

Worcester Bosch Danesmoor Utility 12/14 User guide

Worcester Bosch GREENSTAR 25SI Instruction manual

Worcester Bosch

Worcester Bosch GREENSTAR 25SI Instruction manual

Popular Boiler manuals by other brands

IDEAL IMAX XTRA EL 320 user guide

IDEAL

IDEAL IMAX XTRA EL 320 user guide

UTICA BOILERS BC3D Installation, operation & maintenance manual

UTICA BOILERS

UTICA BOILERS BC3D Installation, operation & maintenance manual

Lochinvar SOLUTION 260000 Installation & service manual

Lochinvar

Lochinvar SOLUTION 260000 Installation & service manual

Weil-McLain EG 6 Series manual

Weil-McLain

Weil-McLain EG 6 Series manual

RBI LCD Series Installation & operation manual

RBI

RBI LCD Series Installation & operation manual

Baxi MainEco Combi 28 Installation and service manual

Baxi

Baxi MainEco Combi 28 Installation and service manual

Unical ALKON R 24 Installation and Servicing Manual

Unical

Unical ALKON R 24 Installation and Servicing Manual

Automatic Heating Gasogen Installation and Servicing Manual

Automatic Heating

Automatic Heating Gasogen Installation and Servicing Manual

Viessmann VITORADIAL 300-T Type VR3 Service instructions for contractors

Viessmann

Viessmann VITORADIAL 300-T Type VR3 Service instructions for contractors

Alpha GasSaver GS-1 Installation and servicing instructions

Alpha

Alpha GasSaver GS-1 Installation and servicing instructions

Baxi ROCA LAURA PLUS 28/28 Operating, cleaning and maintenance instructions for the user

Baxi

Baxi ROCA LAURA PLUS 28/28 Operating, cleaning and maintenance instructions for the user

