ZIEHL-ABEGG Acontrol PTE-6AHQ User manual

Acontrol
PTE-6AHQ / PTE-10AHQ
Air-conditioning controller for single phase fans in agriculture
Operating Instructions
Keep for reference!
Software version: D1337A from Version 1.04
L-BAL-E044-GB 1911 Index 003 Part.-No.
english

Content
1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Explanations of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Requirements placed on the personnel / due diligence . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Start-up and during operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6 Work on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.7 Modifications / interventions in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.8 Operator’s obligation of diligence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.9 Employment of external personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Minimum space requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.3 Outdoor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.4 Installation location for agriculture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.5 Temperature influences during commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2 EMC-compatible installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2.1 Motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2.2 Control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2.3 Harmonics current for devices ≤ 16 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Mains connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4 Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4.1 Running noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.5 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.6 Sensor connection (E1, E2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.7 Control output 0 - 10 V (A2, A3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.8 Relay outputs (K1, K2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.9 Potential at control voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Controls and Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.1 Main switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.2 Multipurpose LC display and keyboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.3 Menu operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.4 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7 The Installation menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7.1 Entrance to the installation menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ
L-BAL-E044-GB 1911 Index 003 Part.-No.
2/36

7.2 Installation - Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2.1 Minimum speed cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2.2 Setting Startvoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.3 Installation - Shutter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.4 Installation - Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.5 Installation – Setpoint derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.6 Installation – Sensor adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.7 IO Setup Assignment of inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.1 Prerequisites for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9 Settings for operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9.1 Menu overview for operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9.2 Quickinfo, setpoint, min. and max. compartment temperatures . . . . . . . . . . . . . . . . . . 19
9.3 Setting Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.3.1 For the regulation of the fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.3.2 For throttle shutter control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.3.3 Setpoint derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.4 Temperature monitoring settings (Alarm functions) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.5 Settings for heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9.5.1 Heating control by relay (two-point mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
9.5.1.1 Example for two-position control independent of the ventilation nominal
value (factory setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
9.5.1.2 Example for two-position control independent of the ventilation nominal
value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
9.5.2 Controlling the heating via the 0...10 V signal (linear) . . . . . . . . . . . . . . . . . . . . . . 26
10 Menu table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11 Malfunctions / trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
12 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
12.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
12.1.1 Performance reduction during elevated ambient temperatures . . . . . . . . . . . . . . . . 31
12.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
12.3 Dimensions [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12.4 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
12.5 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
12.6 Service information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ
L-BAL-E044-GB 1911 Index 003 Part.-No.
3/36

1 General notes
Compliance with the following instructions is mandatory to ensure the functionality and safety of the
product. If the following instructions given especially but not limited for general safety, transport,
storage, mounting, operating conditions, start-up, maintenance, repair, cleaning and disposal / recy-
cling are not observed, the product may not operate safely and may cause a hazard to the life and
limb of users and third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material
defect liability rights and to the liability of the buyer for the product that has become unsafe due to the
deviation from the specifications.
1.1 Structure of the operating instructions
Before installation and start-up, read this manual carefully to ensure correct use!
We emphasize that these operating instructions apply to specific units only, and are in no way valid for
the complete system!
Use these operating instructions to work safely with and on the device. They contain safety instruc-
tions that must be complied with as well as information that is required for failure-free operation of the
device.
Keep these operating instructions together with the device. It must be ensured that all persons that
are to work on the device can refer to the operating instructions at any time.
Keep the operating instructions for continued use. They must be passed-on to all successive owners,
users and final customers.
1.2 Target group
The operating instructions address persons entrusted with planning, installation, commissioning and
maintenance and servicing and who have the corresponding qualifications and skills for their job.
1.3 Exclusion of liability
Concurrence between the contents of these operating instructions and the described hardware and
software in the device has been examined. It is still possible that non-compliances exist; no guarantee
is assumed for complete conformity. To allow for future developments, construction methods and
technical data given are subject to alteration. We do not accept any liability for possible errors or
omissions in the information contained in data, illustrations or drawings provided.
ZIEHL-ABEGG SE is not liable for damage due to misuse, incorrect use, improper use or as a
consequence of unauthorized repairs or modifications.
1.4 Copyright
These operating instructions contain copyright protected information. The operating instructions may
be neither completely nor partially photocopied, reproduced, translated or put on data medium without
previous explicit consent from ZIEHL-ABEGG SE. Infringements are liable for damages. All rights
reserved, including those that arise through patent issue or registration on a utility model.
2 Safety instructions
This chapter contains instructions to prevent personal injury and property damage. These instructions
do not lay claim to completeness. In case of questions and problems, please consult our company
technicians.
2.1 Intended use
The equipment is to be used solely for the purposes specified and confirmed in the order.
Any other use above and beyond this is considered not for the intended purpose unless agreed
otherwise by contract. The manufacturer will not be liable for any damage resulting from this. The
individual or company using it bears the sole risk.
Reading these operating instructions and complying with all contained instructions - especially the
safety notifications contained therein - are considered part of intended use. To consider is also the
manual of attached components. Not the manufacturer, rather the operator of the device is liable for
any personal harm or material damage arising from non-intended use!
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ General notes
L-BAL-E044-GB 1911 Index 003 Part.-No.
4/36

