AccuEnergy RIK 1AR User manual

RIK 1AR
Relay Class Integrator
User's Manual

II
www.accuenergy.com
V: 1.0.1 Revised: Nov. 2021
Copyright © 2021 V1.0.1
This manual may not be altered or reproduced, in whole or in part, by any means without the expressed written consent of Accuenergy
(Canada) Inc.
The information contained in this document is believed to be accurate at the time of publication, however, Accuenergy (Canada) Inc.
assumes no responsibility for any errors which may appear here and reserves the right to make changes without notice. Please ask the local
representative for latest product specications before ordering.

1
www.accuenergy.com
V: 1.0.1 Revised: Nov. 2021
Please read this manual carefully before installation, operation, and maintenance of the 1AR Rogowski Coil Integrator Kit.
The following symbols in this manual are used to provide warning of the danger or risk during the installation and operation of the unit.
Electric Shock Symbol: Carries information about procedures which must be followed to reduce the risk of electric shock and
danger to personal health.
Safety Alert Symbol: Carries information about circumstances which, if not considered, may result in injury or death.
This mark indicates that this product is UL Listed.
Installation and maintenance of the 1AR Rogowski Coil Integrator Kit should only be performed by qualied, competent professionals who
have received training and show have experience with high voltage and current devices.
Accuenergy (Canada) Inc. shall not be responsible or liable for any damages caused by improper device installation and/or operation.
Product is protected by reinforced insulation
Application Around and removal from UNINSULATED
HAZARDOUS LIVE conductors is permited
WARNING: Disconnect power supply before making electrical connections.
WARNING: Current Transformers (CT’s) should be installed by trained electrician or technician.
WARNING: The secondary circuit of a CT should not be opened when current is owing through the primary circuit.

2
www.accuenergy.com
V: 1.0.1 Revised: Nov. 2021
Table of Contents
Chapter 1: Introduction ...................................................................................................................................... 3
1.1 Overview ............................................................................................................................................................................. 3
1.2 What's Included ................................................................................................................................................................. 3
Chapter 2: Installation......................................................................................................................................... 4
2.1 Hardware Overview ........................................................................................................................................................... 4
2.2 Installation .......................................................................................................................................................................... 5
2.3 Conguration ..................................................................................................................................................................... 6
2.4 Measurements ................................................................................................................................................................... 6
Appendix .............................................................................................................................................................. 7

V: 1.0.1 Revised: Nov. 2021
3
www.accuenergy.com
Chapter 1: Introduction
1.1 Overview
The Relay-Class 1AR Rogowski Integrator Kit (RIK) is designed to provide users with an easy-to-install, plug-and-play solution that can be used
with any protection relay, power meter, or device with a 1A nominal current input. The exibility of Rogowski Coil CTs reduces installation
complexity and is ideal for a variety of applications or unique congurations where spatial constraints may limit the use of rigid-body CT
solutions.
The integrator kit is rated for class 5P20 (IEC 61869-2). This means that if the primary current is 20 times the rated primary current of the
1AR, it will be able to sense and measure the current with an accuracy of 5%. The 1AR is user-congurable and can measure current from
0.25A to 100kA. Additionally, it can be used on systems that operate at both 50Hz and 60Hz further increasing its utility across industries.
1.2 What's Included
The Rogowski Coil Kit includes a single-phase integrator unit with ve, congurable CT ratios for the current input channel and a 24Vdc power
supply to power the integrator. The integrator can be surface-mounted or DIN rail mounted; the power supply is designed to be mounted on
DIN rail. One Rogowski coil (model RCTxx-1000; available in sizes from 16” to 47”) is required to measure the current and is sold separately.
Rogowski Coil Input
One channel for a exible rope-style CT
1A Output
One channel, 1A output
Power On Light
Indicates that the RIK is powered up
Overtemp Light
Indicates that the unit is over the
specied temperature limits
CT Congurator
Five eld congurable CT ratios
Power Supply
24Vdc
Power Supply Input
Power Supply Input (100-240Vac)
Flexible Rogowski Coil
Current Transformer
Model RCTxx-1000 CT; sizes available
from 16” to 47” inches (sold separately)
Coil Input Lead
Rogowski CT lead for connection
with RIK integrator
1
4
7
2
5
8
3
6
9
Chapter 1: Introduction

