AB Regin Corrigo E81D-3 User manual

Corrigo manual
Ventilation application
© Copyright AB Regin, Sweden, 2013

DISCLAIMER
The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties
as regards the contents of this manual and users are requested to report errors, discrepancies or ambiguities to Regin, so that
corrections may be made in future editions. The information in this document is subject to change without prior notification.
The software described in this document is supplied under licence by Regin and may be used or copied only in accordance
with the terms of the licence. No part of this document may be reproduced or transmitted in any form, in any fashion,
electronically or mechanically, without the express, written permission of Regin.
COPYRIGHT
AB Regin. All rights reserved.
TRADEMARKS
Corrigo, E tool©, EXOdesigner, EXOreal, EXOrealC, EXOline, EXO4, EXO4 Web Server, Optigo, Regio and Regio tool are
registered trademarks of AB Regin.
Windows, Windows 2000, Windows XP, Windows Vista, Windows 7, Windows 8 and Windows Server 2003 are registered
trademarks of Microsoft Corporation.
Some product names mentioned in this document are used for identification purposes only and may be the registered
trademarks of their respective companies.
Revision R, September 2013
Software revision: 3.3

Table of contents
CHAPTER 1 ABOUT THE MANUAL ..................................................................................................6
More information ........................................................................................................................6
CHAPTER 2 ABOUT CORRIGO .........................................................................................................7
2.1 News in version 3.3................................................................................................................7
2.2 Application choice .................................................................................................................7
2.3 Technical data......................................................................................................................12
CHAPTER 3 INSTALLATION AND WIRING...................................................................................... 14
3.1 Installation ...........................................................................................................................14
3.2 Wiring ..................................................................................................................................14
CHAPTER 4 COMMISSIONING ...................................................................................................... 21
4.1 How to do it .........................................................................................................................21
CHAPTER 5 FUNCTIONAL DESCRIPTION ....................................................................................... 24
5.1 Temperature control ...........................................................................................................24
5.2 Extra control circuit .............................................................................................................37
5.3 Humidity control..................................................................................................................38
5.4 Fan control...........................................................................................................................39
5.5 Pump control .......................................................................................................................45
5.6 Damper control....................................................................................................................45
5.7 Extended running and External switch ................................................................................46
5.8 Time-switch outputs ............................................................................................................47
5.9 Alarms..................................................................................................................................47
CHAPTER 6 STARTING AND STOPPING THE UNIT ......................................................................... 49
6.1 Start conditions....................................................................................................................49
6.2 Stop conditions ....................................................................................................................49
6.3 Start sequence .....................................................................................................................50
6.4 Stop sequence .....................................................................................................................50
CHAPTER 7 DISPLAY, LEDS AND BUTTONS ................................................................................... 51
7.1 Display .................................................................................................................................51
7.2 LEDs .....................................................................................................................................51
7.3 Buttons ................................................................................................................................51
7.4 Navigating the menus ..........................................................................................................51
CHAPTER 8 ACCESS RIGHTS.......................................................................................................... 53
8.1 Log on ..................................................................................................................................53
8.2 Log off ..................................................................................................................................53
8.3 Change password.................................................................................................................54
8.4 Change password to remove automatic logoff ...................................................................54
CHAPTER 9 RUNNING MODE ....................................................................................................... 55
9.1 Running mode, unit .............................................................................................................55
9.2 Selected functions ...............................................................................................................55
9.3 Alarm events........................................................................................................................56
9.4 Inputs/Outputs ....................................................................................................................56
CHAPTER 10 TEMPERATURE ........................................................................................................ 57
CHAPTER 11 AIR CONTROL........................................................................................................... 62
CHAPTER 12 HUMIDITY CONTROL................................................................................................ 65
CHAPTER 13 TIME SETTINGS ........................................................................................................ 66
13.1 Time / Date ........................................................................................................................66
13.2 Timer Normal speed ..........................................................................................................66
13.3 Timer Reduced speed ........................................................................................................67