2.2 Explanations of symbols
Safety instructions are highlighted with warning triangles and are depicted according to the degree of
hazard as follows.
Attention!
General hazardous area. Death or severe injury or significant property damage can occur if the
corresponding precautions are not taken!
Danger due to electric current
Danger by dangerous, electric voltage! Death or severe injury can occur if the corresponding
precautions are not taken!
Information
Important additional information and advice for user.
2.3 Product safety
The device conforms to the state of the art at the time of delivery and is fundamentally considered to
be reliable. The device and its accessories must only be used in a flawless condition and installed and
operated in compliance with the assembly instructions and/or operating instructions. Operating out-
side the device's technical specifications (see name plate and attachment / technical data) can lead to
a defect in the device and additional damage!
Information
In the case of a malfunction or a failure of the equipment check all functions with alarms in order to
prevent injury to persons or property. Note possibility of back-up operation. If used in intensive animal
environments, any malfunctions in the air supply must be detected as soon as possible to prevent the
development of a life-threatening situation for the animals. The design and installation of the system
must comply with local regulations and directives. In Germany these include DIN VDE 0100, the
animal protection and the keeping of working animals ordinance and the pig-keeping ordinance etc.
Also note the instructions of AEL, DLG, VdS.
2.4 Requirements placed on the personnel / due diligence
Persons entrusted with the planning, installation, commissioning and maintenance and servicing in
connection with the frequency inverter must have the corresponding qualifications and skills for these
jobs.
In addition, they must be knowledgeable about the safety regulations, EU/EC directives, rules for the
prevention of accidents and the corresponding national as well as regional and in-house regulations.
Personnel to be trained or instructed and apprentices are only permitted to work on the device under
the supervision of an experienced person. This also applies to personnel undergoing general training.
Comply with the legal minimum age.
2.5 Start-up and during operation
Attention!
•During commissioning, unexpected and hazardous conditions can arise in the entire installation due
to defective adjustments, defective components or incorrect electrical connections. Remove all
persons and objects from the hazardous area.
•During operation, the device must be closed or installed in a control cabinet. Fuses may only be
replaced by new ones and must not be repaired or bypassed. The data for the maximum line fuse
are to be considered absolutely (see Technical data). Use only fuses specified in schematic
diagrams.
•Any faults detected in the electric system/modules/operating equipment must be corrected
immediately. If these faults are not corrected, the device/system is potentially very dangerous. The
device/system must therefore not be operated when it is faulty.
•Pay attention to smooth, low vibration running of the motor/fan, the appropriate instructions in the
drive documentation must be observed!
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Safety instructions
L-BAL-E044-GB 1911 Index 003 Part.-No.
5/36

2.6 Work on the device
Information
Mounting, electrical connection, and start-up operation may only be carried out by an electrical
specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)!
Danger due to electric current
It is generally forbidden to carry out work on electrical live parts. Protection class of the device when
open is IP00! It is possible to touch hazardous voltages directly.
The safe isolation from the supply must be checked using a two-pole voltage detector.
Attention!
Even after switching off, dangerous temperatures can still occur in and on the device.
Attention!
Automatically restart after a power failure or mains disconnection!
2.7 Modifications / interventions in the device
Attention!
For reasons of safety, no unauthorized interventions or modifications may be made on the device. All
planned modifications must be authorized by the manufacturer in writing.
Use only genuine spare parts / genuine wearing parts / genuine accessories from ZIEHL-ABEGG.Th-
ese parts were specifically designed for the device. There is no guarantee that parts from non-original
sources are designed and manufactured in correspondence with load and safety requirements.
Parts and optional equipment not supplied by ZIEHL-ABEGG are not approved by ZIEHL-ABEGG for
use.
2.8 Operator’s obligation of diligence
•The contractor or owner must also ensure that the electric systems and equipment are operated
and maintained in accordance with electro-technical regulations.
•The owner is obliged to ensure that the device is operated in perfect working order only.
•The device may only be used as intended.
•You must periodically examine the safety equipment for their properly functioning condition.
•The assembly instructions and/or operating instructions are always readily available at the location
where the device is being used, are complete and are in legible condition.
•These persons are regularly instructed in all applicable questions regarding occupational safety
and environmental protection and are knowledgeable regarding the assembly instructions and/or
operating instructions and, especially, are familiar with the safety instructions contained therein.
•All safety and warning notices attached to the device are never removed and remain legible.
2.9 Employment of external personnel
Maintenance and service work are frequently carried out by external employees who often do not
recognize the specific situations and the thus resulting dangers.These persons must be comprehen-
sively informed about the hazards in their area of activity.
You must monitor their working methods in order to intervene in good time if necessary.
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Safety instructions
L-BAL-E044-GB 1911 Index 003 Part.-No.
6/36

