YOKOGAWA SmartDac Plus GX70SM User manual

Introduction
Thank you for purchasing the SMARTDAC+ GX70SM
Wireless Input Unit. This manual explains the precaution on
the use, installation, and wiring of the GX70SM.
For details on the wireless settings, input settings, and
maintenance of the GX70SM, see the Wireless Input Unit
User's Manual (IM 04L57B01-01EN) (Electronic Manual).
This manual denotes devices with their product names or
model (e.g. GX70SM).
To ensure correct use, please read this manual and the
following manuals thoroughly before beginning operation.
Paper Manuals
Manual Title Manual No.
Model GX70SM Wireless Input Unit
First Step Guide (Notes about Using This Product)
IM 04L57B01-02EN
(this manual)
Electronic Manuals and General Specifications
Manual Title Manual No.
Model GX70SM Wireless Input Unit
Users Manual
IM 04L57B01-01EN
Genaral Specifications
Title General
Specifications No.
Model GX70SM Wireless Input Unit GS 04L57B01-01EN
You can download these documents from the following web
page:
http://www.smartdacplus.com/manual/en/
Application software
To configure the wireless input unit, generate logging
data files, and perform maintenance, you need a software
application exclusive to the wireless input unit, “Wireless Input
Unit Configurator.”
Download it from the following website.
http://www.smartdacplus.com/software/en/
User Registration
Thank you for purchasing YOKOGAWA products.
We invite you to register your products in order to receive the most up
to date product information. To register, visit the following URL.
http://www.yokogawa.com/ns/reg/
Notes
● The contents of this manual are subject to change without
prior notice as a result of continuing improvements to the
instrument’s performance and functions.
● Every effort has been made in the preparation of this
manual to ensure the accuracy of its contents. However,
should you have any questions or find any errors, please
contact your nearest YOKOGAWA dealer.
● Copying or reproducing all or any part of the contents of
this manual without YOKOGAWA’s permission is strictly
prohibited.
● This manual explains the functions of the product. It does
not guarantee that the product will suit a particular purpose
of the user.
Revisions
June 2018 1st Edition September 2018 2nd Edition
March 2019 3rd Edition
Trademarks
● SMARTDAC+ and SMARTDACPLUS are registered
trademark of Yokogawa Electric Corporation.
● Microsoft and Windows are registered trademarks or
trademarks of Microsoft Corporation in the United States
and other countries.
● Pentium is a registered trademark of Intel Corporation.
● Adobe and Acrobat are registered trademarks or
trademarks of Adobe Systems Incorporated.
● Company and product names that appear in this manual
are registered trademarks or trademarks of their respective
holders.
● The company and product names used in this manual are
not accompanied by the registered trademark or trademark
symbols (® and ™).
Notice
NO RIGHTS OR LICENSES, EXPRESS OR IMPLIED,
ARE GRANTED TO USE THIRD-PARTY DEVICES IN
COMBINATION WITH THESE PRODUCTS IN A WIRELESS
MESH NETWORK, OR TO USE THIRDPARTY SERVICES
TO ACCESS, MONITOR OR CONTROL THESE PRODUCTS
IN A WIRELESS MESH NETWORK VIA THE INTERNET OR
ANOTHER EXTERNAL WIDE AREA NETWORK.
Patent Marking
Covered by one or more claims of patents: http://sipcollc.
com/patent-list/ and http://intusiq.com/patent-list/.
QR code
The product has a QR Code pasted for efficient plant
maintenance work and asset information management.
It enables confirming the specifications of purchased products
and user’s manuals.
For more details, please refer to the following URL.
https://www.yokogawa.com/qr-code
QR Code is a registered trademark of DENSO WAVE
INCORPORATED.
Safety Precautions
• This instrument conforms to IEC/CSA/UL 61010,
overvoltage category I, Pollution degree 2, Measurement
category O (other)(Excluding area suffix code: K).
Measurement category O products are for measuring circuits
that are not directly connected to the main power supply.
• The general safety precautions described here must be
observed during all phases of operation. If the GX70SM
is used in a manner not described in this manual, the
GX70SM safety features may be impaired. Yokogawa
Electric Corporation assumes no liability for the customer’s
failure to comply with these requirements.
• The GX70SM is designed for indoor use.
Model GX70SM
Wireless Input Unit
First Step Guide
(Notes about Using This Product)
IM 04L57B01-02EN
Userʼs
Manual
IM 04L57B01-02EN
3rd Edition