13.4 Extended running ..............................................................................................................67
13.5 Timer outputs 1…5.............................................................................................................67
13.6 Holidays .............................................................................................................................68
CHAPTER 14 MANUAL / AUTO ..................................................................................................... 69
CHAPTER 15 SETTINGS ................................................................................................................. 72
15.1 Control temp......................................................................................................................72
15.2 Control pressure ................................................................................................................73
15.3 Control flow .......................................................................................................................73
15.4 Humidity control................................................................................................................74
15.5 Control Extra unit...............................................................................................................74
15.6 Alarm settings....................................................................................................................74
15.7 Save and restore settings...................................................................................................76
CHAPTER 16 EXPANSION MODEL ................................................................................................. 77
16.1 Ports...................................................................................................................................77
16.2 Wiring ................................................................................................................................77
CHAPTER 17 CONFIGURATION ..................................................................................................... 79
17.1 Inputs and outputs.............................................................................................................79
17.2 Sensor settings...................................................................................................................81
17.3 Control function.................................................................................................................82
17.4 Fan control.........................................................................................................................82
17.5 Extra control circuit ...........................................................................................................83
17.7 Extra sequence Y5..............................................................................................................84
17.8 Heating coil ........................................................................................................................84
17.9 Exchanger ..........................................................................................................................84
17.10 Chiller...............................................................................................................................85
17.11 Pump control ...................................................................................................................86
17.12 Free cooling .....................................................................................................................86
17.13 Support control................................................................................................................87
17.14 CO2Demand control ........................................................................................................87
17.15 Fire function.....................................................................................................................87
17.16 Humidity control..............................................................................................................88
17.17 Exchanger de-icing...........................................................................................................88
17.18 Cooling recovery ..............................................................................................................88
17.19 Minimum limit dampers ..................................................................................................88
17.21 External setpoint..............................................................................................................89
17.22 Run indication / Motor protection ..................................................................................89
17.23 Actuator type...................................................................................................................90
17.24 Running time, 3-position actuators .................................................................................90
17.25 Step controllers................................................................................................................91
17.26 Recirculation ....................................................................................................................92
17.27 Pretreatment ...................................................................................................................93
17.28 Alarm setting ...................................................................................................................93
17.29 Communication ...............................................................................................................97
17.30 Other parameters ............................................................................................................99
17.31 System ...........................................................................................................................102
CHAPTER 18 OTHER FUNCTIONS................................................................................................ 105
18.1 Alarm handling.................................................................................................................105
18.2 Free text...........................................................................................................................105
18.3 Revision number..............................................................................................................105
18.4 Language..........................................................................................................................106
18.5 Indication LEDs ................................................................................................................106
18.6 Changing the battery .......................................................................................................106
18.7 Start-up wizard ................................................................................................................107
18.8 Energy calculation............................................................................................................109
18.9 SFP (Specific Fan Power) ..................................................................................................109

INDEX ........................................................................................................................................ 110
APPENDIX FREQUENCY CONVERTERS ........................................................................................ 114

6 Chapter 1 About the manual Manual Corrigo Ventilation, revision R
Chapter 1 About the manual
This manual covers all the models in the Corrigo series used with the ventilation application. This
revision covers program revisions from 3.3.
More information
More information about Corrigo can be found in:
•Corrigo ventilation user guide – A simplified manual
•Manual E tool©– Manual on how to configure the controllers using the PC software
E tool©, available in Swedish, English, German and French.
•LON-interface variable list – Variable list for the Corrigo series, available in Swedish and
English.
•Corrigo ventilation variables for EXOline, Modbus and BACnet – Variable list for
EXOline, BACnet and Modbus communication, available in English.
•Corrigo ventilation Communication Guide – The most common Modbus and BACnet
variables.
•Editable PDF files for Corrigo
•CE - Declaration of conformity, Corrigo
The information is available for download from Regin's website, www.regin.se.