3 Product overview
3.1 Application
The controller described is used for continuous speed adjustment on variable voltage 1~ motors used
to drive ventilators or pumps.
3.2 Maintenance
The device must be checked for soiling and, if necessary, cleaned in periodic intervals.
3.3 Transport
•The device is packed ex factory to suit the transport method previously agreed.
•Always use the original packaging materials when transporting the device.
•Avoid shocks and impacts to the device during the transport.
•During manual handling the human lifting and carrying restrictions must be observed and adhered
to.
3.4 Storage
•The device must be stored in its original packaging in a dry and weather-proof room.
•Avoid exposure to extreme heat and cold.
•Avoid over-long storage periods (we recommend a maximum of one year).
3.5 Disposal / recycling
Disposal must be carried out professionally and in an environmentally friendly way in accordance with
the respective national legal stipulations.
"Separate the materials by type and in an environmentally friendly way.
"If necessary, commission a specialist company with the waste disposal.
4 Mounting
4.1 General notes
Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect
in the device due to assembly errors or environmental influences:
•Before installation remove the device from the packing and check for any possible shipping
damage! Start-up is not allowed in the case of transport damage!
•At a weight greater than 25 kg for men / 10 kg for women, the device should be lifted out by two
persons (according to REFA). The values may differ from country to country.
•Wear safety shoes and gloves for handling!
•Assemble the device on a clean and stable base. Do not distort during assembly! Use the
appropriate mounting devices for proper installation of the unit!
•Do not mount equipment on vibrating base!
•When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock
loads. Any banging shut of doors that are integrated into these lightweight walls, can result in
extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
•Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
•The device should be installed in a location where it will not be disturbed, but at the same time can
be easily accessed!
•Depending on the housing model use supplied stoppers for cable inlets, cut off necessary cable
inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands. Any cable
ducts openings not used must be sealed!
•Care must be taken to avoid direct radiation from the sun!
•The device is designed for vertical installation (bottom cable inlet). A horizontal or reclined installa-
tion is only permissible after technical release of the manufacturer!
•Be sure to observe proper heat dissipation (see Technical data, heat dissipation).
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Product overview
L-BAL-E044-GB 1911 Index 003 Part.-No.
7/36

4.2 Minimum space requirement
In order to ensure sufficient ventilation of the device, clearance on all sides of at least 50 mm has to
be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance
applies to the installation of several devices next to each other.
When installing several devices on top of each other, the danger of reciprocal heating exists. This
layout is only then permissible when the air suctioned from the upper unit does not become warmer
than the permissible ambient temperature (see Technical data). I.e., a correspondingly larger clear-
ance or thermal shielding is required.
4.3 Outdoor installation
Outdoor installation is possible up to -20 °C when the controller supply is not switched off. Installation
must be protected from the effects of weather as much as possible, including protection from direct
sunlight!
4.4 Installation location for agriculture
When using for animal keeping, do not install the device directly in the stable but in a separate room
with a lower pollutant load. This helps to avoid damages caused by pollutant gases (e.g. ammonia
fumes, hydrogen sulphide fumes).
4.5 Temperature influences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by storing the
controller at room temperature!
5 Electrical installation
5.1 Safety precautions
Danger due to electric current
•Work on electric components may only be carried out by trained electricians or by persons
instructed in electricity under the supervision of an electrician in accordance with electrical
engineering regulations.
•The 5 electrical safety rules must be observed!
•It is forbidden to carry out work on electrically live parts.
•Cover neighbouring electrical equipment during installation work.
•Other measures may be necessary to achieve safe electrical isolation.
•A second person must always be present when working on energized parts or lines who
disconnects in case of emergency.
•Electrical equipment must be checked regularly: Loose connections are to be re-tightened and
damaged lines or cables must be replaced immediately.
•Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for
authorized persons using a key or special tool.
•Operating the device with the housing cover removed is prohibited because energized, exposed
parts are present inside the device. Disregarding this regulation can lead to severe personal injury.
•The required protective earth connection is established using screws between the housing parts in
metal terminal space covers and housing casings. Commissioning is only permissible after these
screws have been properly attached!
•The device owner is responsible for the EMC of the entire plant according to the locally applicable
standards.
•Metal screwed-connections are not permitted in plastic housing parts because there is no potential
equalization.
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Electrical installation
L-BAL-E044-GB 1911 Index 003 Part.-No.
8/36

•Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this Operating Instructions (see
connection diagram)!
5.2 EMC-compatible installation
5.2.1 Motor cable
The applicable standard for interference emissions is EN 61000-6-3. Compliance with this standard is
achieved through the use of an unscreened motor feed cable.
5.2.2 Control cables
Pay attention to sufficient distance from powerlines and motor wires to prevent interferences. The
control cable may not be longer than 30 m. Screened control cables must be used when the cable
length is longer than 20 m. When using a shielded cable connect the shielding to one side only, i.e.
only to the control unit with the protective ground (keep cable short and with as little inductance as
possible!).
5.2.3 Harmonics current for devices ≤ 16 A
According to EN 61000-3-2 these devices are to be classified as “professional” devices.
Connection to a low voltage supply (public networks) is allowed insofar as this has been clarified with
the respective energy supply company responsible.
Note: up to a maximum current of approx. 4 A, the limits are adhered to with no restrictions.
Exception for Germany: An energy provider follows the technical connection conditions of the
TAB2007, in which case the use of phase angle controlled devices up to a rating of 3.4 kVA per phase
is allowed.
5.3 Mains connection
The mains connection is made at the terminals: PE, L1 and N. In this regard, it is essential to ensure
that the mains voltage lies within the allowable tolerance specifications (see technical data and rating
plate affixed to the side).
Danger due to electric current
The mains voltage must comply with the DIN EN 50160 quality characteristics and the defined
standard voltages in IEC 60038!
5.4 Motor connection
The motor is connected at terminals U1 and U2. Several motors can be connected to the device.
Attention
The maximum total control current (specified for electronic voltage regulation) for all motors may not
exceed the device’s rated current.
If the maximum control current for electronic voltage regulation is not known, a supplementary 20 % of
the rated motor current must be allowed for.
When controlling motors from other manufacturers, the controllability and the maximum current for
electronic voltage regulation should be requested from the manufacturer.
Information
•It is recommended that a separate motor protection unit be foreseen for each fan.
•For motors with thermistors “TB” e.g. type S-ET10.
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Electrical installation
L-BAL-E044-GB 1911 Index 003 Part.-No.
9/36

5.4.1 Running noise
When controlling ventilators using electronic voltage regulators, motor noise can occur (due to the
system), which can be troublesome (Phase cutting series “P...”).
On fast running ventilators with a high level of air noise, this noise is relatively low. On slow running
ventilators with a low level of air noise, this noise may be dominant in the lower speed range due to
the occurrence of resonance.
For systems where noise is critical, we recommend using our Fcontrol series frequency converters
with integrated sinusoidal filter.
5.5 Motor protection
Attention!
Motor thermostats cannot be connected to these controller. I.e. a separate motor protection is
required. We cannot under any circumstances accept liability for damage to the motors which do not
have the required motor protection. It is recommended that every fan is equipped with a separate
motor protection unit e.g. type S-ET10 (see connection diagram)!
5.6 Sensor connection (E1, E2)
The device has 2 inputs for type TF.. temperature sensors (KTY):
•For Compartment temperature
–Sensor type TFR (Part.-No. 00089846) in scope of delivery
–Terminals “E1” / “GND”
•For the out door temperaure or separate sensor for shutter or heating
–Input factory setting deactivated
–Terminals “E2” / “GND”
–Sensor not in scope of delivery
Danger due to electric current
Never apply line voltage to analog inputs!
5.7 Control output 0 - 10 V (A2, A3)
The unit has two 0 - 10 V outputs:
•For ventilation shutter
–output 2 Terminals A2 / GND (I
max
10 mA).
–factory setting inverted (10 V..0 V) i.e. .: 10 V shutter CLOSED, 0 V shutter OPEN.
•For slave controller proportional modulation (factory setting) or with reprogramming for heating.
–output 3 Terminals A3 / GND (I
max
10 mA)
–factory setting not inverted
Information
It is not permissible to connect outputs of several devices to each other!
Inverting outputs and setting curve points possible (e.g. for not linear ouput) in IO Setup (see
installation menu).
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Electrical installation
L-BAL-E044-GB 1911 Index 003 Part.-No.
10/36