Vaillant uniSTOR VIH SW GB 500 BES operating instructions

Vaillant

Vaillant uniSTOR VIH SW GB 500 BES operating instructions

Kärcher HWE 4000 Gas manual

Kärcher

Kärcher HWE 4000 Gas manual

Radijator BIO max 23.1 instruction manual

Radijator

Radijator BIO max 23.1 instruction manual

Granby BKC Installation, operation and maintenance manual

Granby

Granby BKC Installation, operation and maintenance manual

Brunner BSV 20 Instructions for use

Brunner

Brunner BSV 20 Instructions for use

Potterton 50e Installation and Servicing Manual

Potterton

Potterton 50e Installation and Servicing Manual

UTICA BOILERS TriFire Assembly instructions

UTICA BOILERS

UTICA BOILERS TriFire Assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

....--
~
~
~ORCESTER--.
Highflow
3.5
RSF
ROOM
SEALED
FANNED
FLUE
MODEL
FLOOR STANDING COMBINATION BOILER FOR CENTRAL
HEATING
AND
MAINS
FED
DOMESTIC
HOT
WATER
INSTALLATION AND
SERVICING
INSTRUCTIONS
GC
NUMBER
41
311
40
BOILER OUTPUT
To
Hot Water
Maximum
23.4
kw
(80,000
Btu/h)
To
Central Heating
Minimum
8.8
kW (30,000
Btu/h)
Maximum
23.4
kW (80,000
Btu/h)
IMPORTANT:
THIS
APPLIANCE
IS
FOR
USE
WITH
NATURAL
GAS
ONLY
THESE
INSTRUCTIONS
APPLY
IN
THE
UK
ONLY
THESE
INSTRUCTIONS
ARE
TO
BE
LEFT
WITH
THE
USER
OR
AT
THE
GAS
METER
...__
_____
:::.
~
.rwoRCESTER
_____
...
Bosch
Group
CONTENTS
INSTALLATION
REGULATIONS
AND
TECHNICAL
DATA
Section
1
Section
2
Section
3
Section
4
Section
5
Section
6
Section
7
Section
8
Section
9
Section
9.1
Section
9.2
Section
9.3
Section
10
Section
11
Section
12
Section
13
Section
14
Section
15
Section
16
Section
17
Section
18
Section
19
Section
20
General
Information
Siting
the
Appliance
Removal
of
Cabinet
System
Considerations
Air
Supply
-
Horizontal
Flues
Terminal
Position
-
Horizontal
Flue
Air
Supply
-
Vertical
Flue
Connection
of
Primary
and
Secondary
Vertical
Flues
Installing
the
Appliance
-
General
Rear
Horizontal
Flue
Outlet
Vertical
Flue
Systems
Pre-plumbing
of
the
Appliance
Completion
of
the
Installation
Sealed
Primary
System
-
Open
Vent
Secondary
System
Open
Vent
Primary
System
~
Mains
Feed
Secondary
System
Mains
Feed
Domestic
Hot
Water
Supply
(Secondary)
Electrical
Commissioning
the
Appliance
System
Guidance
and
Bypass
Adjustment
Users
Instructions
Routine
Cleaning
and
Inspection
Replacement
of
Parts
Short
Parts
List
Fault
Finding
Chart
INSTALLATION REGULATIONS
The
installation
of
this
appliance
must
be
in
accordance
with
the relevant
requirements
of
the
Gas Safety
(Installation
and
Use)
Regulations,
local
Building
Regulations,
Building
Standards
(Scotland)
(Consolidation),
current
lEE
wiring
regulations
and
bye
laws
of
the
local
water
undertaking.
It
should
be in
accordance
with
the relevant
recommendations
of
the
following
British
Standards
and
Codes
of
Practice: BS 6798:1987, BS 5449:1:1990,
BS
5546:1:1990,
BS
5440:1:1990,
BS 5440:2:1989 and BS 6891.
Gas Safety
(Installation
and Use)
Regulations
1984:
It
is
the
law
that
all
gas
appliances
are
installed
by
a
competent
person,
in
accordance
with
the
above
regulations. Failure
to
install
appliances
correctly
could
lead
to
prosecution.
It
is
in
your
interest, and
that
of
safety
to
ensure
compliance
with
the
law.
The
manufacturers
notes
must
not
be taken,
in
any
way, as
overriding
statutory
obligations.
TECHNICAL
DATA
NOTE: THE
DATA
PLATE
IS
POSITIONED INSIDE THE APPLIANCE
AT
THE FRONT LEFT
HAND
SIDE.
Table
1
NOMINAL
BOILER RATINGS (10
minutes
after
lighting)
BURNER SETTING
MODE
OUTPUT
INPUT PRESSURE GAS RATE
kW
(Btu/h)
kW
(Btu/h) m bar (in.
wg)
m3
/h
ift'ih
I
8.79 (30000) 12.0 (40955) 2.2 (0.88) 1.11 (39.4)
11.0 (37545) 14.7 (50170) 3.2 (1.28) 1.36 (48.3)
HEATING 13.0 1443701 17.1 (58360) 4.4 (1.76) 1.59 (56.2)
RANGE 15.0 151195) 19.6 (66555) 5.8 (2.32) 1.81 (64.0)
17.0 (58020) 21.9 (74745) 7.3 (2.92) 2.03 (71.9)
19.0 (64845) 24.2 (82595)
9.1
(3.64) 2.25 (79.5)
23.44 (80000) 29.3
(1
00000) 14.3 (5.72) 2.72 (96.2)
DOMESTIC 23.44 (80000) 29.3
(1
00000) 14.3 (5.72) 2.72 (96.2)
HOT WATER
Note:
The
pressure
test
point
is
located
on
the
gas
valve
(See
fig.
31a).
2
Table 2
SPECIFICA
nONS
HEATING FLOW
28mm
COPPER
TUBE
HEATING RETURN
28mm
COPPER
TUBE
SAFETY VALVE
22mm
COPPER
TUBE
COLD
FEED
22mm
COPPER
TUBE
COLD WATER
MAINS
IN
15mm
COMPRESSION -SUPPLIED
DOMESTIC WATER OUT
22mm
COPPER
TUBE
GAS INLET
22mm
COPPER
TUBE
HEIGHT
860mm
(33.9in)
WIDTH
550mm
(21.6inl
DEPTH
600mm
(23.6in)
WEIGHT 95kg (2101b)
empty-
147kg (3241b) full