Manual Corrigo Ventilation, revision R Chapter 2 About Corrigo 7
Chapter 2 About Corrigo
The Corrigo series comprises three model sizes: 8, 15 or 28 in-/outputs.
In each third generation model Corrigo, all applications are loaded in a separate memory area. The
models have article number E...-3 (where 3 stands for third generation). A new feature in version
3.3 are models with three communication ports. The 3 port Corrigo models have article number
E...3-3 (where the initial “3” stands for 3 ports). For more detailed information, see chapter 16.
The controllers are available with or without a front panel display and buttons. For all third
generation units, both with and without display, a separate, cable-connected terminal E3-DSP with
display and buttons is available.
All configuration and normal handling can be done using the display and buttons or using the
configuration tool E tool©, installed on a PC and connected via the communication cable E-cable.
2.1 News in version 3.3
•The operating system has been further improved and is now called EXOrealC.
•Support for three communication ports.
•BACnet/IP is now available as a communication protocol.
•New filter alarm: Separate filter alarms.
•Analogue filter alarm, filter pressure alarm.
•Temperature alarm for extra sensors 1-5.
•Support for 0…10V outdoor sensor and room sensor.
•Modulating recirculation air damper, Y4-Extra sequence.
•Communication with Danfoss model Frequency converters FC 101 now supported.
•Additional Modbus signals.
2.2 Application choice
On delivery, the main memory in the Corrigo is empty. All the application programs that can be run
in the Corrigo are located in a separate memory area.
On the first start-up, the controller will start a special program for downloading a suitable
application and suitable languages to the main memory.
For certain customised models, an application has already been selected when the product is
delivered. If so, the selected application will be started immediately.
E283W-3
PLA: 254 ELA: 30
Baud#1: 9600
Rev: 3.3-1-01
The initial screen details the model of the Corrigo unit, its communication address, communication
speed and which software revision is loaded into the unit.
Press down arrow to go to ”Application choices”.
Application
System
Communication
Time/Date
Input/Output

8 Chapter 2 About Corrigo Manual Corrigo Ventilation, revision R
Use the up and down arrows to move the cursor in the left edge of the display to the function you
wish to select. Select “Application” and press the right arrow.
Corrigo Vent.131021
Expansion unit 1
Expansion unit 2
Corrigo Vent.140212
Move the cursor to the desired application. Press the right arrow.
Title:
Corrigo Ventilation
3.3
Activate? No
Press ”OK” and change ”No” into ”Yes”. Press ”OK”.
The most recently loaded ventilation application will now be entered into memory. This will take
approx. 30 seconds. The application start screen is displayed.
To change languages, press the right arrow 3 times and then choose a language in the same way you
selected an application.
2.2.1 Additional menu options
System:
Information on the Corrigo model and serial number.
EXOreal version.
MAC address and IP address.
Battery status and memory size.
Memory status and voltage frequency.
Communication:
Communication mode selection.
Serial:
Enables selecting EXOline address, communication speed, port mode and routing span.
TCP/IP:
Enables EXOline address selection and choice of DHCP (Yes/No).
Also enables manual IP address and subnet mask setting before the Corrigo is initiated. Default
Gateway and DNS name is also available under this menu.
Current subnet mask, gateway and DNS name.
Main computer status.
Main computer IP address.
Permit connection to main computer.
TCP port routing to serial port 1 or 2.
Time/Date:
Permits setting the time and date.

Manual Corrigo Ventilation, revision R Chapter 2 About Corrigo 9
Input/Output:
Enables In-/Output reading and writing.
2.2.2 Ventilation application
The temperature controller is based on a supply air PI-controller for heating control with a pre-
programmed set of control modes. A number of different control functions as well as analogue and
digital in- and output functions can be bound to this controller. Certain functions are necessary,
while others can be considered optional. The choice of which functions are to be used is free, the
only restriction is the physical number of inputs and outputs of the different models. The maximum
number of I/Os is 3*28 (a 2- or 3-port Corrigo with two expansion units).
The Corrigo is designed for DIN-rail mounting.
The program for an air handling unit contains, apart from other things, the following functions:
Different temperature control modes:
•Supply air temperature control, with or without outdoor temperature compensation
•Room temperature control (cascade control).
•Extract air control (cascade control).
•Seasonal switching between supply air temperature control and room/extract air
temperature control.
•Outdoor compensated room/extract air control.
•Extra, separate temperature control circuit for after-heaters, etc.
•Extra control sequences Y4 and Y5 (in addition to Y1, Y2 and Y3) for free integration
into the controller output.
With control of:
•Heat exchanger (liquid connected, plate or rotating) or mixing dampers.
•Heating coil: Water with or without frost protection or electric with high temperature limit
switch.
•Cooling: Water or DX cooling in up to 3 steps.
•Circulation pumps heating, cooling, exchanger.
Fan control
•1- or 2-speed supply air and extract air fans.
•Frequency controlled supply and extract air fans with pressure or flow control, manual
control or external control from a VAV system.
•Pressure controlled supply air fan with slave connected extract air fan (output dependent or
flow dependent) or opposite function (pressure controlled extract air fan with slave
connected supply air fan, output dependent or flow dependent).
Humidity control
It is possible to use either humidification or dehumidification, or to use combined humidification
and dehumidification.
Timer control
For starting and stopping the unit, annual clock function. Up to 5 timer outputs for control of
external functions such as lighting, doorlocks etc.