5.8 Relay outputs (K1, K2)
The controller has two relay outputs (contact rating see technical data):
•For Fault indication Relays K1
–Connection of the floating contacts to the terminals 11, 12, 14.
–For operation the relay is energized i.e. terminals “12” and “14” are bridged (factory setting not
inverted).
–At line fault, blown internal fuse, temperature fault the relay ist de-energized terminals “12” and
“11” bridged.
–The fault signal over the relay can be acknowledged with the
|
ESC
|
-key combination. In such a
way the error remains existing (e.g. sensor fault) comes after an adjustable time interval again a
message (factory setting alarm pause 60 min (see Alarm).
•For Heating Relays K2
–Connection of the floating contacts to the terminals 21, 22, 24.
–For heating “ON” relay energized i.e. terminals “22”, “24” bridged (factory setting not inverted).
Information
Inverting relay function in IO Setup possible.
5.9 Potential at control voltage connections
The connections for the control voltage (< 30 V) relate to the common GND potential (exception: relay
contacts are potential-free). There is a potential isolation between the connections for the control
voltage and the PE conductor. It must be ensured that the maximum external voltage at the con-
nections for the control voltage cannot exceed 30 V (between the “GND” and “PE” conductor
terminals). A connection to the PE conductor potential can be made if required; fit a bridge between
the “GND” terminal and the “PE” connection (terminal for shield).
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Electrical installation
L-BAL-E044-GB 1911 Index 003 Part.-No.
11/36

6 Controls and Menu
6.1 Main switch
0Controller off
Auto Continuous speed control
100 % Ventilators are operated directly from the mains with
no control.
Equipment fuse disabled!
6.2 Multipurpose LC display and keyboard
Overview display
1. Numeric display 5 digit
2. Alarm-Symbol (fault indication)
3. Fire symbol Heating is activated
4. Lowering function activ
5. Bargraph fan modulation
6. Text line 3 figures (display unit, etc.)
7. SH: Exhaust airshutter opening
8. S: active set value
PProgram key and open menu
Menu selection, reduce value
Menu selection, increase value
|
ESC
|
-key combination, Escape leave menu
▼
▲
▼ + ▲
In case of an alarm, the display overview changes together with the alarm message. It can be confirmed by pressing the “Esc”-
key shortcut (approx. 3 sec). I.e., the malfunction indication via the display and via the relay is switched off (see Alarm
functions).
S:25°C SH:99%
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Controls and Menu
L-BAL-E044-GB 1911 Index 003 Part.-No.
12/36

6.3 Menu operation
Selection of the menu group to the right through the
down key ▼, to the left through the up key ▲.
By pushing the P button, one reaches individual menu
items in the menu group (e.g., to go to nominal values).
One moves up and down within the menu group using
the arrow keys.
To make adjustments, press the P key after selecting the
menu item. If the previously set value starts to flash, it
can be adjusted with the ▼ + ▲ keys and then saved
with the P key.
To exit the menu without making any changes, use the
|
Esc
|
short-key, i.e., the originally set values remain.
One returns to the menu group using the
|
ESC
|
(▼ + ▲)
shortcut keys.
S:20.0° SH:94%
▼
▲Ventilation
▼
▲
P ↓
↑
▼+▲
|
Esc
|
P ↓
↑
▼+▲
|
Esc
|
Setpoint
Setpoint
▼ ▲ ▼ ▲
E2
Pband
6.4 Menu structure
The main menus:
|
Quick Info
|
,
|
ventilation
|
,
|
alarm
|
and
|
heating
|
, can be opened by briefly pressing the P-key.
S:20.0° SH:94%
▼
▲Ventilation
▼
▲Alarm
▼
▲Heating
▼
▲Installation
P
↓
↑
▼+▲
|
Esc
|
P
↓
↑
▼+▲
|
Esc
|
P
↓
↑
▼+▲
|
Esc
|
P
↓
↑
▼+▲
|
Esc
|
P*
5 sec
↓
↑
▼+▲
|
Esc
|
Setpoint Ventilation
and Quick Info
Ventilation Fan +
Shutter
Alarm Overtempera-
ture + Undertempera-
ture
Heating via relay or 0
- 10 V
Base setup
* You must keep the
|
P
|
-key pressed for approx. 5 seconds to protect the installation menu from
unintentional modifications.
7 The Installation menu
7.1 Entrance to the installation menu
Installation
Starting from the overview display, press the UP key
|
▼
|
four times until you reach the
Installation menu. Press the P-key until the menu changes (the first menu, Ventilation,
will appear after approx. 5 sec.).
Once this menu is open, this time delay is no longer active for approx. 15 minutes after
the last key confirmation.
Other than that, operation in the installation is no different from the other menus. To exit
the installation menu, press the
|
Esc
|
(▲ +▼) key shortcut.
P
5 sec
↓
↑
▼+▲
|
ESC
|
Ventilation ▼
▲Shutter ▼
▲Heating ▼
▲
Setp. Derat-
ing
▼
▲
Sensor ad-
just
▼
▲IO Setup
Attention!
The settings in the installation menu are priority basic settings that must be made during start-up
operation. Make these settings only if you have an exact understanding of the device functions and
system functions. Subsequent modifications must be coordinated with your electrician. We are never
liable for damage or harm caused by improper operation or insufficient knowledge.
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ The Installation menu
L-BAL-E044-GB 1911 Index 003 Part.-No.
13/36

