RIK 1A Relay Class Integrator
V: 1.0.1 Revised: Nov. 2021
6
www.accuenergy.com
2.3 Conguration
The face of the integrator has a set of dip switches that are used to congure the current range for the current channel. When the dip switch
is in the up position, the dip switch is ON. When the dip switch is in the down position, the dip switch is OFF.
Congure the channel dip switch to output the desired range. For example, to measure current rated for 500A, the dip switches 1 through 5
must be congured to 'OFF', 'OFF', 'ON', 'OFF', 'OFF'. The table below outlines the position of the dip switches for the desired current ranges.
Table 1 - Current Ratio Table
12345
50:1A ON OFF OFF OFF OFF
200:1A OFF ON OFF OFF OFF
500:1A OFF OFF ON OFF OFF
2000:1A OFF OFF OFF ON OFF
5000:1A OFF OFF OFF OFF ON
2.4 Measurements
For each current range, the Integrator will be able to measure the current from 0.5% up to 2000% of the rated current. When the integrator
is congured to measure a current rated for 500A, it will measure the current from 2.5A to 10000A.
The table below provides all the ranges of current that can be measured for each range.
Table 2 - Current Range Congurations
Primary Input (Arms) Sensing Range (A) Output Relay Class Output CT Ratio
50 0.25 to 1000 1A @ 50A 20A @ 1kA 50:1A
200 1 to 4000 1A @ 200A 20A @ 4kA 200:1A
500 2.5 to 10000 1A @ 500A 20A @ 10kA 500:1A
2000 10 to 40000 1A @ 2000A 20A @ 40kA 2000:1A
5000 25 to 100000 1A @ 5000A 20A @ 100kA 5000:1A