10 Chapter 2 About Corrigo Manual Corrigo Ventilation, revision R
Demand controlled ventilation
In buildings with strongly varying occupancy the fan speeds or mixing dampers can be controlled
by the air quality measured by a CO2sensor.
Support control
When using the control function room control or extract air temperature control, it is possible to
utilise support-heating and/or support-cooling.
Free cooling
When this function has been activated, it is used during the summer to cool the building during the
night using cool outdoor air thereby reducing the need to run chillers during the day.
Free heating
If the outdoor temperature is higher than the indoor temperature and there is a heating demand, the
recovery damper will not open for recovery but instead open fully for outdoor air. This may occur
during low night-time outdoor temperatures, when the room has been cooled considerably and the
outside heat is rising faster than indoors. This function is activated at the same time as “Free
cooling”.
Enthalpy control
Measures and compares the energy content (enthalpy) of the outdoor air and the extract air
(temperature and air humidity). When this function is active, the mixing damper signal will be
overridden to recirculation if the enthalpy is higher outdoors than indoors.
Pretreatment
Damper and pump control for preheating or precooling of the outdoor air via an underground intake
channel.
Cooling recovery
If the extract air is colder than the outdoor air and cooling is required, the heat exchanger control is
reversed in order to return the cool extract air.
Recirculation control
Recirculation of air using a supply air fan and (optionally) extract air fan and a recirculation damper
with or without temperature control. Used as a recovery function or during heating with support
control during the night. Recirculation control is available as an analogue or a digital function.
Step controllers Heating/Cooling
As an alternative to the analogue control of ”Actuator heating Y1” or ”Actuator cooling Y3” step
controllers can be used for controlling heating or cooling in steps using digital control.
Change-over
In 2-pipe systems where a combination heater/cooler is operating together with a heat pump,
Change-over is a function that enables using the same pipe for both heating and cooling, depending
on which is currently required. It uses the output Y1 Heating/Y3 Cooling.

Manual Corrigo Ventilation, revision R Chapter 2 About Corrigo 11
Corrigo hardware overview
E81-3
E81D-3
E151-3
E151W-3
E151D-3
E151DW-3
E15D-S-LON
E152W-3
E152DW-3
E281-3
E281D-3
E281W-3
E281DW-3
E282W-3
E282DW-3
E28D-S-LON
E283W-3
E283DW-3
AI* 2
2
4
4
4
4
4
4 4 4
4
4 4
4
4 4
4
4
DI*
3
3
4
4
4
4
4
4
4
8
8
8
8
8
8
8
8
8
UI* -
-
-
-
-
-
-
- - 4
4
4 4
4
4 4
4
4
AO* 1
1
3
3
3
3
3
3 3 5
5
5 5
5
5 5
5
5
DO*
2
2
4
4
4
4
4
4
4
7
7
7
7
7
7
7
7
7
RS485 •
•
•
•
•
• • •
•
•
••
•
•
BACnet/IP
•
•
•
•
•
•
•
•
•
•
LON •
•
TCP/IP •
•
• • • •
•
• •
•
1 port
•
•
•
•
•
•
•
•
•
•
•
2 ports • • •
• •
3 ports
•
•
Display •
•
•
•
• •
•
• •
•
* AI=analogue inputs, DI=digital inputs, AO=analogue outputs, DO=digital outputs, UI=universal
inputs (can be configured to function as either analogue input or digital input).
All third generation Corrigo controllers support external displays.
Corrigo model overview
Models with display Models without display Description
E81D-3
E151D-3
E281D-3
E81-3
E151-3
E281-3
Standard controller with RS485 port
E15D-S-LON
E28D-S-LON Controller with both LON and RS485 port
E151DW-3
E281DW-3 E151W-3
E281W-3 Controller with TCP/IP port and built-in web server
E152DW-3
E282DW-3 E152W-3
E282W-3
Controller with one RS485 port, one TCP/IP port and
built-in web server
E283DW-3 E283W-3 Controller with two RS485 ports, one TCP/IP port
and built-in web server