7.2 Installation - Ventilation
Ventilation
P
↓
↑
▼+▲
|
ESC
|
7.2.1 Minimum speed cut off
Msco
In some cases in which minimum air ventilation is not needed, this feature can be used
to prevent an undercooling of the room.
Msco. OFF (factory setting).
If no “Min. speed” is adjusted, the fan stops with reaching the desired value.
If “Min. speed” is adjusted (e.g. 20%), then no disconnection of the fan takes place. I.e.,
always a minimum ventilation is ensured (fan does not go under setting “Min. speed”).
Msco ON
It takes place a disconnection from setting “Min. speed” to “0”, if the given difference
is reached related to the desired value.
•At a plus value (+) before reaching the desired value
•At a minus value (-) after falling below the desired value. Setting range: -10...+10 K
Msco
Msco
Msco. e.g. -2.0 K
nM
50 %
100 %
I
Min.
Min. 35 % Max. = 100 %
20 °C
S
7 K
R
27 °C
-2.0 K
10.05.2007
v_min_luft_abschalt.vsd
Minimum speed cut off (idealized principle diagram)
nM Motor speed
S Setpoint
R Pband
I Actual value
7.2.2 Setting Startvoltage
Startvoltage
Startvoltage (parameter depending on software version avaiable)
The power section switch-on point can be adjusted to prevent humming noises in
stationary fans.
With a control variable of approx. 5 %, the modulation is switched from “0” to 15%. The
new control range is thus 15 - 100 % (Modulation see Info menu).
Setting range: 0 - 50 %
Factory setting: 15 %
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ The Installation menu
L-BAL-E044-GB 1911 Index 003 Part.-No.
14/36

7.3 Installation - Shutter
Shutter
P
↓
↑
▼+▲
|
Esc
|
Shutter input
Shutter input
0 Sensor on E1 Control via offset to setpoint ventilation (factory setting)
1 Sensor on E2 Control independent from the ventilation nominal value
Kl. Val<Set +
Kl. Val<Set +
Basic control function:
OFF shutter open if the current value is higher than the set point (Cooling function)
ON shutter open if the current value is less than the set point (Heating function)
Ventilation link
Ventilation link
Ventilation link OFF
With the factory setting of “OFF”, the shutter operates completely independent of the
fan control. I.e., at the values set for the shutter control (offset or setpoint, min, max,
control range).
Ventilation link 1...100 %
Fan coupling value ventilation level control (in %) during which the shutter is opened
100 % independent of the settings.
If the ventilation level control is less than the vantilation link, the shutter position is
calculated as in the following:
Shutter position [%] Ventilation level control [%] / ventilation link × 100
Example:
Ventilation link setting 50 %
Ventilation level control 40 %
shutter position 40 % / 50 % x 100 80 %
Using this function, sufficient shutter opening can be ensured even during low temper-
atures and a minimal fan preset speed.
7.4 Installation - Heating
Heating
P
↓
↑
▼+▲
|
Esc
|
Heating mode
Heating mode
OFF Heating not active
1 Heating works as a two-point controller via relay (factory setting)
2 Heating works as a proportional controller (0 - 10 V)
Heating input
Heating input
0 Sensor on E1 Control via offset to setpoint ventilation (factory setting)
1 Sensor on E2 Control independent from the ventilation nominal value
Heat. Val<Set +
Heat. Val<Set +
Basic control function:
OFF cooling
ON heating (factory setting)
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ The Installation menu
L-BAL-E044-GB 1911 Index 003 Part.-No.
15/36

