BRIEF UNIT INFORMATION
BRIEF UNIT INFORMATION
P14 OF34P13 OF34
USER NOTES AND SERVICE LOG
OUTDOOR UNIT WORKING TEMPERATURE RANGE
Maximum cooling
Minimum cooling
Maximum heating
Minimum heating
o
Outdoor side DB( F)
115(T1)
20
75
5
SPECIFICATION
Outdoor Unit Models WMMS-21CH-V2B(59)(2) (1 to 2)
WMMS-30CH-V2B(59)(2) (1 to 2) WMMS-24CH-V2B(59)(2) (1 to 3)
WMMS-36CH-V2B(59)(2) (1 to 3) WMMS-48CH-V2B(59)(2) (1 to 4)WMMS-42CH-V2B(59)(2) (1 to 4)
Power Supply 208-230/1/60
Cooling Capacity*
(Btu/h)
Max. Allowed IDU Cap. Total 30,000 36,000 48,000 57,000
Rated 18,000 24,000 28,000 30,000
Min. 7,200 10,000 10,000 10,000
Total Power Input in
Cooling Mode* (W)
Max. 2300 3300 4500 4500
Rated 1550 2250 2600 2600
Min. 650 800 900 1000
SEER
HSPF
16.0
8.2
16.0
8.2
16.0
8.2
16.0
8.2
Heating Capacity*
(Btu/h)
32,000 38,000 50,000 59,000
Rated 19,000 29,500 31,000 33,000
Min. 6,500 9,000 9,000 9,000
Total Power Input in
Heating Mode*
Max. 2400 3000 3500 3500
Rated 1750 2500 2920 2920
Min. 650 800 900 1000
WMMS-60CH-V2B(59)(2) (1 to 5)
72,000
42,000
12,000
5100
3950
1200
16.0
8.2
74,000
46,000
10,000
4800
4400
1200
Compressor Manufacturer/trademark
Liquid Valve Size 2 x 1/4" 3 x 1/4" 4 x 1/4" 4 x 1/4"
Gas Valve Size 2 x 3/8" 3 x 3/8" 4 x 3/8" 4 x 3/8"
Sanyo / Mitsubishi / Others Sanyo / Mitsubishi / Others Sanyo / Mitsubishi / Others Sanyo / Mitsubishi / Others
Throttling Method Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Starting Method Transducer starting Transducer starting Transducer starting Transducer starting
Recommended Working Ambient Temp Ranges (F) AC: 20 to 115 HP: 5 to 75 AC: 20 to 115 HP: 5 to 75 AC: 20 to 115 HP: 5 to 75 AC: 20 to 115 HP: 5 to 75
Condenser Aluminum fin-copper tube Aluminum fin-copper tube Aluminum fin-copper tube Aluminum fin-copper tube
Output of Fan Motor (W) 60 60 60 60
Fan Motor RLA (A) 0.65 0.65 0.65 0.65
Fan Motor Capacitor (uF) 3 3.5 3.5 3.5
Air Flow Rate of Outdoor Unit ////
Fan Type-Piece Axial fan 1 Axial fan 1 Axial fan 1 Axial fan 1
Fan Diameter (Inches) 18.1 18.1 18.1 18.1
Defrosting Method Auto Defrost Auto Defrost Auto Defrost Auto Defrost
Climate Type T1 T1 T1 T1
Isolation IIII
Moisture Protection IP24 IP24 IP24 IP24
Max. Operating Pressure at High Side (PSI) 550
Max. Operating Pressure at Low Side (PSI) 175
Sound Pressure Level dB (A) (H/L) 56/54 56/54 56/54 56/54
Sound Power Level dB (A) (H/L) 66/64 66/64 66/64 66/64
Dimensions of Outdoor Unit (W x H x D) (Inches) 33.3 x 27.0 x 11.8 37.4 X 27.5 X 15.5 37.2 X 27.6 X 15.75 37.4 X 27.5 X 15.5