12 Chapter 2 About Corrigo Manual Corrigo Ventilation, revision R
2.3 Technical data
Protection class ..................................................................................................................IP20
Display........................................................4 rows of 20 characters. Background illumination.
LEDs
Yellow.......................................................................................................Settable parameter
Red ...............................................................................................................Alarm indication
Clock ..................................................................Year base 24 hour clock with battery backup.
Automatic summer-/winter-time changeover.
Operating system..........................................................................................................EXOreal
Supply voltage....................................................24 V AC ±15%, 50…60 Hz or 21…36 V DC
Power consumption ........................................5 VA, 3 W (DC), model …W: 9 VA, 5 W (DC)
Dimensions....................................................................148x123x60 (WxHxD incl. terminals)
Casing..........................................................................Standard Euronorm (8.5 modules wide)
Mounting ................................................................................................................On DIN-rail
Operation
Climatic conditions according to IEC 721-3-3........................................................Class 3k5
Ambient temperature..................................................................................................0...50°C
Ambient humidity..............................................................................................Max 95% RH
Mechanical requirements according to IEC721-3-3 ..............................................Class 3M3
Vibration..........................................................IEC60068-2-6, Test FC, vibration Sinusoidal
Shock................................................................................................IEC60068-2-27, Test Ea
Transport
Climatic conditions according to IEC 721-3-2........................................................Class 2k3
Ambient temperature..............................................................................................-20...70°C
Ambient humidity..............................................................................................Max 95% RH
Mechanical requirements according to IEC721-3-2 ..............................................Class 2M2
Vibration..........................................................IEC60068-2-6, Test FC, vibration Sinusoidal
Shock................................................................................................IEC60068-2-27, Test Ea
Free fall.............................................................................................IEC60068-2-27, Test Ed
Storage
Climatic conditions according to IEC 721-3-1........................................................Class 1k3
Ambient temperature..............................................................................................-20...70°C
Ambient humidity..............................................................................................Max 95% RH
Battery
Type.................................................................................... Replaceable Lithium cell, CR2032
Battery life ...................................................................................................Better than 5 years
Warning.................................................................................................... Low battery warning
Battery backup...............................................................................Memory and real time clock
Communication
EXOline Port 1, insulated via a built-in RS485 contact.
EXOline Port 2, via a built-in RS485 contact.
EXOline TCP/IP.
Modbus communication via serial RS485 communication (not TCP/IP).
BACnet/IP.
LON serial communication.
Suitable model should be selected for appropriate needs.
EMC emission and immunity standard
This product conforms to the requirements of the EMC Directive 2004/108/EC through product
standards EN 61000-6-1 and EN 61000-6-3.
RoHS
This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council.

Manual Corrigo Ventilation, revision R Chapter 2 About Corrigo 13
Inputs
Analogue inputs AI..............................................Settable 0…10 V DC or PT1000, 12 bit A/D
Digital inputs DI.......................................................................................Potential-free closure
Universal inputs UI...........................................Can be set to act as either an analogue input or
a digital input with specifications as above
Outputs
Analogue outputs AO...............................................Configurable 0…10 V DC; 2…10 V DC;
10…0 V DC or 10…2 V DC
8 bit D/A short-circuit protected
Digital outputs DO ...........................................Mosfet outputs, 24 V AC/DC, 2 A continuous.
Totally max 8 A.
Options
LON...................................................................FT3150, gives a second communication route
…W (TCP/IP-port)...............................Replaces RS485 for EXOline (Port 1) communication
2-port Corrigo models ........................Two serial ports or one serial port and one TCP/IP port
3 ports Corrigo................................................................Two serial ports and one TCP/IP port
External hand terminal, E3-DSP .........................For use with Corrigo E units without display
External room unit...................................................................... ED-RU / ED-RUD / ED-TCV
Position of the terminals on the Corrigo

14 Chapter 3 Installation and wiring Manual Corrigo Ventilation, revision R
Chapter 3 Installation and wiring
3.1 Installation
Corrigo can be mounted in a DIN-standard casing (minimum 9 modules), on a DIN-rail in a cabinet
or, using a suitable front-mounting kit, in a cabinet door or other control panel.
Ambient temperature: 0…50°C.
Humidity: Max. 90 % RH, non-condensing.
The picture below shows a wiring example for Corrigo E283W-3.
3.2 Wiring
At the end of this chapter there are wiring diagrams showing the factory set configuration. There are
also empty wiring diagrams. Since the function of most of the inputs and outputs depends on the
programming of the unit the final wiring diagram cannot be filled in until the installer has decided
how to use the inputs/outputs. It is important to ensure that the wiring is performed correctly and in
accordance with the instructions given in this manual.