PRIMARY CAPACITY 48 litres (10.6 gal)
*MAXIMUM
STATIC HEAD
25m
(81ft.)
*MINIMUM
STATIC HEAD 1000mm (39in)
CIRCULATING PUMP
Grundfos
15-60
EXPANSION VESSEL 12
litres
charged
0.5
bar
OUTPUT
TO
HEATING
MAXIMUM
23.4kW (80,000 Btu/h)
OUTPUT
TO
DOMESTIC HOT WATER 23.4kW (80,000 Btu/h)
CH
CONTROL
THERMOSTAT-
MAX.
TEMPERATURE
Nominally
82°C
(180°F)
DOMESTIC HOT WATER FLOW
RATE
(35°C
RISE)
Nominally
9.6
litres/min
+
15%
(2.1
gal/min)
MAXIMUM
DOMESTIC HOT WATER FLOW RATE
Nominally
15
litres/min
(3.3
gal/min)
±15%
*
Appliance
static
heads
are
measured
from
the top
of
the
casing
to
the
highest
point
of
the
system
(See
Fig_s.
24.
and
25)
Table 3
HORIZONTAL VERTICAL
FLUE
DETAILS-
See Notes
Below
REAR FLUE PRIMARY FLUE
WALL OR
CEILING-
HOLE DIAMETER FOR AIR DUCT 125mm (Sin) 125mm (Sin)
WALL HOLE DIAMETER FOR SEALING RING 150mm (6in)
MINIMUM FLUE
LENGTH-
STANDARD FLUE KIT 100mm (4in) 1557mm (61.3in)
MAXIMUM FLUE
LENGTH-
STANDARD FLUE KIT 1
OOOmm
(39in) 2000mm (73in)
FLUE LENGTHS WITH EXTENSION KIT 1
001
to 2000mm
2001
to
3000mm
(39
to
73in) (79
to
118in)
If
a
flue
extension
is
required
(See
Section
9)
it
may
be
obtained
from
Worcester
Heat
Systems
Ltd. ONE
EXTENSION
FLUE
KIT ONLY
MAY
BE
USED
PER
APPLIANCE. Part No. ZAGAS066
Table 4
AVAILABLE PUMP HEADS
HEATING OUTPUT HEAD MIN. FLOW RATE OPTIMUM
kW Btu/h METRES
FEET
LITRES/MIN.
GALUMIN.
TEMPERATURE
RISE
8.8 (30,000)
5.1
16.6
8.41
1.89
11
(37,500) 4.7 15.5
10.51
2.36
13
(44,350) 4.3
14.1
12.42 2.79
15°C
between
15
(51,200) 3.8 12.6 14.33 3.22
heating
flow
and
return
17
(58,000) 3.3 10.9 16.24 3.65
19
(64,800) 2.2 7.2 18.15 4.08
23.4 (80,000) 1.5 5.0 22.35 5.02
3
1.
GENERAL
INFORMATION
IMPORTANT:
Although
the
appliance
includes
the
facility
to
instal
a
sealed
primary
water
system
and
feed
the
sec-
ondary
system
via
the
mains
supply,
only
one
of
these
can be
used,
i.e.
the
system
arrangement
must
be
one
of
the
following:
(i) Sealed
primary
and
open
vented
(i.e.
cistern
feed)
secondary
(Section
10)
or
(ii)
Open
vented
primary
and
mains
feed
secondary
(Section
11)
or
(iii)
Open
vented
primary
and
open
vented
(i.e.
cistern
feed)
secondary.
FOR FURTHER ADVICE
CONTACT
WORCESTER
HEAT
SYSTEMS
LTD.
1.
HIGHFLOW
3.5 RSF INCORPORATES
(a)
An
induced
draught
fan, a
low
thermal
capacity
heat
exchanger
having
a
maximum
heat
output
of
23.4kW (80000 Btu/h).
(b)
Either
a
horizontal
(rear
outlet)
or
vertical
fanned
flue
system
-to
order.
(c) A
standard
duct
kit
for
horizontal
flue
lengths
from
100mm
{4in)
to
1000mm
{39in).
(An
extension
duct
kit
from
1001
mm
(39in)
to
2000mm
{79in)
maximum
length
is
available
as an
option).
A
standard
duct
kit
for
vertical
flues,
complete
with
diverter
intended
for
installation
within
a
roof
space.
The
kit
will
enable
the
diverter
to
be
installed
be~
tween
1557 (61.3in)
and
2000mm
(79in)
above
the
appliance
top
outlet.
(An
extension
duct
kit
from
2001mm
(59in)
to
3000mm
{118in) is
available
as an
option).
(d) A
heatbank
having
a
nominal
capacity
of
45
litres
(10
gallons)
of
circulating
primary
hot
water
posi-
tioned
inside
the
appliance.
A
copper
finned
water
to
water
heat-exchanger
is
fitted
into
the
heatbank.
Secondary
supply
domestic
hot
water
passes
through
the
heat
exchanger.
{e) A
diverter
valve
to
direct
the
boiler
output
either
to
domestic
hot
water
or
central
heating
as
required.
(f) A
circulating
pump.
(g) A
multifunctional
HIGH/LOW
gas
valve
and
elec-
tronic
control
system
to
control
individually
the
domestic
hot
water
and
central
heating.
The
system
provides
automatic
ignition.
(h)
Boiler
and
hot
water
temperature
control
thermo-
stats
providing
control
for
central
heating
and
dom-
estic
hot
water.
(j)
A User/s
Operating
Switch
for
selection
of
water
only
or
heating
and
water.
A
programmer
kit is
available
as an
optional
extra.
(k)
An
expansion
vessel,
pressure
gauge,
pressure
relief
valve
and
auto
air
vent
to
enable
the
primary
circuit
to
be
connected
to
a sealed
water
system.
{I)
An
electronic
pump
delay
control
board
which
en-
ables
the
pump
to
run
on
for
a
period
of
about
5
min-
utes
after
each
operating
cycle.
2.
INSTALLATION
WARNING:
GREAT CARE
MUST
BE
TAKEN
TO
ENSURE
THAT
NO
FOREIGN
MATTER
IS
LEFT IN THE
WATER
SYSTEM. THIS
COULD
CAUSE
DAMAGE
TO
THE
APPLIANCE.
3.
NATURAL
GAS
SUPPLY
The boiler requires 2.72m'/h (96.2ft'/h) of gas. Meter and
supply pipes
must
be capable of delivering this quantity of
gas
in
addition to the
demand
from any other appliances
in tho house.
The