Dimensions of Package (W x H x D) (Inches) 39.1 x 29.5 x 16.9 40.6 X 29.5 X 16.5 40.5 X 29.5 X 18.0 40.6 X 29.5 X 16.5
Net Weight /Gross Weight (LBs) 115 / 126 150 / 161 165 / 176 165 / 176
Refrigerant /Factory Pre-Charge for 25' (LBs) R410A / 2.97 R410A / 4.84 R410A / 4.84 R410A / 4.84
Loading
Quantity
20' Container 87 80 80 80
40' Container 183 170 170 170
40' High Cube Container 183 170 170 170
550 550 550
175 175175
30 30 30/40 40
L.R.A. (A) 27 45 45 45
Compressor RLA (A) 8.4 9.7 9.7 10
Compressor Power Input (W) 1245 2200
Fuse or Circuit Breaker (HVAC Type)
MCA (A) 15 20 20/30 30
Compressor Oil / FV50S / / FV50S / / FV50S / / FV50S /
2200 2200
4 x 1/4" + 3/8"
2 x 3/8" + 2 x 1/2" + 5/8"
Sanyo / Mitsubishi / Others
Electronic Expansion Valve
Transducer starting
AC: 20 to 115 HP: 5 to 75
Aluminum fin-copper tube
140
1.1
6
/
Axial fan 1
22.5
Auto Defrost
T1
I
IP24
56/54
66/64
42.25 X 43.5 X 17.5
46.0 X 48.6 X 19.4
225 / 248
R410A / 10.6
50
100
100
550
175
50
55
13
50
/ FV50S /
3000
Max. Allowed IDU Cap. Total
YMGI, Engineered Comfort Products for ASustainable and Efficient Green World !YMGI, Engineered Comfort Products for ASustainable and Efficient Green World !
SAMPLE SIZE COMBINATIONS AND PERFORMANCE DATA
1) The DC inverter outdoor unit may work with many different combinations of styles (wall, ceiling, ceiling/floor, concealed, etc.) and sizes of indoor units.
2) In real world, there might be small percentage of applications where all indoor units will be working at peak demand of cooling or heating needs. One room
could be at peak demand, others may not. This way, the outdoor unit doesn't need to work at peak speed/load all the time.
3) Not all pairs of refrigerant valves need to be connected at initial installation. But, there is minimum amount of indoor units shall be connected (refer to the spec.
sheet for details).
If only few of indoor units are installed initially, other indoor units can still be installed in the future whenever ready (need to vacuum and adjust refrigerant
charge accordingly).
4) These outdoor unit can only drive all indoor units for one thermal mode at one time. Shall not run cooling in one indoor unit, and heating in another one. In
case of mode conflict or clash, correct the thermal mode which is different from others, or shut off power and select one thermal mode for all indoor units.
Indoor Unit
Combinations Total
Capacity Room A Room B Room C Room D Capacity Rating-Btu/h
(Min. Max.) Input Power Rating-Watts
(Min. Max.)