Manual Corrigo Ventilation, revision R Chapter 3 Installation and wiring 15
3.2.1 Supply voltage
24 V AC ±15%, 50…60 Hz or 21…36 V DC
If Corrigo and its connected actuators share the same transformer, it is essential that the same
transformer pole is used as reference for all the equipment. The equipment may otherwise not
function as intended and may also suffer damages.
3.2.2 Inputs and outputs
The list of input and output functions in section 3.2.3 is a handy instrument to help you keep track
of which inputs and outputs you will need to configure.
Analogue inputs
Analogue inputs must refer to an Agnd terminal placed in the same terminal block as the input being
wired.
Analogue inputs can, depending on the configuration, be used for either PT1000 temperature
sensors or for 0…10 V DC analogue input signals, for example from a pressure transmitter.
Digital inputs
Digital inputs must refer to +C on terminal 4. Digital inputs may only be wired to voltage-free
contacts. Any external voltage applied to a digital input may harm the unit. The input signal can be
set to either NO or NC.
Universal inputs
A universal input can be configured to act as either an analogue input or as a digital input.
A universal input configured as an analogue input can, depending on the configuration, be used for
either PT1000 temperature sensors or for 0…10 V DC analogue input signals, for example from a
pressure transmitter.
Universal inputs configured as an analogue input must refer to an Agnd terminal placed in the same
terminal block as the input being wired.
A universal input configured as a digital input must, just like other digital inputs refer to C+ on
terminal 4. It may only be wired to voltage-free contacts.
Analogue outputs
Analogue outputs must refer to the Agnd terminal placed in the AO terminal block.
All analogue outputs can be individually set to any one of the following signals:
0…10 V DC
2…10 V DC
10…0 V DC
10…2 V DC
If the Corrigo and the actuators connected to it share the same transformer it is essential that the
same transformer-pole is used as reference for all the equipment. Failure to do so will prevent the
equipment from functioning as intended and may also lead to damages.
Digital outputs
Digital outputs should normally refer to GDO on terminal 10. GDO is internally connected to G on
terminal 1 and supplies 24 V AC or DC depending on the choice of supply voltage.
All the digital outputs are controlled by MOSFET transistors. The outputs are internally connected
with G0and can deliver max 2 A per output. However, the total power for all the DOs must not be
over 8 A.

16 Chapter 3 Installation and wiring Manual Corrigo Ventilation, revision R
A number of different wiring alternatives are possible depending on the type of supply voltage to
the Corrigo and the relay type.
24 V AC supply and 24 V AC relays
24 V DC supply and 24 V DC relays
24 V AC supply and 24 V DC relays
G
G0
10
11
12
L
N
24 VAC
G
G
0
10
11
12
+
-
24 V DC
+ -
+ -
+ -
G
G0
10
11
12
L
N
24 VAC
24 V DC
+ -
+ -
+ -
+ -
24 V AC
24 V AC