7.5 Installation – Setpoint derating
Setp. Derating
P
↓
↑
▼+▲
|
Esc
|
Increase
Increase
If the compartment temperature rises above the “setpoint” + the “control range”, the
setpoint is increased via an automatic timer per hour by the adjustable value (e.g. 0.2
K/h). The increase is only carried out up to a max. value (adjustable) via “Max. Rising”.
Setting range: 0.1...10 K/h
Factory setting: 0.2 K/h
Derating
Derating
If the compartment temperature sinks below the settings “Setpoint” + the “Pband”, the
Setpoint is reset via an automatic timer per hour by the adjustable value down to the
“normal set point” (setpoint in the “Ventilation” menu) (e.g. 0.1 K/h).
Setting range: 0.1...10 K/h
Factory setting: 0.2 K/h
Max. Rising
Max. Rising
Setting range: 0.0...20 K
Factory setting: 5.0 K
Minimum extra
Minimum extra
While the set point is increased, an (adjustable) tolerance is added to the ventilation
minimum.
As long as the compartment temperature is greater than the increased set point, this
results in a higher ventilation minimum (summer minimum).
If the compartment temperature falls under the increased setpoint, the tolerance
function is reduced until, with undercutting of the “normal setpoint”, the tolerance is
reduced to “0”. Thus, an overly-great amount of chilling is prevented during extreme
temperature drops, but at the same time a good degree of minimal ventilation is
feasible.
Setting range: 0...100 %
Factory setting: 50 %
Information
Function explanation see Ventilation – set point derating
7.6 Installation – Sensor adjust
Sensor adjust
P
↓
↑
▼+▲
|
Esc
|
Adjustment E1
Adjustment E1
Sensor adjustment for “E1” with a comparator. Enter the difference to the temperature
here.
Setting range: -10.00...+10.00 K
Factory setting: 0.0 K
Adjustment E2
Adjustment E2
Sensor adjustment for “E2” with a comparator. Enter the difference to the temperature
here.
Setting range: -10.00...+10.00 K
Factory setting: 0.0 K
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ The Installation menu
L-BAL-E044-GB 1911 Index 003 Part.-No.
16/36

7.7 IO Setup Assignment of inputs and outputs
IO Setup
P
↓
↑
▼+▲
|
ESC
|
Outdoor temperature
Outdoor temperature
OFF No measurement of the supply air temperature.
If ON measurement of supply air temperature active. Sensor on “E2” is taken into
consideration for the temperature alarm message (Adjustable alarm differential).
K1 Invert.
K1 Invert.
Inverting the “K1 fault indicator relay”
OFF Relay “K1” releases in cases of malfunctions, i.e., terminals 11 - 12 are bridged
(factory setting).
ON4 Relay “K1” connects in cases of malfunctions, i.e., terminals 12 - 1 are bridged.
K2 Invert.
K2 Invert.
Inverting the heating relay “K2”
OFF Relay “K2” attracts so that the heating is active, i.e., terminals 22 - 24 are
bridged (factory setting).
ON Relay “K2” releases so that the heating is active, i.e., terminals 21 - 22 are
bridged.
A2 Inverting
A2 Inverting
Inverting “A2” Shutter
OFF 0 V...10 V
ON 10 V...0 V (factory setting)
Attention is advised when operating with the output characteristic curve without invert-
ing!
A2 output curve
A2 output curve
OFF (factory setting)
ON programming of curve active, to see the following characteristic curve points.
A3 Inverting
A3 Inverting
Inverting “A3” (depending on the “heating mode” for the sequence controller or heating)
OFF 0 V...10 V (factory setting)
ON 10 V...0 V
Attention is advised when operating with the output characteristic curve without invert-
ing!
A3 output curve
A3 output curve
OFF (factory setting)
ON programming of curve active, to see the following characteristic curve points.
Output curve P0
It is possible to operate with non-linear output characteristic curves for the actuator
outputs.
The curve that is intended to be operated is defined by 6 points (these are then the
same for all connected characteristic curves).
Each point can be set from 0 - 100 %. That means an inversion made in this manner is
also possible.
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ The Installation menu
L-BAL-E044-GB 1911 Index 003 Part.-No.
17/36