meter
outlet governor
must
ensure a
nominal pressure of 20
mbar
(Bin wg) at the appliance,
equivalent to a pressure of about 18:5-19
mbar
at the gas
valve.
The
complete
installation,
mcluding
the
meter,
should be inspected and tested for soundness and purged
in
accordance with the recommendations of BS 6891.
4
4. ELECTRICAL SUPPLY
Mains
supply
240
V,
........
50 Hz, 160
watts
fused
at 3A.
See
Section
13.
The
length
of
supply
cable
provided
with
the
appliance
is
rated
at a
temperature
of
aooc
continuous.
5. OPEN
VENTED
SYSTEM
The
appliance
is
supplied
ready
for
connection
to
a
sealed
water
system.
An
open
vented
system
can
be
used
by
carefully
removing
the
safety
valve
and
seal-
ing
its
connection.
See
Section
11. Care
should
be
taken
not
to
distort
the
pipe.
6.
CONTROLS
All
controls
included
with
the
appliance
are
specified
in
the
'Short
List
of
Parts'
included
in
this
leaflet.
There
is
provision
for
a
room
thermostat
and
frost
thermostat
to
be
fitted
to
the
appliance.
See
Section
13.
Thermostatic
radiator
valves
can be
used
in
the
system;
however,
a
suitable
by-pass
is
essential
with
this
type
of
control.
See
Section
15.
7.
DRAINAGE
A
drain
cock
is
fitted
in
the
pipe
connecting
thE!
primary
heat
bank
to
the
sealed
system
expansion
vessel
to
drain
water
from
the
boiler
and
the
heat
bank. (Fig. 46)
8.
PACKAGING
The
appliance
is
despatched
in
one
package. A sep-
arate
package
contains
either
the
standard
horizontal
or
vertical
flue
kit. Each kit
includes
either
a
balanced
flue
terminal
(horizontal
flue)
or
diverter
(vertical
flue)
together
with
the
necessary
duct
work,
sealin~1
materials,
etc.
2.
SITING
THE
APPLIANCE
(Refer also to sections
5,
6,
7 and 8).
1. The appliance is floor standing and the floor
must
be firm
and level.
2.
The
following
clearances
must
be
left
to
allow
for
servicing and ventilation:
(a) Above the appliance: Servicing 450
mm
(18 in.)
Ventilation 5 mm (0.2 in.)
(b) In front of the appliance: Servicing 600
mm
(24 in.)
Ventilation 75
mm
(3 in.)
(c) Left and right-hand side: Servicing 20
mm
(0.8 in.)
Ventilation 20 mm (0.8 in.)
NOTE:
Care
must
be
taken
to
ensure
adequate
space
is
available
at
either
side
for
installing
the
boiler.
See Sec-
tion
9.
3.
The
chosen
position
must
allow
the
provision
of
a
satisfactory
balanced
flue
termination.
See
Section
6,
if
a
horizontal
flue
system
is
to
be
used
OR
4.
The
chosen
position
must
allow
the
provision
of
a
satisfactory
secondary
flue
terminal
discharge
in
a
down
draught
free
zone. See
Section
8,
if
a
vertical
flue
system
is
to
be used.
NOTE:
If
the
appliance
is
to
be
fitted
in
a
timber
framed
building
it
should
be
fitted
in
accordance
with
the
British
Gas
publication
"Guide
for
Gas
Installation
in
Timber
Framed
Housing"
Ref
DM2.
If
in
doubt
advice
must
b~3
sought
from
the
local
Region
of
British
Gas.
3.
REMOVAL
OF
FACIA
PANEL
AND
CABINET
See Fig.
1.
NOTE:
It is
necessary
to
remove
the
cabinet
top
cover,
front
cover,
and
may
be
necessary
to
remove
the
facia
panel,
left
and
right
hand
side
panels
and
lower
grille
to
aid
installation.
Fig. 1
Cabinet
-
Control
Panel
and
Facia Fixing
Screws
A
A TOP
COVER
RETAINING LUGS
B TOP
COVER
FIXING BOLT
c FACIA FIXING SCREWS
D DHW AND
CH
THERMOSTAT
MOUNTING
BRACKET FIXING SCREWS
E CONTROL PANEL FIXING SCREWS
F CONTROL PANEL SUPPORT BRACKET
AND SCREW
G
LEFT
HAND SIDE PANEL FIXING SCREWS
H SIDE PANEL BRACKET FIXING SCREWS
J RIGHT HAND SIDE PANEL FIXING SCREWS
K LOWER FRONT GRILL
KICKSTRIP FIXING SCREWS
L FRONT COVER {NO FASTENINGS)
""
(a)
Remove
the
cabinet
front
cover
by
pulling
firmly
at
the
base
and
lifting
upwards
and
outwards.
Remove
the
cabinet
top
cover
by
slackening
com-
pletely
the
bolt
'B'
retaining
the
front
of
the
top
cover.
See
Fig.
1.
(b)
Pull
up
the
front
edge
of
the
cover
sharply
to
disengage
the
fasteners.
Draw
the
cover
forward
enough
to
disengage
it
at
the
rear
and
lift
clear.
(c)
Undo
the
five
screws
'K'
holding
the
lower
front
grille
kick
strip.
(d) Pull
off
the
two
thermostat
knobs
and
remove
the
five
screws
'C';
two
securing
the
ends
of
the
facia
to
the
side
panels
and
three
underneath
the
facia,
fixing
it
to
the
base
of
the
control
panel.
Pull
the
facia
forward
until
it
clears
the
side
panels.
The
facia
will
come
away
complete
with
three
position
switch
or
programmer,
if
fitted.
Support
the
facia
having
drawn
it
forward
enough
to
gain
access
to
the
plug
in
terminal
rail
positioned
behind
and
to
the
right
of
the
