Xvent Atacama 2 User manual

1
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
INSTRUCTIONS FOR OPERATION AND
INSTALLATION OF THE EXTRACTION
UNIT AND THE ATACAMA
DESTRATIFICATION UNIT

2
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
CONTENT
1. General information ....................................................................................................................................................... 4
1.1. Introduction .................................................................................................................................................................. 4
1.2. Use of the unit............................................................................................................................................................... 4
1.3. Transport, inspection of delivery and storage........................................................................................................... 4
1.4. Contents of the package .............................................................................................................................................. 5
1.5. Before start of installation ........................................................................................................................................... 5
2. Technical parameters ..................................................................................................................................................... 5
2.1. Atacama heating unit design ....................................................................................................................................... 5
EXHAUST COVER ....................................................................................................................................................... 5
2.1.1. EXHAUST COVER ....................................................................................................................................... 5
2.1.2. WATER EXCHANGER ................................................................................................................................. 5
2.1.3. FAN ........................................................................................................................................................... 5
2.1.4. CONSOLE ................................................................................................................................................... 5
2.2. Main dimensions and minimum working space requirements for Atacama units ............................................... 6
2.3. Technical data ............................................................................................................................................................... 7
2.4. Technical data of water heaters.................................................................................................................................. 7
3. Installation of heating units in the working position .................................................................................................... 9
3.1. General information, recommendations and safety during installation of the Atacama heating unit .............. 9
3.1.1. Electrical safety before assembling the unit ........................................................................................... 9
3.1.2. Modification of existing heating distribution systems ........................................................................... 9
3.1.3. Load bearing capacity of the assembly site............................................................................................. 9
3.1.4. Minimum assembly distances ................................................................................................................. 9
3.1.5. Minimum safety distance from flammable substances .......................................................................... 9
3.2. Ceiling installations .................................................................................................................................................... 10
3.3. Wall installation .......................................................................................................................................................... 10
3.4. Examples of chained heating units ATACAMA ........................................................................................................ 10
3.5. Water exchanger connection ................................................................................................................................... 11
3.5.1. Connection of the unit to the existing hot water distribution system ................................................................. 11
3.5.2. Water exchanger connection .................................................................................................................................... 11
3.5.3. Venting (discharge) valve ....................................................................................................................... 12
3.5.4. Example of hydraulic diagram of the unit ............................................................................................. 12
3.6. Electrical installation and electrical connection ...................................................................................................... 12
3.6.1. General Information -Safety .................................................................................................................. 12
3.6.2. Power and control cables ofthe unit ..................................................................................................... 13
3.6.3. Description of power and control cables .............................................................................................. 13
3.6.4. Connection to the mains ........................................................................................................................ 14
3.7. Direction lamellas setting .......................................................................................................................................... 15

3
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
4. Regulation ..................................................................................................................................................................... 15
4.1. General Information –Safety ..................................................................................................................................... 15
4.2. Control elements ........................................................................................................................................................ 15
5. Atacama heating unit wiring diagram ......................................................................................................................... 16
5.1. Wiring diagram for connection of units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator ELEMENTAIR-E-M1 .......... 16
5.2. Connection of chained units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator ELEMENTAIR-E-M1 ........... 16
5.3. Connection of units ATA1-2-ECS, ATA1-3-ECS, ATA4-ECS with regulator ELEMENTAIR-B-M1 ........................... 17
5.4. Connection of chained units ATA1-2-ECS, ATA1-3-ECS, ATA4-ECS with regulator ELEMENTAIR-B-M1 ............ 17
5.5. Connection of units withoutregulation .................................................................................................................... 18
6. Commissioning ............................................................................................................................................................. 18
6.1. Before the first start , check the following: ............................................................................................................. 18
6.2. Switching on ................................................................................................................................................................ 18
7. Regular maintenance and cleaning of Atacama heating unit ..................................................................................... 18
7.1. Regular maintenance ................................................................................................................................................. 18
7.2. Cleaning procedure .................................................................................................................................................... 19
8. Service ........................................................................................................................................................................... 20
8.1. Troubleshooting procedure ..................................................................................................................................... 20
9. Decommissioning and recycling ................................................................................................................................... 20
10. Warranty................................................................................................................................................................... 21
11. Conclusion ................................................................................................................................................................ 21