2IM 04L57B01-02EN
Precautions Related to the Protection,
Safety, and Alteration of the Product
• Improper handling or use can lead to injury to the user or
damage to the instrument. This symbol appears on the
instrument to indicate that the user must refer to the user’s
manual for special instructions. The same symbol appears
in the corresponding place in the user’s manual to identify
those instructions. In the manual, the symbol is used in
conjunction with the word “WARNING” or “CAUTION.”
“Handle with care.” To avoid injury and damage to the instrument,
the operator must refer to the explanation in the manual.
Functional ground terminal (do not use this terminal
as a protective ground terminal.)
Direct current
• For the protection and safe use of the product and the
system in which this product is incorporated, be sure to
follow the instructions and precautions on safety that are
stated in this manual whenever you handle the product.
Take special note that if you handle the product in a
manner that violates these instructions, the protection
functionality of the product may be damaged or impaired.
In such cases, Yokogawa does not guarantee the quality,
performance, function, and safety of product.
• When installing protection and/or safety circuits such as
lightning protection devices and equipment for the product
and control system or designing or installing separate
protection and/or safety circuits for fool-proof design and
fail-safe design of the processes and lines that use the
product and the control system, the user should implement
these using additional devices and equipment.
• If you are replacing parts or consumable items of the
product, make sure to use parts specified by Yokogawa.
• This product is not designed or manufactured to be used
in critical applications that directly affect or threaten human
lives. Such applications include nuclear power equipment,
devices using radioactivity, railway facilities, aviation
equipment, air navigation facilities, aviation facilities, and
medical equipment. If so used, it is the user’s responsibility
to include in the system additional equipment and devices
that ensure personnel safety.
• Do not modify this product.
Notes on 920 MHz Wireless
Communication
• 920 MHz wireless communication can be used only in the US
(Area suffix code: A) or Republic of Korea (Area suffix code: K).
• Only US FCC standards and UL standards are supported.
(Area suffix code: A)
• Only Korea KC mark standards are supported.(Area suffix code: K)
• This product has obtained FCC certification or KC mark
conformity. As such, the following acts may be punishable
by law.
• Disassembling or altering the product
• Removing the certification label
• Using an antenna other than the specified option
• Communication may not be possible in the following
locations due to radio signal reflection.
• Where strong magnetic field, static electricity, or radio
interference occurs
• Rooms with metallic walls (including concrete containing
metal reinforcement material), inside cabinets, etc.
• If another wireless device using the same radio frequency
band as this product is present in the communication area
of this product, data rate degradation or communication
errors may occur, preventing normal communication.
• Because this product uses radio signals, bear in mind that
communication may be intercepted by third parties.
• This equipment complies with FCC radiation exposure limits set
forth for an uncontrolled environment and meets the FCC radio
frequency (RF) Exposure Guidelines.
This equipment has very low levels of RF energy that is deemed
to comply without testing of specific absorption rate(SAR).
• Communication errors can occur when wireless
communication is temporarily interrupted due to
environmental factors such as radio interference.
• When several GX70SMs perform wireless communication
with a single coordinator, there is a slight possibility that
data loss may occur due to collision of data transmitted
simultaneously from the GX70SMs to the coordinator.
In addition, communication errors may occur due to
operating environment conditions such as electromagnetic
interference from other devices.
● DoNotOperateinanExplosiveAtmosphere
Donotoperatetheinstrumentinthepresenceofam-
mablegas,vapors,orcombustibledust.Operation
in such an environment constitutes a safety hazard.
Prolonged use in a highly dense corrosive gas (H2S,
SOx,etc.)willcauseamalfunction.
● DoNotRemoveCovers
ThecovershouldberemovedbyYokogawa’squalied
personnel only.
● DamagetotheProtection
Operatingtheinstrumentinamannernotdescribedin
this manual may damage the instrument’s protection.
● InstallationandWiring
• To prevent electric shock, do not apply voltages that
exceedtheratingstotheinputterminals.
• Make sure to use appropriate wires, and torque. To
prevent electric shock due to damage, prevent strong
tension from being applied to the cords.
● Using920MHzwirelesscommunication
•Donotinstalloruseinsideaircraftsorhospitalsorin
areas where the use of wireless devices is prohibited.
•Donotinstallorusenearautomaticdoors,re
alarms, and other automatically controlled equip-
ment.
Theradiosignalsfromthisproductmayaectthe
equipment and may cause a malfunction.
•Donotinstallorusenearcardiacpacemakersor
electronic devices that involve highly accurate con-
trol or minute signals.
Doingsomaycausethemtomalfunction.
•Donotusetheproductinmedicalequipmentorother
applications that require high level of safety or in
systems (e.g., trunk line communication equipment,
computersystems)thatrequireextremelyhighreli-
ability.
Malfunction or failure may cause life-threatening ac-
cidents or great social disruption.
This instrument is a Class A product.
Operation of this instrument in a residential area may cause
radio interference, in which case the user is required to take
appropriate measures to correct the interference.
해당 무선설비는 전파혼신 가능성이 있으므로 인명안전과
관련된 서비스는 할 수 없습니다
A 급 기기 (업무용 방송통신기자재)
이 기기는 업무용(A 급) 전자파적합기기로서 판매자 또는
사용자는 이 점을 주의하시기 바라며, 가정외의 지역에서
사용하는 것을 목적으로 합니다.