Manual Corrigo Ventilation, revision R Chapter 3 Installation and wiring 17
24 V DC supply and 24 V AC relays
3.2.3 Input and output lists
The lists below are intended to be used during commissioning to help you keep track of the desired
input and output functions.
The left column contains a description of the in-/output signal, the middle column displays the name
of the corresponding signal in E tool©and the right column shows the text displayed in the Corrigo
controller.
Analogue input signal
Description E tool©Display
Inactive input
Not active
Not active
Outdoor temperature sensor, PT1000 or
0…10V
Outdoor Temp Outdoortemp
Supply air temperature sensor Supply Air Temp Supplytemp
Extract air temperature sensor Extract Air Temp Extracttemp
Exhaust air temperature sensor Exhaust Air Temp Exhausttemp
Room temperature sensor 1, PT1000 or
0…10V
Room Temp 1 Roomtemp1
Room temperature sensor 2 Room Temp 2 Roomtemp2
CO2sensor, 0…10 V DC
CO2 Sensor
CO2
Pressure transmitter supply air, 0…10
V DC
SAF Pressure SAF pressure
Pressure transmitter extract air, 0…10
V DC EAF Pressure EAF pressure
De-icing sensor, heat exchanger
Deicing Temp
Deicingtemp
Frost protection sensor Frost Protection Temp Frost prot. temp
Room humidity sensor
Humidity Room
Humidity room
Duct humidity sensor Humidity Duct Humidity duct
Outdoor humidity sensor Humidity Outdoor Humidity out
Temperature sensor, Extra controller
Extra unit temp
Extra unit temp
External control supply air fan External control SAF SAF ext. Ctrl
External control extract air fan
External control EAF
EAF ext. Ctrl
Pressure transmitter supply air 2 SAF Pressure 2 SAF pressure 2
G
G0
10
11
12
+
-
24 V DC
24 VAC
L N
24 V AC

18 Chapter 3 Installation and wiring Manual Corrigo Ventilation, revision R
Description E tool©Display
Intake temperature Intake Temp Intaketemp
Extra temperature sensor 1
Extra Sensor Temp 1
Extrasensor
Extra temperature sensor 2 Extra Sensor Temp 2 Extrasensor 2
Extra temperature sensor 3
Extra Sensor Temp 3
Extrasensor 3
Extra temperature sensor 4 Extra Sensor Temp 4 Extrasensor 4
Extra temperature sensor 5 Extra Sensor Temp 5 Extrasensor 5
Extra pressure transmitter supply air
Extra SAF Pressure
Extra SAF Pressure
Extra pressure transmitter extract air Extra EAF Pressure Extra EAF Pressure
External flow pressure transmitter
External flow setpoint
Ext sp flow
Analogue filter guard 1 Filter Guard 1 Filter alarm 1
Analogue filter guard 2 Filter Guard 2 Filter alarm 2
Digital input signal
Description E tool©Display
Inactive input
Not active
Not active
Filter guard, supply air Filter Guard 1 Filter alarm 1
Filter guard, extract air
Filter Guard 2
Filter alarm 2
Run-indication/alarm circulation pump,
Heating
Heat Pump Indication P1-Heating
Run-indication/alarm circulation pump,
exchanger Exchange Pump Indication P1-Exchanger
Run-indication/alarm circulation pump,
Cooling Cooling Pump Indication P1-Cooling
Fire alarm
Fire Alarm
Fire alarm
Fire damper end-switch monitoring Fire Damper Indication Fire damper-ind
Extended operation, Normal
Extended Operation, Normal
Ext run 1/1
Extended operation, Reduced Extended Operation, Reduced Ext run 1/2
External switch External Switch External switch
External alarm
External Alarm
External alarm
Flow switch Flow Switch Flow guard
Rotation guard exchanger
Exchange Rotation
Rot.sent.exch
Run-indication/alarm supply air fan SAF Indication SAF-Ind
Run-indication/alarm extract air fan EAF Indication EAF-Ind
Deicing thermostat exchanger
Deicing
De-icing
Frost protection thermostat water heater Frost Protection Frostprotection
High temperature limit switch
Overheated Electric heater
Overheatprotection
Recirculation start Recirculation Recirculation
Change over Change over Change over
The universal inputs on Corrigo E28 can be individually configured as either analogue inputs, using
any of the analogue input signals above, or as digital inputs using any of the digital inputs above.