WMMS-2AM21-V2B(59)(2) / WMMS-2AM30-V2B(59)(2) Cooling Performance Nominal Data
9K 9K 10880 10880 (9180~12240) 1050 (1000~1300)
12K 12K 11900 11900 (9180~14960) 1050 (1000~1500)
18K 18K 17000 17000 11220~22780)( 1400 (1000~2600)
9+9K 18K 8500 8500 17000 11220~22780)( 1400 (1000~2600)
9+12K 21K 8500 11900 20400 11220~26520)( 1800 (1000~3300)
12+12K 24K 11900 11900 23800 11220~27880)( 2300 (1000~3800)
9+18K 27K 8840 15300 24140 11220~32300)( 2200 (1000~4600)
12+18K 30K 11900 12240 24140 11220~32300)( 2200 (1000~4600)
9+9+9K 27K 8075 8075 8075 24140 11220~32300)( 2200 (1000~4600)
9+9+12K 30K 7140 7140 9860 24140 11220~32300)( 2200 (1000~4600)
9+12+12K 33K 6460 8840 8840 24140 11220~32640)( 2200 (1000~4650)
12+12+12K 36K 8075 8075 8075 24140 11220~32640)( 2200 (1000~4650)
9+9+18K 36K 7480 7480 9180 24140 11220~32640)( 2200 (1000~4650)
9+12+18K 39K 7140 7820 9180 24140 11220~32640)( 2200 (1000~4650)
12+12+18K 42K 7820 7820 8500 24140 11220~32640)( 2200 (1000~4650)
WMMS-3AM24-V2B(59)(2) / WMMS-3AM36-V2B(59)(2) Cooling Performance Nominal Data
9+9K 18K 8500 8500 17000 11220~22780)( 1400 (1000~2600)
9+12K 21K 8500 11900 20400 11220~26520)( 1800 (1000~3300)
12+12K 24K 11900 11900 23800 11220~27880)( 2300 (1000~3800)
9+18K 27K 8840 15300 24140 11220~32300)( 2200 (1000~4600)
12+18K 30K 11900 12240 24140 11220~32300)( 2200 (1000~4600)
9+9K 18K 8500 8500 1400 (1000~2600)
9+12K 21K 8500 11900 1800 (1000~3300)
9+9+9K 27K 8044 8044 8044 2200 (1000~4600)
9+9+12K 30K 7140 7140 9860 2200 (1000~4600)
9+12+12K 33K 6460 8840 8840 2200 (1000~4650)
12+12+12K 36K 8044 8044 8044 2200 (1000~4650)
9+9+18K 36K 7480 7480 9180 2200 (1000~4650)
9+12+18K 39K 7140 7820 9180 2200 (1000~4650)
12+12+18K 42K 7820 7820 8500 2200 (1000~4650)
9+9+9+9K 36K 6800 6800 6800 6800 2480 (1000~4650)
9+9+9+12K 39K 1750 1750 1750 2750 2480 (1000~4650)
9+9+12+12K 42K 1500 1500 2500 2500 2480 (1000~4700)
9+12+12+12K 45K 1700 2100 2100 2100 2480 (1000~4700)
WMMS-4AM42-V2B(59)(2) Cooling Performance Nominal Data
Indoor Unit
Combinations Total
Capacity Room A Room B Room C Room D Capacity Rating-Btu/h
(Min. Max.) Input Power Rating-Watts
(Min. Max.)
12+12K 24K 11900 11900 2300 (1000~3800)
9+18K 27K 8840 15300 2200 (1000~4600)
12+18K 30K 11900 12240
10880 (9180~12240)
11900 (9180~14960)
17000 (11220~22780)
17000 (11220~22780)
20400 (11220~26520)
24140 (11220~32300)
24140 (11220~32300)
24140 (11220~32640)
24140 (11220~32640)
24140 (11220~32640)
24140 (11220~32640)
24140 (11220~32640)
27200 (11220~32640)
23800 (11220~27880)
24140 (11220~32300)
24140 (11220~32300)
2200 (1000~4600)
Indoor Unit
Combinations Total
Capacity Room A Room B Room C Room D Capacity Rating-Btu/h
(Min. Max.) Input Power Rating-Watts
(Min. Max.)