heating
thermostat.
The
terminal
rail
is
numbered
14
to
17
inclusive.
Separate
the
two
halves
of
the
terminal
rail,
enabling
the
facia
to
be
removed
completely.
(Fig. 37)
(e)
Remove
the
two
remaining
posidrive
screws
'C'
retaining
the
top
of
the
left
hand
side
panel
and
the
two
M5
slotted
head
screws
and
single
posidrive
screw
retaining
the
top
of
the
right
hand
side
panel
'J'.
Draw
the
side
panels
forward
and
lift
out.
NOTE:
The
control
panel
is
supported
in
position
by
a
single
posidrive
screw
'F'. (See Fig. 1).
This
is
intended
to
hold
the
panel
during
installation
only
and
no
undue
strain
should
be
placed
on
the
panel.
4.
SYSTEM
CONSIDERATIONS
(a)
The
appliance
includes
a
pump
and
no
other
circulating
pump
is
required.
When
fitting
a
room
or
frost
thermostat,
refer
to
Section
13,
Electrical.
The
appliance
will
operate
satisfactorily
on
a
two
pipe
small
bore
or
micro-bore
system.
5
J,C
c L
K
(b)
The
heatbank
contains
a
finned
copper
heat
exchanger
which
provides
domestic
hot
water.
A
control
system
is
incorporated
that
gives
priority
to
the
domestic
hot
water
and
the
central
heating
will
be
turned
off
when
a
demand
for
hot
water
is
made.
For
large
quantities
of
hot
water
the
control
thermostat
should
be
set
at
maximum
and
after
use, a
few
minutes
may
be
required
to
re-heat
the
heatbank.
The
central
heating
will
remain
off
during
this
period.
IT
IS ESSENTIAL TO FIT A BYPASS TO ALL
SYSTEMS.
5.
AIR
SUPPLY
HORIZONTAL
FLUE
1.
The
room
in
which
the
appliance
is
installed
does
not
require
a
purpose
air
vent.
2.
If
the
appliance
is
installed
in
a
cupboard
or
compartment,
permanent
air
vents
are
required
in
the
cupboard
or
compartment,
one
at
high
level,
and
one
at
low
level,
either
direct
to
outside
air
or
to
a
room.
Both
high
and
low
level
air
vents
must
communicate
with
the
same
room
or
must
both
be
on
the
same
wall
to
outside
air.
The
minimum
effective
areas
required
are
given
in
Table
5.
Table
5 COOLING AIR REQUIREMENTS
HORIZONTAL
AND
VERTICAL FLUE SYSTEMS
Position
of
Air
from
Air direct
Air
Vents
room
from
outside
High
Level
264cm
2
132cm
2
{41
in
7)
{20.5in
2)
Low
Level
264cm
7
132cm
2
(41
in2)
(20.5in
7)
6.
FLUE
TERMINAL
POSITION-
HORIZONTAL
FLUE
IMPORTANT
1.
Flue length. See
note
in
Section
1,
General
Informa-
tion,
regarding
standard
flue
assembly
and
extension
flue.
2. The flue must be installed in accordance
with
the
recommendations
of
BS
5440:Part
1.
Minimum
siting
dimensions
for
positioning
the
balanced
flue
terminal:
TERMINAL
POSITION (See Fig.
2)
MIN
DISTANCE
A-
Directly
below
an
open
able
window
or
other
opening,
e.g.
air
brick
300mm
(12in)
B-
Below
gutters,
soil
pipes
or
drain
pipes
75mm
(3inl
c-
Below
eaves
200mm
(Sin)
D-
Below
balconies
or
car
port
roof
200mm
(Bin)
E-
From
vertical
drain
pipes
and
soil
pipes
75mm
(3in)
F -
From
internal
or
external
corners
300mm
(12in)
G -
Above
ground,
roof
or
balcony
level
300mm
(12in)
H-
From
a
surface
facing
a
terminal
600mm
(24in)
1-
From
a
terminal
facing
a
terminal
1200mm
(47inl
J -
From
an
opening
in
a
car
port
(e.g.
door,
window)
into
dwelling
1200mm
(47in)
K-
Vertically
from
a
terminal
on
the
same
wall
1500mm
(59in)
L -
Horizontally
from
a
terminal
on
the
same
wall
300mm
(12inl
GENERAL NOTES
1.
The
terminal
must
be
positioned
such
that
the
com-
bustion
products
can
disperse
freely
at all
times.
2. In
certain
weather
conditions
a
terminal
may
steam
and
positions
where
this
could
cause
a
nuisance
should
be
avoided.
3.
If
the
terminal
is
fitted
within
850mm
of
a
plastic
gutter
or
within
450mm
of
painted
eaves, an
alumi-
nium
shield
of
at
least
750mm
long
should
be
fitted
to
the
underside
of
the
gutter
or
painted
surface
(Dimensions
8
and
C in Fig. 2).
4.
If
a
terminal
is
fitted
less
than
2
metres
(78.6in)
above
a
surface
to
which
people
have
access
then
a
suitable
guard
must
be
provided.
A
terminal
protect-
ive
guard
is
available
from:
Tower
Flue
Components
Limited,
vale
Rise,
Tonbridge,
TN9
1TB.
Terminal
Guard
Reference:
GC
393
553-
Type
K2.
The
terminal
guard
must
be
securely
fixed
to
the
wall
using
the
three
brackets
provided,
suitable
plugs
and
corrosion
resistant
screws.
The
guard
must
be
sym-
metrically
positioned
about
the
terminal
assembly
and
spaced
such
that
there
is a
gap
of
50mm
min-
imum
between
the
end
of
the
terminal
and
the
guard.
5.
The
air
inlet/products
outlet
duct
and
the
terminal
of
the
boiler
must
not
be
closer
than
50mm
(2 in)
to
combustible
material.
Detail