3
IM 04L57B01-02EN
■ExemptionfromResponsibility
• YOKOGAWA makes no warranties regarding the product
except those stated in the WARRANTY that is provided
separately.
• YOKOGAWA assumes no liability to any party for any loss
or damage, direct or indirect, caused by the user or any
unpredictable defect of the product.
■ProductDisposal
The instrument should be disposed of in accordance with
local and national legislation/regulations.
■HowtoDisposetheBatteries
Dispose of the batteries according to the rules of your local
government.
Handling Precautions
• Use care when cleaning this instrument, especially its
plastic parts. Use a soft dry cloth. Do not use organic
solvents, such as benzene or thinner, or other cleansers.
They may cause discoloring and deformation.
• Keep electrically charged objects away from the signal
terminals. Doing so may damage the GX70SM.
• Do not apply volatile chemicals to the GX70SM. Do not
allow rubber and vinyl products to remain in contact with
the GX70SM for long periods of time. Doing so may
damage the GX70SM.
• If you are not using the product for a long time, be sure to
remove the batteries and store them properly.
• If there are any symptoms of trouble such as strange odors
or smoke coming from the product, immediately remove
the batteries.
Then, contact your nearest YOKOGAWA dealer.
Checking the Package Contents
After receiving the product and opening the package, check
the items described below. If the wrong items have been
delivered, if items are missing, or if there is a problem with the
appearance of the items, contact your nearest YOKOGAWA
dealer.
Check that the product that you received is what you ordered
by referring to the model name and suffix code given on the
nameplate on the GX70SM.
No. (Instrument number)
When contacting the dealer from which you purchased the
instrument, please give them the instrument number. The
number is inscribed on the nameplate.
MODELandSUFFIXCodes
GX70SM
Model SuffixCode Optional
Code
Description
GX70SM Wireless Input Unit
Channels -2 2 channels
Type -L0 Universal input, Scanner type
(isolated between channels)
- N Always N
Terminal type -C Clamp terminal
Area A For US, FCC standards are
supported
K For Republic of Korea,
KC mark are supported
Optional features /RH Built-in humidity sensor, 1
channel
Standard Accessories
The instrument is shipped with the following accessories.
Make sure that all accessories are present and undamaged.
* Batteries (CR123A) are not included. Please obtain
them separately (recommended battery manufacturer:
Panasonic).
No. Name Part Number/Model Qty. Notes
1 Manual IM 04L57B01-02EN 1 This manual.
OptionalAccessories(Soldseparately)
Name Part Number/Model Minimum.
Q’ty
Notes
Sleeve antenna A1061ER 1 indoor use
Roof top antenna A1062ER 1 indoor/outdoor
use, cable
length: 2.5 m
Input terminal A2226JT 1
GX70SM Style Number, Release Number,
and Firmware Version Number
Style number: The GX70SM hardware ID number. This
number is written on the nameplate (H
column).
Release number: The GX70SM firmware ID number. This
number is written on the nameplate (S
column). This number matches with the
integer part of the firmware version number.
Example: If the firmware version number is 1.01, the release
number is 1.
Firmware version number:
You can check this number on the Wireless
Input Unit Configurater.
For the procedure, see the User’s Manual
(IM 04L57B01-01EN).
Firmware Version of Connectable Coordinator and
Router (Repeater) Wireless Modules
Firmware version: v 4.2.0 and later
Note) If the firmware version of the coordinator or router
(repeater) wireless module is not compatible with the
wireless input unit, you need to update it.
Download it from the following website.
http://www.smartdacplus.com/software/en/
Conventions Used in This Manual
• This manual covers information regarding GX70SMs
whose display language is English.
The notes and cautions in this manual are indicated using the
following symbols.
Improper handling or use can lead to injury to the user or
damage to the instrument. This symbol appears on the
instrument to indicate that the user must refer to the user’s
manual for special instructions. The same symbol appears in
the corresponding place in the user’s manual to identify those
instructions. In the manual, the symbol is used in conjunction
with the word “WARNING” or “CAUTION.”
WARNING
Calls attention to actions or conditions that could cause
serious or fatal injury to the user, and precautions that can be
taken to prevent such occurrences.