9+9K 10880 10880 21760 (8670~27880) 2050 (900~2950)
9+12K 10880 13600 24480 (8670~28900) 2300 (900~3300)
12+12K 13260 13260 26520 (10200~31620) 2400 (900~3500)
9+18K 9860 17000 26860 (10200~31620) 2400 (900~3500)
12+18K 12240 15300 27540 (10540~33660) 2400 (1000~3900)
9+9+9K 9180 9180 9180 27540 (10540~33660) 2400 (1000~4000)
9+9+12K 8500 8500 10540 27540 (10540~33660) 2400 (1000~4000)
9+12+12K 7480 10370 10370 28220 (10540~33660) 2450 (1000~4000)
9+9+18K 7990 7990 11560 27540 (10540~33660) 2400 (1000~4000)
12+12+12K 9690 9690 9690 29070 (10540~33660) 2500 (1000~4000)
9+12+18K 7480 9180 10880 27540 (10540~33660) 2400 (1000~4000)
12+12+18K 8500 8500 10540 27540 (10540~33660) 2400 (1000~4000)
9+9+9+9K 8160 8160 8160 8160 32640 (11220~37400) 2600 (1100~4200)
9+9+9+12K 7480 7480 7480 10200 32640 (11220~37400) 2600 (1100~4200)
9+9+12+12K 7140 7140 9180 9180 32640 (11220~37400) 2600 (1100~4200)
9+12+12+12K
18K
21K
24K
27K
30K
27K
30K
33K
36K
36K
39K
42K
36K
39K
42K
45K 6120 8840 8840 8840 32640 (11220~37400) 2600 (1100~4200)
Indoor Unit
Combinations Total
Capacity Room A Room B Room C Room D Capacity Rating-Btu/h
(Min. Max.) Input Power Rating-Watts
(Min. Max.)
WMMS-4AM42-V2B(59)(2) Heating Performance Nominal Data
Indoor Unit
Combinations Total
Capacity Room A Room B Room C Room D Capacity Rating-Btu/h
(Min. Max.) Input Power Rating-Watts
(Min. Max.)
9K 9K 9860 9860 (6630~15980) 1100 (850~2450)
12K 12K 13260 13260 (6800~17000) 1450 (850~2500)
18K 18K 19720 19720 (8670~27880) 1850 (900~2950)
9+9K 18K 10880 10880 21760 (8670~29240) 2050 (900~2950)
9+12K 21K 10880 13600 24480 (8670~30600) 2300 (900~3300)
12+12K 24K 13260 13260 26520 (10200~32640) 2400 (900~3500)
9+18K 27K 12240 17000 26860 (10200~31620) 2400 (900~3500)
12+18K 30K 12240 15300 27540 (10540~33660)
9+9+9K 27K 9632 9632 9632 28900 (10540~37400)
9+9+12K 30K 9010 9010 10880 28900 (10540~37400)
9+12+12K 33K 7820 10880 10880 29580 (10540~37400) 2400 (1000~3900)
2350 (1000~4000)
2350 (1000~4000)
2400 (1000~4000)
9+9+18K 36K 7990 7990 13600 29580 (10540~37400)
12+12+12K 36K 9860 9860 9860 29580 (10540~37400)
9+12+18K 39K 7480 9180 12920 29580 (10540~37400)
12+12+18K 42K 8500 8500 12580 29580 (10540~37400)
2600 (900~3800)
2600 (900~3800)
2600 (900~3800)
2600 (900~3800)
9+9K 18K 10880 10880 21760 (8670~29240) 2050 (900~2950)
9+12K 21K 10880 13600 24480 (8670~30600) 2300 (900~3300)
12+12K 24K 13260 13260 26520 (10200~32640) 2400 (900~3500)
9+18K 27K 12240 17000 26860 (10200~31620) 2400 (900~3500)
12+18K 30K 12240 15300 27540 (10540~33660)
WMMS-3AM24-V2B(59)(2) / WMMS-3AM36-V2B(59)(2) Heating Performance Nominal Data
WMMS-2AM21-V2B(59)(2) / WMMS-2AM30-V2B(59)(2) Heating Performance Nominal Data
Indoor Unit
Combinations Total
Capacity Room A Room B Room C Room D Capacity Rating-Btu/h
(Min. Max.) Input Power Rating-Watts
(Min. Max.)