4
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
1. General information
1.1. Introduction
- This document "Installation and Operating Manual" is intended for the heating unit Atacama
(hereinafter referred to as the "Unit") used to heat the required space by warm air. Detailed
familiarisation with this document is important for correct and safe installation and functioning of the unit.
Failure to follow the conditions in this document may result in malfunction of the unit.
- The assembly and connection of the unit may only be carried out by a trained person with the
appropriate authorization to connect electrical equipment, which has suitable tools and means
available. During the assembly, it is necessary to observe all the instructions and recommendations in
this manual.
- For the correct operation and long-term service life of the unit, it is necessary to prevent access to
unauthorised persons and to train operators according to this document and applicable legislative
regulations.
- The documentation must always be available at the place of installation for any service intervention. It
is forbidden to interfere in any way with the internal connection of the unit, which does not correspond to
the instructions given in this manual. Due to the continuous development of our products, we reserve the
right to change this manual without prior notice.
1.2. Use of the unit
- The Atacama heating unit is designed to heat and filter air in the indoor environment (it is possible to
order filters as accessories) of industrial halls, warehouses, sports facilities, workshops and smaller
facilities.
- The unit is intended for indoor and dry spaces with ambient temperatures from 5°C to +40°C.
- The unit can also be used for environments with a higher non-condensing humidity corresponding to
the protection levels IP54 and IP44 according to EN 60529, depending on the type of unit. The unit may
also be used in corrosion environment C2, according to EN ISO 9223. The unit must not be operated in
environments with a risk of explosion and increased dustiness.
- Neither the manufacturer nor the supplier is liable for damage caused by improper use of the units.
The risk is borne by the user alone.
- The unit must not be operated during finishing construction activities, especially during activities that
create excessive dustiness, e.g. by grinding concrete, plasterboard, etc...
1.3. Transport, inspection of delivery and storage
- Before starting the installation and before unpacking the unit from the box, it is necessary to check for
any traces of damage on the packaging. In case of damage to the packaging, please contact your carrier.
- Check if the product ordered by you is in agreement. After unpacking, check that the unit and other
components are intact. Please report any non-conformity with the order to the supplier immediately. If an
order complaint is not made immediately after delivery, it will not be taken into account later.
- If you do not install the unit immediately after purchase, it must be stored in an indoor, non-
condensing environment at temperatures in the range of 5 to 40°C. If the product has been transported at
temperatures below 5°C, it must be stored after unpacking for at least 2 hours in the working environment
where it will be installed.
- Use adequate tools to prevent damage to the goods and to avoid health and safety risks of persons.

5
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
1.4. Contents of the package
Atacama heating unit 1x
Assembly console 1x
Assembly accessories – screw M6x20 4x
Quick manual + Safety Data Sheet 1x
Name plate 1x
1.5. Before start of installation
- Before starting the installation, we recommend that you attach the serial nameplate (normally
delivered with the unit in its package) to the operational documentation (e.g.: equipment operating book,
etc.), which is subsequently kept for a later maintenance record and the respective servicing.
- Before starting all installation or maintenance work, it is necessary to switch off the power supply
and secure the switch against switching it on again.
2. Technical parameters
2.1. Atacama heating unit design
2.1.1. EXHAUST COVER
It forms a sheet metal casing of the unit and also contains turning lamellas to direct the air blowing out of the
unit, as required by the user. The cover is in RAL 7016 colour.
2.1.2. WATER EXCHANGER
Maximum permissible temperature/pressure of heating medium is 120°C / 1.6MPa. The exchanger consists of
an aluminium - copper structure that is protected by powder coating RAL 9005. The connection to the water
exchanger is solved by connecting collectors with mail thread ¾“. The exchanger is equipped with a venting
valve on both collectors.
2.1.3. FAN
The maximum operating temperature of the fan motor is + 60°C, operating humidity 0-90% non-condensing,
protection class IP54 and IP44 according to the selected unit type, motor insulation class B. The fan fan and its
board are treated with powder coating RAL 9005.
2.1.4. CONSOLE
Standard part of the delivery. Steel sheet structure with thickness of 3 mm, treated against corrosion with RAL
9005.
EXHAUST COVER
WATER EXCHANGER
FAN
CONSOLE