4IM 04L57B01-02EN
CAUTION
Calls attention to actions or conditions that could cause light
injury to the user or cause damage to the instrument or user’s
data, and precautions that can be taken to prevent such
occurrences.
Note
Calls attention to information that is important for the proper
operation of the instrument.
OverviewoftheWirelessInputUnit
The GX70SM is a compact, battery-driven analog input unit
that uses 920 MHz specified low power radio.
Because it is battery-driven, it can collect data in a variety of
locations.
It connects to a SMARTDAC+ GX20, GP20, or GM10
coordinator over a multi-hop wireless link, and allows data
collection and status display on the GX20/GP20/GM10.
GX70SM
Master
(GX/GP/GM)
GX70SM
Wireless Netwok
(PAN)
OperatingProcedure
This section describes how to connect the GX70SM to a GX/
GP/GM, collect data, and display the status.
For details, see the Wireless Input Unit User’s Manual (IM
04L57B01-01EN).
For details on the configuration of the GX/GP/GM
(coordinator), see the 920 MHz Wireless Communication
User’s Manual (IM 04L51B01-41EN).
Items to Prepare
Item Description
1. GX70SM Wireless Input Unit
2. GX20/GP20/GM10 Master (Coordinator)
3. PC For configuring the wireless input unit and
coordinator
* Microsoft .Net Framework 4.6.1 or later is
required.
4. USB cable Connector type: mini B
* With a power supply function.
5. Wireless Input Unit
Configurator
Setting software for wireless input unit
6. Maintenance console Setting software for master (Coordinator)
(made by Oki Electric Industry Co., Ltd.)
Procedure
1 From the Wireless Input Unit Configurator, configure the
environment (COM port, password, etc.) for connecting to the
GX70SM, and configure the wireless and input settings of the
wireless input unit.
2 From the maintenance console, configure the coordinator
settings of the GX/GP/GM (coordinator).
3 On the GX/GP/GM, under Basic configuration of Communication
(Serial) settings, set the receiver function to Wireless Input Unit.
4 On the GX/GP/GM, obtain the connection information of the
wireless input unit.
The assignable GX70SM is displayed.
5 On the GX/GP/GM, reconfigure the wireless input unit.
The GX70SM is automatically assigned.
6 Using the Wireless Input Unit Configurator of the GX/GP/GM, set
the span, alarm, display, and the like of the data to obtain from
the GX70SM.
7 The GX/GP/GM is now ready to collect data and display the
status.
Communication (serial)
settings
• Basic settings
Wireless input unit
reconfiguration
• GX70SM identification
• Automatic assignment of
the GX70SM
• Enviroment settings
• Wireless settings
• Input settings
Coordinator configu-
ration of the coordinator
Wireless
connecting
1
PC
Wireless Input Unit Configurator Maintenance console
GX/GP/GM
GX70SM PC
2
3
4
5
Wireless input unit settings
• Span
• Alarm
• Display setting, etc
Obtain the wireless input
unit connection information
Operation of GX/GP/GM (Master)
Operation of Wireless Input Unit
Configurator
Operation of Maintenance console
6
7
USB USB
Note: Before configuration, the GX70SM
must be set to configuration mode
(with a switch on the unit).
Set the mode back to measurement
mode after configuration.
Data collection,
status display
Component Names
Input terminal
Status LED Magnet
Hole for hooking
USB2.0 connector
(mini-B)
Antenna connector
RearFront
Right Side humidity sensor (/RH)
Test switch
Reboot switch
Mode setting switch
Holes for attaching the band used to prevent
the cover from falling