Manual Corrigo Ventilation, revision R Chapter 3 Installation and wiring 19
Analogue output signal
Description E tool©Display
Inactive output Not used Not used
Y1 Actuator Heating
Heating Y1
Y1-Heating
Y2 Actuator Exchanger Exchanger Y2 Y2-Exchanger
Y3 Actuator Cooling
Cooling Y3
Y3-Cooling
Frequency converter, supply air fan SAF SAF
Frequency converter, extract air fan EAF EAF
Actuator Humidity control Dehumidification/
Humidification Humidity
Split of any one of temp outputs Y1, Y2,
Y3 or Y1 Heating/Y3 Cooling outputs Split Sequence
Extra controller
Extra unit control
ExtraUnitCtrlVa
Y1 Heating / Y3 Cooling, Change-over
output
Y1 Heating/Y3 Cooling Y1-Heat/Y3-Cool
Y4 Extra Sequence
Also used for control of recirculation air
damper 0...10V
Extra Sequence Y4 Y4-extra sequence
Y5 Extra Sequence Extra Sequence Y5 Y5-extra sequence
Digital output signal
Description E tool©Display
Inactive output Not used Not used
Start/stop Supply air fan Normal
SAF Start 1/1 Normal Speed
SAF 1/1-speed
Start/stop Extract air fan Normal EAF Start 1/1 Normal Speed EAF 1/1-speed
Start/stop Supply air fan Reduced
SAF Start 1/2 Reduced Speed
SAF 1/2-speed
Start/stop Extract air fan Reduced EAF Start 1/2 Reduced Speed EAF 1/2-speed
Start/stop circulation pump, heating Heating Pump Start P1-Heating
Fire damper
Fire Damper
Fire damper
Sum alarm A- and B-alarm Sum Alarm Sum alarm
Sum alarm A-alarm
Sum Alarm A
A-sum alarm
Sum alarm B-alarm Sum Alarm B B-sum alarm
Start/stop circulation pump, cooling Cooling Pump Start P1-Cooling
Start/stop circulation pump, liquid
exchanger Exchanger Start P1-Exchanger
Activation-signal SAF frequency
converter SAF Freq Start SAF-frequence
Activation-signal EAF frequency
converter EAF Freq Start EAF-frequence
Activate heating
Heating Activate
Heat start
Activate cooling Cooling Activate Cool start
Activate exchanger Exchanger Activate Exch start
Exhaust air close-off damper
Exhaust Air Damper
Exhaust air d
Fresh air close-off damper Outdoor Air Damper Fresh air dam

20 Chapter 3 Installation and wiring Manual Corrigo Ventilation, revision R
Description E tool©Display
Recirculation damper Recirculation Air Damper Recirc. damper
Heating 3-position actuator, increase Heating Increase Heat-inc
Heating 3-position actuator, decrease Heating Decrease Heat-dec
Exchanger 3-position actuator, increase
Exchanger Increase
Exch-inc
Exchanger 3-position actuator, decrease Exchanger Decrease Exch-dec
Cooling 3-position actuator, increase Cooling Increase Cool-inc
Cooling 3-position actuator, decrease Cooling Decrease Cool-dec
Step controller heating, step 1 Heat Step 1 Heat step1
Step controller heating, step 2
Heat Step 2
Heat step2
Step controller heating, step 3 Heat Step 3 Heat step3
Step controller heating, step 4 Heat Step 4 Heat step4
Step controller cooling, step 1 Cool Step 1 Cool step1
Step controller cooling, step 2 Cool Step 2 Cool step2
Step controller cooling, step 3
Cool Step 3
Cool step3
Extra time channel 1 Time Channel 1 Timer 1
Extra time channel 2 Time Channel 2 Timer 2
Extra time channel 3 Time Channel 3 Timer 3
Extra time channel 4 Time Channel 4 Timer 4
Extra time channel 5
Time Channel 5
Timer 5
Humidity Humidity/DeHumidity Humidity
External controller active Extra unit active ExtraUnitActi
Heating/cooling step 1 Heat/cool step 1 HeatCoolStep1
Heating/cooling step 2 Heat/cool step 2 HeatCoolStep2
Heating/cooling step 3
Heat/cool step 3
HeatCoolStep3
Free cooling operation Free cool run Free cool run
Pretreatment Pretreatment Pretreatment
Free cooling operation Free cool run Free cool run
Pretreatment Pretreatment Pretreatment
Split sequence active
Split Sequence
Split sequence
Run indication Run indication Run ind.
Pulse modulated heating output Heating PWM Heating PWM
This manual suits for next models
17
Table of contents
Popular Fan manuals by other brands

LUCCI
LUCCI ATLANTA Installation, operation, maintenance & warranty information

Bionaire
Bionaire BAFE1507 instruction manual

Sonnenkonig
Sonnenkonig FLOWER FAN instruction manual

HOFFEN
HOFFEN USB01 instruction manual

Klimatronic
Klimatronic CoolBreeze 1500 TV manual

Monte Carlo Fan Company
Monte Carlo Fan Company 5WF52XXD Series owner's manual