RECOMMENDED MATCHING INDOORAND OUTDOOR UNITS (NOT ALL
POSSIBILITIES BEING LISTED)
1 Indoor Unit 2 Indoor Units 3 Indoor Units 4 Indoor Units
09K 12K
18K 09K+12K09K+09K
1 Indoor Unit 2 Indoor Units 3 Indoor Units 4 Indoor Units
4 Indoor Units
09K+12K
09K+18K 12K+12K 09K+09K+09K 09K+09K+12K 09K+09K+18K
1 Indoor Unit 2 Indoor Units 3 Indoor Units
Not allowed
Not allowed
09K+09K+12K 09K+12K+12K 09K+09K+09K+09K 09K+09K+09K+12K 09K+09K+12K+12K12K+12K 09K+18K 09K+12K+18K
09K+09K+24K 12K+12K+18K 09K+12K+12K+12K 12K+12K+12K+12K 09K+09K+09K+18K
12K+18K
1 Indoor Unit 2 Indoor Units 3 Indoor Units 4 Indoor Units
09K+09K+09K 09K+09K+12K
09K+12K+24K
09K+12K+12K 09K+09K+09K+09K 09K+12K+12K+18K
09K+09K+09K+12K
09K+09K+12K+18K 09K+09K+09K+18K
09K+09K+12K+24K 09K+12K+12K+24K
12K+18K 09K+24K 09K+09K+18K 12K+12K+12K 09K+12K+18K
12K+12K+24K 09K+09K+09K+24K 12K+12K+12K+12K
12K+12K+18K
Not allowed
Not allowed Not allowed
Not allowed
12K+24K
12K+24K
18K+18K 09K+12K+12K 09K+12K+18K 12K+12K+12K
18K+18K
Important Notes:
Indoor Unit Mix and Match Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-21CH-V2B(59)(2) / WMMS-30CH-V2B(59)(2)
Indoor Unit Mix and Match Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-24CH-V2B(59)(2) / WMMS-36CH-V2B(59)(2)
Indoor Unit Mix and Match Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-42CH-V2B(59)(2)
Indoor Unit Mix and Match Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-48CH-V2B(59)(2)
12K+12K 12K+18K24K
1 Indoor Unit
Not allowed
Indoor Unit Mix and Match Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-60CH-V2B(59)(2)
2 Indoor Units 5 Indoor Units
09K+09K+09K+12K+12K/18K/24K
09K+12K+12K+12K+12K/18K
09K+09K+12K+12K+18K
09K+12K+12K+18K+18K
12K+12K
18K+18K
18K+24K
12K+18K
12K+24K
24K+24K
3 Indoor Units
09K+09K+09K
09K+09K+18K
12K+12K+12K
09K+09K+12K
12K+12K+18K
12K+12K+24K
09K+12K+12K
09K+12K+18K
09K+12K+24K
4 Indoor Units
09K+09K+09K+12K
09K+09K+12K+18K
09K+09K+12K+24K
09K+09K+09K+09K
09K+12K+12K+18K
09K+12K+12K+24K
09K+09K+09K+18K
12K+12K+12K+12K
12K+12K+12K+24K
09K+09K+09K+09K+12K/18K/24K
09K+09K+12K+12K+12K/18K/24K
12K+12K+12K+12K+12K/18K
09K+09K+12K+18K+18K
12K+12K+12K+18K+18K
18K+24K
18K+18K
24K+24K
18K+24K
9K+9K+9K
9K+9K+18K
12K+12K+12K 09K+12K+24K 09K+09K+12K+18K
* When the rated total capacity of all the indoor units exceeds the rated capacity of outdoor unit, each indoor unit may not output the rated
capacity and one may differ from other, upon other installation/operation factors, it all units are turned on to run compressor simultaneously.
* Must follow pipe length and refrigerant charge adjustment as instructed in below table:
PIPE ADAPTOR
Whenever the outdoor unit gas valve of size 3/8" is to connect with indoor unit gas pipe of 1/2" or 5/8",
one 3/8" - 1/2" or 3/8" - 5/8" adaptor is to be used in between. This reducer is packed separately and
shall be installed at job site. PIPE ADAPTOR
PIPE FROM
INDOOR UNIT
OUTDOOR UNIT VALVE
OUTDOOR UNIT WORKING TEMPERATURE RANGE