5
IM 04L57B01-02EN
Installation
Installation Location
Install the GX70SM indoors in an environment that
meets the following conditions:
• Ambient temperature range between -20 to 70°C.
• Ambient humidity between 0 to 90%RH.
No condensation should be present.
Note
Condensation may form when moving the GX70SM from
a low temperature or humidity environment to a high
temperature or humidity environment, or when there is a
sudden change in temperature. Temperature or humidity
changes may also result in thermocouple measurement
, humidity measurement errors. In these kinds of
circumstances, wait for at least an hour before using the
GX70SM, to acclimate it to the surrounding environment.
• Minimal mechanical vibrations
Install the GX70SM in a location that has minimal
mechanical vibrations. Installing the GX70SM in a location
that is subject to large levels of mechanical vibration will
not only put added stress on its components, it may also
impede ordinary measurement.
Do Not Install the Instrument in the Following Places
• Outdoors
• In direct sunlight or near heat sources
Install the GX/GP in a place that is near room temperature
(23°C) and that is not subject to large temperature fluctuations.
Placing the GX70SM in direct sunlight or near heat sources
can cause adverse effects on the internal circuitry.
• Where an excessive amount of soot, steam, moisture,
dust, or corrosive gases are present Soot, steam,
moisture, dust, and corrosive gases will adversely affect
the GX70SM. Avoid installing the GX70SM in such
locations.
• Near strong magnetic field sources
Do not bring instruments that produce electromagnetic
fields close to the GX70SM. Operating the GX70SM near
strong magnetic fields can cause measurement errors.
Installation Procedure
The GX70SM can be used on a desktop or floor, mounted on
a wall, affixed with the magnet, or hooked on a wall.
Note
Be careful not to bring a magnet close to electronic
devices because it may hinder proper operation or cause a
malfunction.
Onadesktoporfloor Mounted on a wall
The GX70SM can be placed
on a desk, floor, or the like as
shown in the following figure.
Mount the GX70SM on a wall
using screws.
Screw size: M3, Thread: 12
mm or more
Torque: 0.6 to 0.7 N•m
Screw
Hooked on a wall Attach with the magnet
Put a screw into a wall for
hooking the GX70SM.
Hook the GX70SM on the
screw.
The length below the neck of the
screw must be at least 10 mm.
Attach the GX70SM with the
magnet to a metal surface.
Attach to a metal object with
an installation surface of at
least 70 mm × 70 mm.
Magnet
ExternalDimensionsUnit:mm(approx.
inch)
90(3.54)
32(1.26)
9.55
(0.38)
90(3.54)
Unit: mm (approx. inch)
Unless otherwise specified, tolerance is ±3%
(however, tolerance is ±0.3 mm when below 10 mm).
* For the dimensions when the external antenna is installed,
see “Dimensions” (SD 04L57B01-01EN).
WallMountDimensions
2-M3 tap holes
18.5
0.73
70(2.76)
61±2(2.4±0.08)
5
(0.2)
70(2.76)
Mounted on a wall
Wall to mount on