recommendations
on
protection
of
combustible
material
are
given
in BS
5440:1
1990,
sub-section
3.3
IMPORTANT
It is
absolutely
ESSENTIAL
to
ensure,
in
practice,
products
of
combustion
discharging
from
the
terminal
cannot
re-enter
the
building
or
any
other
adjacent
building
through
ventilators,
windows,
doors,
other
sources
of
natural
air
infiltration
or
for-
ced
ventilation/air
conditioning.
If
this
eventuality
should
occur,
the
appliance
MUST
be
turned
off
immediately
and
the
problem
rectified.
6
7.
AIR
SUPPLY
VERTICAL
FLUES
1.
The
room
in
which
the
appliance
is
installed
does
not
require
a
purpose
air
vent.
2.
If
the
appliance
is
installed
in
a
cupboard
or
compartment,
permanent
air
vents
are
required
in
the
cupboard
or
compartment,
one
at
high
level,
and
one
at
low
level,
either
direct
to
outside
air
or
to
a
room.
Both
high
and
low
level
air
vents
must
com-
municate
with
the
same
room
or
must
both
be
on
the
same
wall
to
outside
air.
The
minimum
effective
areas
required
are
given
in
Table
5,
COOLING AIR
REQUIREMENTS,
Section
5.
3.
ALL
installations
must
be
provided
with
purpose
designed
air
vents
in
the
roof
space,
communicating
direct
with
outside
air.
THE
MINIMUM
EFFECTIVE AREA REQUIRED
FOR
AIR
VENTS WITHIN A ROOF SPACE
IS
516cm
2 (80in2).
4.
The
roof
space
containing
the
diverter
must
be
sealed
off
completely
from:-
(a)
the
room,
cupboard
or
compartment
in
which
the
appliance
is
installed
and
(b)
any
other
room.
8.
CONNECTION
OF
PRIMARY
AND
SECONDARY
VERTICAL
FLUES
The
components
up
to
and
including
the
draught
diverter
are
supplied
and
these
must
be
installed
vertically
above
the
top
boiler
flue
outlet,
in
accordance
with
the
dim-
ensions
shown
in Fig. 3.
Note
that
the
draught
diverter
must
be
positioned
such
that
it
will
not
be
obstructed
by
such
as
loft
insulation.
A
secondary
flue
must
be
fitted
to
the
top
of
the
draught
diverter.
This
component
will
accept
flue
pipe
to
BS
715
size
125mm
(5in).
If
flue
pipe
to
BS 4543 is
used,
then
an
adaptor
will
need
to
be
fitted,
but
the
nominal
internal
diameter
must
not
be
decreased.
The
installation
of
the
complete
flue
system
must
be
in
accordance
with
BS
5440:1.
The
secondary
flue
system
must
be
adequately
sup-
ported
and
the
exit
from
the
roof
space
water
proofed.
Horizontal
runs
and
bends
should
ideally
be
avoided,
but
at
least
minimised,
and
a
spillage
test
must
be
carried
out
in
accordance
with
BS 5440:1. Fig. 3
shows
an
ap-
propriate
point
at
which
to
apply
the
test.
No
part
of
the
flue
system
shall
be
within
25mm
(1.0in)
of
combustible
material.
Table
7
Max.
secondary
flue
length
Max
secondary
flue
length
if
set
to
minimum
CH
input
if
set
to
maximum
CH
input
6m
(20ft)
1Om
(33ft)
The
flue
lengths
recommended
above
are
intended
to
en-
sure
that
condensate
does
not
form
in
the
secondary
flue
system
when
the
appliance
operates
under
all
approved
operating
conditions.
NOTE:
The
permanent,
purpose
designed
ventilation
openings
required
within
the
roof
space,
the
openings
within
the
diverter
and
any
compartment
ventilation
-
if
applicable-
MUST
NOT
BECOME BLOCKED.
The
user
MUST
be
instructed
not
to
store
items
within
the
roof
space
which
may
cause
an
obstruction,
or
in
the
compartment
-
if
applicable.
A
space
of
at
least
250mm
(10in)
radius
shall
be
provided
around
the
draught
diverter
with
no
obstructions
(Fig. 3).
Fig. 2 Siting of terminal
Horizontal Flue
A'
/
j '
-'l
..
GJ
~
Dj
'
:.Ji
, , I I
l]
A
I
~
BC~
'
L'hl
IK
•
v .
IK
!
~
I I
F'
/
,,
llF
~HI'
J
, I ' '
I.
I \
~J
'j
F
r·E
Fig. 3 Position of Vertical Primary
Flue and Secondary Flue
See also Fig. 17
TERMINAL
(NOT
SUPPLIED)
.•
TWIN
WALL
SEC. FLUE
-------+
IS
RECOMMENDED
DRAUGHT
T
DIVERTER
WITH
125mm-------l-·f"=Y
(5in) SOCKET OUTLET
~
CLEAR SPACE
250mm
(10in I
RADIUS
AROUND
··1-.,+-~
DIVERTER WITH
NO
..
. M .
OBSTRUCTIONS
STANDARD
FLUE KIT
MINIMUM
HEIGHT H
1557mm
(61.3in)
MAXIMUM
HEIGHT H
2000mm
(79in)
WITH EXTENSION
KIT
MAXIMUM
HEIGHT
H
~
3000mm
(118in)
BOTTOM
OF FLUE OUTLET
SOCKET
H
45mm:
(1.8in)
1;
l_
G
GENERAL GUIDANCE · SITING OF
VERTICAL FLUE
TERMINAL
CHIMNEY
ON
RIDGE
NOT
ON
RIDGE
PITCH
Dim.
Y
1m
(3.3ft)
EXCEEDING 30°
AT
OR
ABOVE ROOF
ABOVE INTERSECTION
PITCH
NOT
RIDGE Dim Y
250mm
(lOin)
EXCEEDING 30° LEVEL ABOVE ROOF
INTERSECTION
NOTE: A spillage test must be carried out at the
diverter HERE,
in
accordance with BS5440:1.
ROOF SPACE VENTILATED
TO
OUTSIDE AIR SECTION 7.3
CEILING FLUE SEALING PLATE
860mm
(33.9in)
7
9.0