6
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
2.2. Main dimensions and minimum working space requirements for Atacama units
ATACAMA HEATING UNIT
ATACAMA
-
D DESTRATIFICATION UNIT
MIN. INSTALLATION
AND OPERATING SPACE
MIN. INSTALLATION
AND OPERATING SPACE

7
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
2.3. Technical data
EC Declaration of Conformity – the current and full version of the EC Declaration of Conformity can be seen on our website
www.xvent.cz under the Atacama product documents
2.4. Technical data of water heaters

8
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65

9
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
3. Installation of heating units in the working position
3.1. General information, recommendations and safety during installation of the Atacama heating unit
3.1.1. Electrical safety before assembling the unit
- Before starting any assembly works, it is necessary to switch off the power supply to the prepared
electrical installation for subsequent activation of the unit. During installation, the switch must be
secured against being switched on again.
3.1.2. Modification of existing heating distribution systems
- It is appropriate to use filters for rough impurities in the heating systems to protect the water exchanger
from possible damage from the existing distribution systems.
3.1.3. Load bearing capacity of the assembly site
- The selected assembly site must be suitable for the permanent load by the unit. In case of doubt, the
load capacity of the wall/walls must be verified by structural engineer or other responsible person.
3.1.4. Minimum assembly distances
- the minimum distance of the unit from the wall is 0.2 m. If this distance is not observed, the unit may not
work properly and the fan may be damaged or the unit’s noise may increase. The minimum height of
assembly of the unit from the floor is 2.5 m. Adjust the exhaust of the unit so that there is no draft in the
heated space. The air flow exiting the exhaust grid must not be directed directly to walls, beams, shelves,
machines, etc.
3.1.5. Minimum safety distance from flammable substances
- The minimum safety distance from flammable substances is at least 0.5 m from the side of the unit and 1
m in the direction of exhaust from the unit
Installation distances in relation to blowing capacity from ATACAMA unit

10
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
3.2. Ceiling installations
3.3. Wall installation
3.4. Examples of chained heating units ATACAMA

11
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
3.5. Water exchanger connection
3.5.1. Connection of the unit to the existing hot water distribution system
- Connect the unit to the heating system using a flexible connection (e.g. flexible hoses – with braided
armour). The heating system piping must not put any load on the exchanger throats.
3.5.2. Water exchanger connection
- Water supply and drainage necks are marked on the water exchanger collectors. To tighten the connected
piping to the unit, use the hexagonal profile on the water exchanger neck. This prevents the exchanger
outlet from being overturned, which may result in irreversible damage to the water exchanger.
- After connecting the water exchanger to the heating system, a pressure test of the unit connection is
recommended.
- The tests must be carried out by a person qualified in this field with knowledge of the applicable
regulations and standards of the country concerned.
- We recommend installing shut-off valves on the water exchanger inlet and outlet for the shut-off of the
heating medium, or to allow the unit dis-assembly without the need to drain water from the heating
system.

12
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
3.5.3. Venting (discharge) valve
- Water supply and drainage necks are marked on the water exchanger collectors. To tighten the connected
piping to the unit, use the hexagonal profile on the water exchanger neck. This prevents the exchanger
outlet from being overturned, which may result in irreversible damage to the water exchanger.
- Drain the heating medium from the exchanger, by loosening the lower vent screw. If the unit is refilled with
a heating medium, check that the exchanger is vented.
- Place the vent valves at the highest installation point.
3.5.4. Example of hydraulic diagram of the unit
- If the automatic control valve is not installed to control the heating capacity, we recommend to shut off the
heating water supply to the exchanger when the fan is switched off. Any high temperature inside the unit
on the exchanger may reduce the fan lifespan.
3.6. Electrical installation and electrical connection
3.6.1. General Information -Safety
- The relevant electrical installation and electrical assembly of the units may only be performed by persons
qualified for this activity with valid authorization and knowledge of the applicable standards and directives.
Before starting any assembly works, it is necessary to switch off the power supply to the prepared electrical
installation for subsequent activation of the unit. During installation, the switch must be secured against
being switched on again by an unauthorized person.
- The unit shall be connected to the main power supply by the TN-S system (neutral wire connected) using
an insulated cable in accordance with the diameter and corresponding regulations.