6IM 04L57B01-02EN
Recommended positions
of the hooks
35
(1.38)
70(2.76)
17.9
(0.70)
44(1.73)
Hooked on a wall
At least 10 mm below the
neck of the screw
3.5~4.0mm(0.14 to 0.16)
wall
surface
Wall to
mount on
Wiring
● Applyingastrongtensiontotheinputsignalcables
connected to the GX70SM may damage the cables or
the GX70SM terminals.
Make sure that pulling force is not directly applied to
the terminals of this product.
● Topreventre,usesignalcableswithatemperature
rating of 70°C or more.
● Donotapplyvoltagesthatexceedthefollowingval-
uestotheinputterminals.Doingsomaydamagethe
instrument.
• Allowable input voltage:
±10VDCforthermocouple,DCvoltage(200mVrange
orlower),RTD,DI(contactinput)
±30VDCforvoltage(2Vrangeorhigher),DI(level)
● ThisinstrumentconformstoovervoltagecategoryI,
Pollutiondegree2,MeasurementcategoryO.
Precautions to Be Taken While Wiring
Take the following precautions when wiring the input signal
cables.
● We recommend the following wire.
Cross-sectional
area
0.08 mm2to 2.08 mm2(AWG28 to 14)
Stripped wire
length
5 to 6 mm
● Take measures to prevent noise from entering the
measurement circuit.
• Move the measurement circuit away from the power
cable (power circuit) and ground circuit.
• Ideally, the object being measured should not generate
noise. However, if this is unavoidable, isolate the
measurement circuit from the object.
Also, ground the object being measured.
• Shielded wires should be used to minimize the noise
caused by electrostatic induction. Connect the shield to the
ground terminal of the GX70SM as necessary (make sure
you are not grounding at two points).
• To minimize noise caused by electromagnetic induction,
twist the measurement circuit wires at short, equal
intervals.
• Make sure to earth ground the functional ground terminal
through minimum resistance.
● When using internal reference junction compensation on
the thermocouple input, take measures to stabilize the
temperature at the input terminal.
• Do not use thick wires which may cause large heat
dissipation (we recommend a cross sectional area of 0.5
mm2or less).
• Make sure that the ambient temperature remains
reasonably stable. Large temperature fluctuations can
occur if a nearby fan turns on or off.
● Connecting the input wires in parallel with other devices
can cause signal degradation, affecting all connected
devices. If you need to make a parallel connection, then
• Turn the burnout detection function off.
• Ground the instruments to the same point.
• Do not turn ON or OFF another instrument during
operation. This can have adverse effects on the other
instruments.
• RTDs cannot be wired in parallel.
Installing and Removing Batteries
1. Remove the battery case cover by sliding the cover while
pressing on the A in the following figure.
1
2
A
2. Insert two batteries (CR123A) into the battery case, or
remove them.
(Batteries are not included. Please obtain them
separately.)
* Pay attention to the polarities and static electricity when
inserting batteries.
* Electric double-layer capacitors are used in this
instrument. When batteries are removed, the instrument
continues to operate until the energy charged in the
capacitors are used up.
3. Slide and attach the battery case cover.
AttachingandDetachingtheTerminal
Block
The terminal block can be attached and detached. This
makes it easy to wire the terminal block.
1. Loosen the terminal block attachment screws.
2. Pull out the terminal block.
3. When you are attaching the terminal block, tighten the
attachment screws.
Recommended torque for tightening the terminal block
attachment screws: 0.1 N•m
Terminal block attachment screws

7
IM 04L57B01-02EN
Wiring Procedure
A label indicating the terminal arrangement is affixed to the
input terminal.
1. First, loosen the screw terminal using a flat-blade
screwdriver.
2. Insert a wire in the connection port, and tighten the screw
terminal.
Recommended torque for tightening clamp terminal:
Approx. 0.2 N•m
Wire
(Stripped wire)
Flat-blade
screwdriver
Connection port
Note
With a clamp terminal, if you use a single wire whose
diameter is 0.3 mm or less, you may not be able to clamp
the wire securely to the terminal. Take measures to securely
clamp the wire such as by folding the conductor section that
will be connected to the clamp terminal in half.
Wiring to a input terminal
TerminalDiagram
CH1 CH2
Terminal Arrangement
CH1 CH2
Symbol A B (+) b (–) A B (+) b (–)
The resistance RTD A terminal of each channel is connected
internally in the device and is not isolated between channels.
WiringDiagram
DCvoltage/DIinput TC input
+−
RTDinput DCcurrentinput
(withanexternalshunt
resistor)
A B b
+−
Functional ground terminal
Functional
ground terminal
Note
Notes on the Functional Ground Terminal
• To reduce noise, use a shielded cable for wiring. Connect
the shield to the functional ground terminal or the ground
terminal of the GX70SM.
• Do not wire the protective grounding cord to the functional
ground terminal.
Connecting to the USB Port
A USB2.0 port (mini B type).
Connect to a PC using a USB cable.1
Use this port to configure the input and
wireless settings of the GX70SM, perform
maintenance, and so on with the Wireless
Input Unit Configurator.
1 When configuring the GX70SM, use a powered USB
cable.
ConnectinganExternalAntenna
Sleeve Antenna
While turning the antenna to the
right, attach the antenna to the
antenna insertion port.
Antenna insertion port
Can be bent.
The antenna direction can be
changed freely.
a
b
Roof Top Antenna
Antenna insertion port
a
b
While turning the antenna connector
to the right, attach the antenna to the
antenna insertion port.
* Use a torque wrench (wrench width 5/16
inches, tightening torque 0.56 to 0.90 N•m).