INSTALLING
THE
APPLIANCE
GENERAL
If
a
HORIZONTAL
FLUE is
to
be
installed
refer
to
Sections
2,
5,
6,
9.1
and
9.3:
also
Figs. 2
and
4.
If
a VERTICAL FLUE is
to
be
installed
refer
to
Sections
2,
7,
8,
9.2
and
9.3;
also
Fig.
3.
NOTE:
MORE
THAN
ONE PERSON
MAY
BE
REQUIRED
TO
INSTAL
THE APPLIANCE.
The
space
required
for
installation
is
50mm
(2in)
at
the
left
hand
side
and
150mm
(6in) at
the
right
hand
side.
A
description
given
in
Section
9.3
covers
one
method
of
installation.
If
connections
are
made
in
a
different
way
then
the
space
required
for
installation
may
be
greater.
In
some
circumstances
when
installing
the
appliance,
particularly
where
minimum
clearances
for
access
and
servicing
have
been
used,
it
may
be
found
necessary
to
pre-plumb
the
appliance
and
fit
unions
and
stub
pipes,
(Fig
5)
to
the
boiler
pipework
before
moving
it
into
posi-
tion.
If
so
refer
to
Section
9.3
and
make
the
connections
before
assembling
the
flue
system.
Check
to
determine
whether
or
not
an
extension
kit is
required.
Refer
to
Sec-
tion
1(c)
and
Section
2.
A
knock-out
panel
is
provided
in
the
cabinet
top
panel
to
facilitate
vertical
pipe
connections.
Compression
fittings
may
be
used
on
all
water
con-
nections
to
allow
for
the
fitting
of
the
boiler
and
servic-
ing.
1.
Unpack
the
appliance.
2.
Unpack
the
standard
flue
kit
and
flue
extension
kit
(if
required)
and
check
the
contents
against
the
en-
dosed
check list.
Ensure
all
cardboard
packing
in
the
standard
flue
assembly
and
flue
extension
is re-
moved.
3.
Remove
the
top
cover
and
the
front
panel
from
the
cabinet
as
described
in
Section
3.
4.
The
boiler
is
supplied
suitable
for
a
horizontal
rear
flue
outlet
configuration;
the
vertical
outlets
being
sealed
off
with
blanking
plates.
If
a
vertical
flue
is re-
quired
refer
to
Figs 6
and
7.
To
gain
access
to
the
top
flue
outlet
cover,
first
re-
move
the
access
cover.
Fig.
6.
Fig. 4 Wall
preparation
·
Rear
outlet
Dimensions
mm
(in)
-1{~~
5
)r
1----
600 {23.6)
~
.L~
1:1.
r-
-,
I
r~~-
I
' ' '
)
~----~
.,(---
--....J---....1
~
,.-t..""_
!.._-----
--
- -
~
~
(a)
Remove
the
top
air
duct
and
flue
duct
blanking
plates.
(b) Run a
bead
of
silicone
sealan1
around
the
inside
of
the
rear
flue
duct
and
air
duct
sockets.
(c) Fit
the
blanking
plate
into
the
rear
flue
outlet
socket,
push
fully
home
and
tighten
the
clamping
screw,
working
through
the
top
air
duct
socket
opening.
(d) Fit
the
rear
air
duct
socket
blanking
plate,
push
it
fully
into
the
socket
and
tighten
the
clamping
screw.
NOTE:
THE ACCESS
PANEL
MUST
BE
REPLACED
WHEN
THE FLUE
SYSTEM
IS
FITTED.
REFER
TO
SECTION 9.2a
{STANDARD
FLUE KIT)
OR
9.2b
{EXTENSION
KIT)
Subsection
3{a).
9.1.
REAR
HORIZONTAL
FLUE
1. Take
account
of
the
requirements
under
Section
2 -
Siting
the
appliance.
Refer
to
page
1
and
Fig
4.
Mark
the
flue
position
re-
quired
on
the
wall.
Cut
a
hole
in
the
wall
125mm
(5in)
diameter.
NOTE:
If
a
core
boring
tool
is
not
used
and
the
hole
is
made
oversize,
it
must
be
reduced
to
130mm
max-
imum
diameter
and
the
inner
skin
of
the
brickwork
made
good
before
the
appliance
is
installed
(Sec-
tions
9.1a; 9.1b; 9.1c).
2.
Determine
the
flue
length
by
referring
to
the
app-
ropriate
section
below,
which
details
the
correct
flue/
boiler
assembly
procedure.
Section
9.1a.
9.1b.
9.1
c.
Length
L
100mm-1000mm
(4in-39.4in)
1001
mm-1200mm
(39.4in-47.2in)
1201
mm-2000mm
(47.2in-78.7in)
NOTE:
REFER
TO
SECTION 9.3. COMPLETE THIS PART
OF THE
INSTALLATION
AS
NECESSARY BEFORE
ASSEMBLING
THE REQUIRED FLUE
ARRANGEMENT.
TOP AIR
DUCT
SOCKET
{DEPTH
18mm
{0.7in)
HOLE
CUT
THROUGH
WALL
TO ACCEPT REAR AIR
DUCT
WALL
THICKNESS TO
INCLUDE
ANY
SURFACE
FINISH, INSIDE
OR
OUTSIDE
REAR AIR
DUCT
SOCKET
{DEPTH
18mm
{0.7in)
INSIDE
PLASTER
DIMENSIONS
ON
PAGE 1
MAY
VARY
DEPENDING
ON
WHETHER
ANY
FLOOR COVERING IS
REMOVED
AND/OR
INSULATING
SHEET IS PLACED BETWEEN THE
APPLIANCE
AND
THE FLOOR
FLOOR LEVEL
8
OUTSIDE
RENDERING
IF
APPLIED
Fig. 5 Rear View of Boiler Pipework and Flue
Connections
NOTE: ALL DIMENSIONS ARE NOMINAL mm (in)
A CENTRAL HEATING RETURN (28mm)
B SAFETY VALVE (22mm)
C GAS INLET (22mm)
D DOMESTIC COLD WATER
IN-
R'h ('/,in BSP)
E DOMESTIC HOT WATER OUT (22mm)
F CENTRAL HEATING FLOW (28mm)
G VENT AND FEED (22mm)
H REAR FLUE CONNECTION (Centrelines)
=
I
[c
r--·
r
--~
r--:_:
I
~
~f
-:-·.
~
•
---
I
I
~..,
H 377mm
(14.81n)
___,
--550mm
{21.6in)--
-1
G & B200mm (7.9in)
D
170mm
(6_7in)
E 135mm
(5.3in)
F 90mm
(3.5~n}
A 60mm (2.4in)
mn
~-g-~
.£
:s