13
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
- The supply voltage of the unit must be connected in such a way that all poles of the network are
disconnected from the power supply by one element (e.g. main switch). The unit inlet phase must be
connected via a protective power circuit breaker (protective switch) according to the corresponding
current. The minimum distance between the disconnected contacts must be greater than 3mm.
- Before installation, check that the cable marking corresponds to the electrical diagram. If you have any
doubts, please contact your supplier.
3.6.2. Power and control cables ofthe unit
- the unit is equipped with a separate power supply and separate control cable (strand-type cable). Stripping
of cables to individual conductors is 80mm. The conductors are equipped with a crimped terminal with
insulation (sleeve).
- Table with minimum cable cross-section and recommended value of safety cut-out:
3.6.3. Description of power and control cables
- The correct connection and use of all or part of the conductors taken out from the unit is subject to the
selected type of control. The connection of the supply and control wires must be carried out in such a
way that they cannot in any case be interconnected or confused. This would result in the destruction of
the unit fan and possible further damage to the property and health of persons.
the power supply cable contains 3
conductors.
- Brown conductor – supply phase. In
the diagram marked as L
- Blue conductor - neutral wire. In the
diagram marked as N
- Green-yellow conductor — earthing
conductor.
In the diagram marked as Pe
- Yellow wire – input control signal 0-
10VDC or PWM. In diagram marked
as 0-10VDC/PWM
- Black wire - input special grounding
conductor to the fan control signal.
It shall not be used other than to
control the fan. In diagram marked
as GND
-
Red conductor
–
output voltage

14
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
3.6.4. Connection to the mains
- Connection to the mains is recommended by means of the wiring box with the corresponding electrical
protection class (according to the installation space).
- The electric installation box must be attached to a solid non-combustible surface at the maximum distance
from the unit according to length of the motor cables.
- Table of cable lengths on the unit
- In the wiring box, connect the unit cable with cable from the mains
3.6.5. Display of electrical parameters on the unit

15
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
3.7. Direction lamellas setting
- Adjust the exhaust lamellas by deflecting them from the front exhaust cover.
- The minimum lamellas deflection for a correct function of the unit is from 45°, which allows ideal direction
of the blown air into the heated space.
- The lamellas must always be opened during operation of the unit
4. Regulation
4.1. General Information –Safety
- The electrical connections of the control elements may only be performed by persons qualified for this
activity with the applicable authorization and knowledge of the relevant standards and directives. Before
starting any assembly work, it is necessary to switch off the power supply. During installation, the switch
must be secured against being switched on again by an unauthorized person.
- Before starting the installation of the control elements and connecting the installation, it is necessary to
familiarize yourself with the original documentation of the individual elements.
4.2. Control elements
Gradually flex the lamellas from top to bottom

16
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
5. Atacama heating unit wiring diagram
5.1. Wiring diagram for connection of units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator
ELEMENTAIR-E-M1
5.2. Connection of chained units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator ELEMENTAIR-E-M1

17
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
5.3. Connection of units ATA1-2-ECS, ATA1-3-ECS, ATA4-ECS with regulator ELEMENTAIR-B-M1
5.4. Connection of chained units ATA1-2-ECS, ATA1-3-ECS, ATA4-ECS with regulator ELEMENTAIR-B-M1