8IM 04L57B01-02EN
Note
• To bring out the full performance of the antenna, install it
on top of a metal rectangle board that is at least 10 x 20
cm long.
• When installing the antenna, make sure no foreign matter
gets caught between the bottom side of the antenna and
the installation plane.
• Do not bend the antenna cable more than the allowable
bend radius of 3 cm.
• When installing the antenna in an area subject to
lightning, be sure to install the antenna at a position safe
from lightning and at a position lower than the height of
other cases.
Wireless Input Unit Configurator
For Installing, see Wireless Input Unit User's Manual (IM
04L57B01-01EN) (Electronic Manuals)
Required Microsoft .NET Framework 4.6.1 or more, to
connect and operate the wireless input unit.
LEDIndication
Configuration modes, data transmission, and battery status
are indicated with green and red LEDs.
RedGreen
Status LED
Configuration mode Green and red blinking in sync at 2
second intervals
Configuration change and
during calibration
Green and red blinking quickly in
sync
During
measurement
or data
transmission
When network
is normal
Green blinking (about 0.2 second
intervals), red off
Not joined the
network
Red blinking (about 0.2 second
intervals), green off
Low battery warning Green lit (0.1 seconds), all off (1.9
seconds)
Red lit (0.1 seconds), all off (1.9
seconds)
The above sequence is repeated
twice, and then the LEDs are off for
10 seconds.
Input error Red lit for 0.1 seconds at about 5
second intervals, green off
Mode setting error 1 Repeats the sequence of green and
red lit in sync (0.1 seconds) and all
off (0.9 seconds) three times, turns
off for 2 seconds, and repeats the
entire sequence.
1 For example, configuring in a mode other than measurement mode
when there is no USB connection.
SettingtheOperationMode
The GX70SM has two operation modes: measurement and
configuration. Change the operation mode accordingly.
Operationmode Description
Measurement mode Use this mode to make
measurements.
Setting mode Use this mode to configure,
retrieve logging data, perform
maintenance, and so on.
1. Slide and remove the battery case cover. (See “Installing
and Removing Batteries.”)
Reboot switch
Operation mode switch
Supply power
through USB
(when changed to
configuration mode)
2. Set the operation mode switch to measurement or
configuration.
Note: When switching to configuration mode, supply power
through USB.
Operationmodeswitch
O
N
1
2
ON
OFF
OperationMode SW1
Measurement mode OFF
Setting mode ON
Wireless Function 1SW2
On OFF
Off ON
1 You can use the GX70SM as a standalone
data logging device by setting the wireless
function to off.
3. Press the reboot switch.
4. The GX70SM changes to the specified operation mode.
Table of contents
Other YOKOGAWA I/O System manuals
Popular I/O System manuals by other brands

Measurement Computing
Measurement Computing PCI-DIO24 user guide

Artistic License
Artistic License vSplit mono xlr8-8 user guide

M-system
M-system R7F4DC-DAC16C-H instruction manual

M-system
M-system 6BSN instruction manual

Mitsubishi
Mitsubishi FX3U-16CCL-M installation manual

NCR
NCR 7772-K038 Kit instructions

Tektronix
Tektronix VX4801 user manual

Crestron
Crestron DMB-4K-CPU-128 Installation guides

Allen-Bradley
Allen-Bradley ArmorBlock-LP 1792-IB16LP installation instructions

Rockwell Automation
Rockwell Automation Allen-Bradley GuardPLC 1753-IB20XOB8 installation instructions

GST
GST I-9301 quick start guide

DOLD
DOLD BG 5914.08 0 Series operating instructions