cr>LOcn~rn
<Drnoc<Jc<J
2.!-~~~'22.
E E E E E
E E E E E
N 0
lO
o o
<r>mro~<D
<Dr-r-roro
Fig. 7 Flue/Air Duct Socket Clamping Screws
NOTE: A SIMILAR METHOD
IS USED TO CLAMP THE
REAR AIR DUCT.
ACCESS TO THE SCREW
IS
FROM THE TOP (FIG
6)
VERTICAL AIR DUCT
CLAMPING SCREW
_.----
VERTICAL AIR
__
_;;;____ DUCT SOCKET
REAR
FLUE DUCT
CLAMPING SCREW
Fig. 6 Interchanging Positions of Air Duct/Flue Duct Outlet Blanking Plates
FLUE DUCT HOUSING
REAR
FLUE DUCT BLANKING
PLATE POSITION
9
APPLY SEALANT
AROUND
INSIDE
OF
FLUE
AND
AIR DUCT SOCKETS
tr
REAR
AIR DUCT
BLANKING PLATE
POSITION
I
9.1
a BOILER FLUE
ASSEMBLY
REAR
OUTLET
100mm-1000mm
(4in-39.4in}
NOTE:
An
extension
kit
is
NOT
required.
1.
Cut
the
air
duct
to
length
as
follows:-
(a)
Measure
the
wall
thickness
Land
add
28mm
(1.1in).
(Fig 4, 8
and
15).
This
is
the
overall
length
of
110mm
(4.5in)
diameter
air
duct
required.
(b)
Reduce
the
air
duct
'A'
to
L +
28mm
(1.1in).
Note.
that
one
end
of
the
duct
has
two
holes
drilled.
DO
NOT CUT FROM THIS END
OF
THE DUCT.
2.
Cut
the
flue
duct
to
length
as
follows:-
(a)
Take
wall
thickness
Land
add
51mm
(2.0in).
This
is
the
overall
length
of
60mm
diameter
(2.38in)
flue
duct
required.
(b)
Reduce
the
flue
duct
to
'C'
to
L +
51mm
(2.0in)
by
cutting
from
either
end.
(Fig 9).
3.
Refer
to
Figs 6 &
7.
Slacken
the
vertical
air
duct
clam-
ping
screw
sufficient
to
allow
the
air
duct
blanking
plate
to
be
pulled
out
of
its
socket.
This
will
facilitate
access
to
the
rear
flue
duct
clamping
screw.
Depending
on
wall
thickness
and
space
available
the
flue
duct
only
should
either:-
(a) Be
passed
through
the
wall
from
outside
and
then
fixed
into
the
socket
at
the
rear
of
the
flue
duct
housing
(Fig 8)
or
(b)
If
the
flue
duct
is
relatively
short
e.g.
less
than
400mm
{16in)
it
may
be
fixed
directly
to
the
flue
duct
housing
prior
to
moving
the
boiler
into
posi-
tion
in
front
of
the
inner
wall
face. (Fig 8).
4.
Remove
the
backing
paper
from
the
square
sealing
gasket
provided.
Position
the
gasket
as
shown,
then
press
the
adhesive
backed
side
firmly
against
the
back
panel,
around
the
rear
flue
outlet
(Fig 8).
Either
(a)
Apply
a
bead
of
silicone
sealant
around
the
inside
of
the
rear
flue
duct
socket
and
around
the
inside
of
the
rear
air
duct
socket.
Move
the
appliance
into
position,
square
to
the
wall
face,
standing
centrally
in
front
of
the
hole
in
the
wall.
Position
the
back
pane140mm
{1.6in) in
front
of
the
watl
face. Pass
the
flue
duct
through
the
wall
and
push
the
end
fully
home
into
the
rear
flue
duct
socket.
Working
through
the
top
air
duct
socket
tighten
the
rear
flue
duct
clamping
screw.
Make
sure
the
flue
duct
is
pos-
itioned
concentrically
within
the
rear
air
duct
socket
and
the
hole
in
the
wall.
or
(b) Push
one
end
of
the
flue
duct
fully
home
into
the
rear
flue
duct
socket.
Working
through
the
top
air
duct
socket
tighten
the
rear
flue
duct
clamping
screw.
Make
sure
the
flue
duct
is
positioned
con-
centrically
within
the
rear
air
duct
socket.
Move
the
appliance
into
position,
square
to
the
wall
face,
with
the
back
panel
about
40mm
(1.6in)
in
front
of
the
wall.
Allow
the
flue
duct
to
pass
into
the
hole
and
check
the
duct
is
positioned
concentrically.
5.
Fit
the
flue
terminal
into
the
end
of
the
air
duct
with
holes.
Slide
the
flue
terminal
into
the
air
duct
up
to
the
rolled
stop
channel.
Using
the
holes
in
the
air
duct
as a
guide
drill
through
the
flue
terminal
with
the
3mm
drill
supplied.
Screw
the
assembly
together
with
two
No
6 x
10mm
self-tapping
screws
provided.
(Fig 10).
6.
RECHECK
THAT
ANY
STUB
PIPE
CONNECTIONS
RE-
QUIRED HAVE
BEEN
MADE. (SECTION 9.3).
7.
Working
from
outside
pass
the
air
duct
and
terminal
assembly
through
the
hole.
A
flue
expansion
joint
of
about
100mm
{4in) is
allowed
for.
The
short
section
of
flue
duct
inside
the
terminal
will
engage
and
push
over
the
section
of
flue
duct
connected
to
the
boiler,
provided
the
air
and
flue
duct
have
been
cut
ac-
curately.
10
Fig. 8 Rear Flue
Application
FLUE DUCT HOUSING
PLAN VIEW
,,
"
CLAMPING
,..--------------,\1
SCREW
P~b.R
FLUE
OUTLET
SOCKET
SEALANT
SEALING
GASKET
BLANKING PLATE
REMOVED FROM TOP AIR
DUCT INLET SOCKET
TOP AIR/FLUE DUCT
CLAMPING SCREWS
BLANKING PLATE "
FITIED
IN TOP FLUE
OUTLET SOCKET
ACCESS PANEL, WITH
M5
SLOTIED
HEAD FIXING
SCREW
FOR
TOP FLUE OUTLET CLAMPING SCREW
REAR
AIR DUCT /
CLAMPING SCREW
OUTER
WALL
FACE
POSITION
SEALING GASKET
AROUND
REAR
FLUE OUTLET AS SHOWN
Fig.Ba OUTER
WALL
SEALING
GASKET
/