Output curve P1
[V]
[%]
020
(18°)
40
(36°)
60
(54°)
80
(72°)
100
(90°)
04.08.2008
v_kennl_anlaog_ausg_6pkt.vsd
Out
1
2
3
4
5
6
7
8
9
10
R
(K)
P5
P4
P3
P2
P1
P0
R Pband
(K) Shutter bracket
Output curve P2
Output curve P3
Output curve P4
Output curve P5
8 Start-up
8.1 Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the hazardous area.
9 Settings for operation
9.1 Menu overview for operation
S:20.0° SH:94%
▼
▲Ventilation
▼
▲Alarm
▼
▲Heating
P
↓
↑
▼+▲
|
ESC
|
P
↓
↑
▼+▲
|
ESC
|
P
↓
↑
▼+▲
|
ESC
|
P
↓
↑
▼+▲
|
ESC
|
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Start-up
L-BAL-E044-GB 1911 Index 003 Part.-No.
18/36

9.2 Quickinfo, setpoint, min. and max. compartment temperatures
S:20.0° SH:94%
P
↓
↑
▼+▲
|
Esc
|
Setpoint
Setpoint
Setting range: 0...40 °C
Factory setting: 20 °C
E2
E2
When a second sensor (optional) is connected to the input “E2” measured temper-
ature.
If no sensor is connected the maximum value is displayed. Depending on the device
type
|
81.6 °C
|
or
|
149.9
|
Temp. min Value
Temp. min. Value
The lowest temperature in the compartment (at input “E1”) since device reset (mains
supply ON / OFF) or a manual reset with “Reset Min-Max”
Temp. max Value
Temp. max. Value
Maximum temperature in the compartment (at input “E1”) since device reset (mains
supply ON / OFF) or a manual reset with “Reset Min-Max”
Reset Min-Max
Reset Min-Max
Reset of minimum and maximum values. I.e., the temperature measurement starts
again.
Language
Language
Menu language by the factory set to German.
In this menu different national languages can be selected (GB English, D German
...).
PIN
PIN
The presets can be stored and reset using PIN codes (
Menu overview)
PIN 9090
Restore user setting
PIN 9091
To save the basic user settings.
The individually made device configurations can be saved here.
With the corresponding PIN input 9090 can be re-established.
PIN 9095
Restore factory setting delivery status
Version
Version
Displays the software version
00056:46:13
O Operation, T Time, C Controller
The time counting runs, as soon as mains voltage is connected (without fault).
If events step on (Motor fault, External Error, etc.), the period of operation is stored at
this time (
Events).
00056:46:13
O Operation, T Time, M Motor
The time counting runs as soon as a modulation of the controller is present.
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Settings for operation
L-BAL-E044-GB 1911 Index 003 Part.-No.
19/36

9.3 Setting Ventilation
Ventilation
P
↓
↑
▼+▲
|
ESC
|
Ventilation
The ventilation level control is additionally to the bargraph displayed here
in digits for informational purposes.
9.3.1 For the regulation of the fan
Setpoint
Setpoint
Setting range: 0...40 °C
Factory setting: 20 °C
Pband
Pband
Adapting the control action to the system conditions.
Narrow control range Short control times
Wide control range Longer control times and more stable control
Setting range: 2.0...20.0 K
Factory setting: 4.0 K
Min. Speed
Min. Speed
Setting range: 0...100 %
Factory setting: 20 %
Max. Speed
Max. Speed
Setting range: 100 %... “Min. Speed”
Factory setting: 100 %
Temperature control (Idealized principle diagram)
nM
50 %
100 %
I
Min.
Min. 0 % Max. = 100 %
Min. 35 % Max. = 85 %
20 °C
S
10 K
R
30 °C 09.05.2007
v_tempcontrol_cool_nmotor.vsd
nM Motor speed
S Setpoint
R Pband
I Actual value
Operating Instructions Acontrol – model series PTE-6AHQ / PTE-10AHQ Settings for operation
L-BAL-E044-GB 1911 Index 003 Part.-No.
20/36
This manual suits for next models
1
Table of contents
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu ASYG 09 LLCA installation manual

York
York HVHC 07-12DS Installation & owner's manual

Carrier
Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Frigidaire
Frigidaire FAC064K7A2 Factory parts catalog

Sanyo
Sanyo KS2432 instruction manual

Mitsubishi Electric
Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic
Panasonic CS-S18HKQ Service manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

Gree
Gree GWH18TC-K3DNA1B/I Service manual

Friedrich
Friedrich ZoneAire Compact P08SA owner's manual

Daikin
Daikin R32 Split Series installation manual