18
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
5.5. Connection of units withoutregulation
- Unit – the fan operation – can be switched on and off only by the ON/OFF controls at the power supply to
the fan.
- Switching/disconnection of the supply voltage can be solved by e.g.: timer, spatial thermostat.
- Other regulation elements will not be connected to the regulator functionality. Their regulation must be
dealt with separately.
- The supply voltage to the fan 1~230V/50-60Hz must not be modified in any way, otherwise there is a risk
of damage to the unit fan.
- The fan connected in this way only operates at maximum speed and cannot be regulated.
6. Commissioning
6.1. Before the first start , check the following:
- If there are no objects in the unit that could damage the unit (e.g. tools);
- If all the hydraulic connections are properly connected (tightness of the vent valve, connection branch and
the mounted valve);
- If all electrical connections are connected correctly according to technical documentation, including
connection of regulation and accessories;
- If the unit has all the assembly and installation screws tightened, and the lamellas properly deflected.
- All connections must be made in accordance with the technical documentation supplied to the unit and
the documentation supplied to the control elements.
6.2. Switching on
- After the first start, check the basic functionality of the individual parts of the unit (fan operation, heating),
and also focus on the tightness of hydraulic system.
- Check the other functions of the entire assembly according to the instructions for use of the selected
regulator.
7. Regular maintenance and cleaning of Atacama heating unit
- Before any maintenance and cleaning of the unit, the unit must be disconnected from the power supply,
and the heating water supply to the unit exchanger must be switched off. Work must be carried out only
after the exchanger has cooled down. Otherwise, there is a risk of burns and injuries caused by rotating
parts!!!
7.1. Regular maintenance
- Regular inspection of the unit, especially the water exchanger, is recommended to perform every 500 hours
of operation of the unit.
- The unit must also be checked before the start and at the end of the heating season.
- If the unit is not used for a longer period of time, it is necessary to switch off the supply voltage to the unit.

19
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
- If the temperature in the space is assumed to fall below 5°C and the temperature of the heating water is
low, there is a risk of the heat exchanger freezing – bursting. Unit – exchanger is not equipped with anti-
freeze protection.
- Regular maintenance must include: o Check the heat exchanger and clean it from dust and grease, if any.
o Check of the motor and fan (bearings), remove the dust and grease on the protective cage and fan
blades.
o Check of tightening of all screw joints on the unit (e.g. screws for unit fixation on the console,
mounting screws to the wall), including check of mechanical damage of the unit (e.g. loose exhaust
lamellas, damaged fan cage)
o Check and replace fan filter if necessary. If installed.
7.2. Cleaning procedure
- Compressed air, aggressive chemicals, water or sharp objects must not be used to clean the unit
- Always wear protective gloves when cleaning the unit
- The following tools are necessary to clean the unit:
o Wrench of the appropriate size, depending on the unit
o Vacuum cleaner
o A lint-free cloth
o Brush
o Cleaning solution (soap water)
- Clean the housing with a damp cloth soaked with soap water.
- Using an appropriate wrench, remove
the fan from the unit rear plate.
- Clean the fan with brush. Alternatively, wash with a
cloth soaked with soap water.
- Clean the water exchanger and inner housing of
the unit with the vacuum cleaner
1.
- Put the fan back into the rear plate of the unit.
Make sure the fan is properly centred against the

20
Verze 1
–
GBR
(11.3.202
0
)
D
-
502
-
01
65
8. Service
- Comply with the general country-specific provisions. In case of any service activity, it is necessary to
disconnect the unit from the mains and switch off the heating water supply to the unit heat exchanger.
Work must be carried out only after the exchanger has cooled down. Any electrical service work must be
carried out by a person with professional qualifications. Complete the electrical connection precisely
according to the supplied electrical documentation
8.1. Troubleshooting procedure
9. Decommissioning and recycling
All unused or not operable products and packaging should be returned to the
appropriate recycling locations where they will dispose of them in a professional
manner. Please dispose the unusable parts of the product in a controlled landfill. Only
like this the recycled product can be reused and bring a new benefit.
This manual suits for next models
5
Table of contents
Other Xvent Air Handler manuals
Popular Air Handler manuals by other brands

Vents
Vents VUTR 400 V EC user manual

Vents-us
Vents-us TwinFresh Expert RW1-50 V.2 user manual

Vents-us
Vents-us Airvents RH user manual

Lennox
Lennox ELA Series Unit information

Kampmann
Kampmann Ultra Allround Assembly, installation and operating instructions

Trane
Trane IntelliPak WEHE Series Installation, operation and maintenance