Overview
This docu ent is a short description of how to power up the Wireless Gateway RER601/603
product and how to get it operational. For further infor ation consult the product Technical
Manual.
Physical connections and switches
Connector panel:
1. Power supply connector
2. Power switch
3. Console/application serial port (RS1)
4. Console/application port selection switch
5. Application serial port (RS2)
6. DIP switches (RS2 hardware settings)
7. I/O connector (only on RER603)
8. Ethernet connector
Antenna panel:
9. Antenna connector (FME)
10.SIM card slot
Installing SIM card
NOTE: If you have PIN code querying enabled on your SIM card, do not install the card before
setting the code. The SIM card could lock up if done otherwise. SIM card is not included.
1. Power off the RER601/603. It is reco ended to turn power off while installing/re oving the SIM
card.
2. Push the yellow button in the SIM card slot to eject the SIM card tray.
3. Insert the SIM card to the tray and push the SIM card tray fir ly and carefully back to its holder.
ABB www.abb.com/substationautomation 1MRS757426 Rev. A
123 4 57 8
910
6

Wireless Gateway RER601/603 2(4)
Quick Start Guide
Connecting the RER601/603 to an Ethernet network
There are two different ways to configure the network settings: via serial port or Web Browser
interface. It is reco ended to use the Web Browser to configure the network connection
settings.
Method 1: Setting IP Address Using Web Browser (Reco ended)
1. Connect the cross-over Ethernet cable between the RER601/603 and your co puter.
2. Configure your co puter to use the sa e IP address space than the RER601/603 (laptop IP
for exa ple 10.10.10.11 with net ask 255.0.0.0). Check the connection to the RER601/603
with ping utility.
3. Connect to the RER601/603 using your web browser. The default IP address of the
RER601/603 is 10.10.10.10 (net ask 255.0.0.0).
4. Fro the initial page click Start configurator and enter login infor ation in the following
page. Userna e is root and by default no password is set (just leave the field e pty).
5. Navigate to Network page and fro there to Ethernet subpage.
6. Enter the IP address and other network settings of your choice and click Apply and
then Commit to store the settings.
7. Reboot the RER601/603 for the settings to take effect.
Figure 1. RER601/603 Configurator screen, Ethernet settings
NOTE: You can check the current network status fro the Network-->Su ary subpage.
ABB www.abb.com/substationautomation 1MRS757426 Rev. A
12
3
4
1
2
3
4

Wireless Gateway RER601/603 3(4)
Quick Start Guide
Method 2: Using serial console
1. Switch off the RER601/603 if necessary
2. Connect a null ode serial cable to console serial connector (RS1)
3. Open a ter inal connection to the RER601/603 using the following serial co unication
settings: 19200-8-N-1, no flow control.
4. Switch on the RER601/603 by turning the power switch to ON position
5. Wait for the text “Hit any key to stop autoboot” and press enter before the counter
goes to zero. If you issed it, just reboot and try again.
6. You are now supposed to be on the PPCBoot console. Figure 2 shows how it looks like.
7. Now enter the following co ands to the console, para eter fields substituted with your
para eters (see figure 2 for exa ple):
setenv ipaddr your_IP_address
setenv netmask your_netmask
setenv gatewayip 0 (By default, GPRS or SSH-VPN is defined as default Gateway)
8. Check that the configuration was entered properly by issuing co and printenv.
9. If everything is correct, save the setting with co and savenv.
10.Reboot the RER601/603 for the settings to take effect.
.
.
.
DRAM: 32 MB
FLASH: 8 MB
In: serial
Out: serial
Err: serial
Net: 00:06:70:01:02:23
Hit any key to stop autoboot: 0
abbrer> setenv ipaddr 192.168.0.50
abbrer> setenv netmask 255.255.0.0
abbrer> setenv gatewayip 0
abbrer> printenv
baudrate=19200
loadaddr=0x20000
...
ipaddr=192.168.0.50
netmask=255.255.0.0
gatewayip=0
Environment size: 407/4092 bytes
Disabling watchdog
abbrer> savenv
Saving Enviroment to EEPROM...
abbrer>
Figure 2. Network parameter configuration using seria conso e
ABB www.abb.com/substationautomation 1MRS757426 Rev. A

Wireless Gateway RER601/603 4(4)
Quick Start Guide
GPRS Network Settings
1. Login to the RER601/603 Configurator (for instructions, see page 2).
2. Navigate to Network page and fro there navigate to GPRS subpage.
3. Set access point na e appropriately (usually INTERNET).
4. Set GPRS network userna e and password appropriately if your GPRS service requires
authentication. Enable “Default Route” setting.
5. Optionally set the PIN code, PPP idle ti eout and ICMP Echo settings (Network-->Monitor
enu) to eet your require ents.
•If your SIM card has PIN code set, type the code to the PIN code field.
•PPP idle ti eout defines the ti e in seconds how ofter the RER601/603 resets the GPRS
connection if the connection is idle.
1. Finally click Apply and then Commit to store the settings.
2. Reboot the RER601/603 for the settings to take effect.
Using the RER601/603 as Wireless Access Point
1. Set your Ethernet device to use the IP address of the RER601/603 as its default gateway.
2. Configure your Ethernet device to be in the sa e network as the RER601/603.
3. Check GPRS Settings. Note that “Default Route” needs to be enabled in GPRS settings.
Final words
It is highly reco ended that the product's Technical Manual be used as reference for opti al
use of this device.
ABB www.abb.com/substationautomation 1MRS757426 Rev. A