RIK 1A Relay Class Integrator
V: 1.0.1 Revised: Nov. 2021
4
www.accuenergy.com
Chapter 2: Installation
The installation method is introduced in this chapter. Please read this chapter carefully before beginning installation.
2.1 Hardware Overview
A complete 1AR Rogowski Integrator Kit is comprised of the integrator and power supply mounted on a DIN rail along with one Rogowski coil
(sold separately)
Dimensions:
4.47”(113.5mm)
1.42”(36.0mm)
5.35” (136.0mm)
2.48” (63.0mm)
4.93” (125.2mm)
2.44” (62.0mm)
3.50” (89.0mm)
1.89” (48.0mm)
0.98” (25.0mm)
4.93” (125.2mm)
4.47” (113.5mm)
2.44” (62.0mm)
3.50” (89.0mm)
5.35” (136.0mm)
234
TB2
1
DC OK
+V ADJ.
TB1
123
+
2.48”(63.0mm)

V: 1.0.1 Revised: Nov. 2021
5
www.accuenergy.com
2.2 Installation
The following steps outline the installation process:
1. Connect a Rogowski coil CT (model RCTxx-1000 in any length) to the integrator
2. Wire the 1A output to the protection relay or power meter which will take the signal
The diagram below illustrates how to connect the integrator.
GNDN L
V+ V+ V- V-
24Vdc Output
Power Supply
100-240Vac Input
Power Supply
100-240Vac-24Vdc
Power Supply
1AR
Rogowski Integrator
IN-IN+ S
CH1
Out-
Out+
CH1
Source
Load
+24V GND
Input
The Rogowski coil provides the input to the integrator. Connect the Rogowski coil to the input channel on the integrator. Be sure to observe
the correct wire polarity: the white lead is positive (+) and the brown lead is negative (-).
• Connect the white lead to 'IN+' and the brown lead to 'IN-'. The Shield of the Rogowski coil should be left oating.
• Open the coil by pulling apart the black connector of the CT.
• Install the CT around the conductor to be measured. Verify the CT is installed with the CT facing the same direction as the current ow
direction as indicated by the arrow on the black connector.
• Connect the coil back together.
Output
Connect the output channel to the protection relay or the 1A current input on the power meter.
• The 'OUT+' is to be connected to the positive current terminal of the relay/meter.
• The 'OUT-' is to be connected to the negative current terminal of the relay/meter.
Power Supply
The RIK requires 24Vdc power to operate. The power supply requires a 100-240Vac (50/60Hz) input and outputs 24Vdc to power the
Integrator.
• Connect the input power supply that is between 100-240Vac to the 'L' and 'N' terminals of the power supply.
• Connect the V+ and V- of the power supply to the +24Vdc and GND terminals of the Integrator.
Chapter 2: Installation

RIK 1A Relay Class Integrator
V: 1.0.1 Revised: Nov. 2021
6
www.accuenergy.com
2.3 Conguration
The face of the integrator has a set of dip switches that are used to congure the current range for the current channel. When the dip switch
is in the up position, the dip switch is ON. When the dip switch is in the down position, the dip switch is OFF.
Congure the channel dip switch to output the desired range. For example, to measure current rated for 500A, the dip switches 1 through 5
must be congured to 'OFF', 'OFF', 'ON', 'OFF', 'OFF'. The table below outlines the position of the dip switches for the desired current ranges.
Table 1 - Current Ratio Table
12345
50:1A ON OFF OFF OFF OFF
200:1A OFF ON OFF OFF OFF
500:1A OFF OFF ON OFF OFF
2000:1A OFF OFF OFF ON OFF
5000:1A OFF OFF OFF OFF ON
2.4 Measurements
For each current range, the Integrator will be able to measure the current from 0.5% up to 2000% of the rated current. When the integrator
is congured to measure a current rated for 500A, it will measure the current from 2.5A to 10000A.
The table below provides all the ranges of current that can be measured for each range.
Table 2 - Current Range Congurations
Primary Input (Arms) Sensing Range (A) Output Relay Class Output CT Ratio
50 0.25 to 1000 1A @ 50A 20A @ 1kA 50:1A
200 1 to 4000 1A @ 200A 20A @ 4kA 200:1A
500 2.5 to 10000 1A @ 500A 20A @ 10kA 500:1A
2000 10 to 40000 1A @ 2000A 20A @ 40kA 2000:1A
5000 25 to 100000 1A @ 5000A 20A @ 100kA 5000:1A

V: 1.0.1 Revised: Nov. 2021
7
www.accuenergy.com
Appendix
Table 3 - Key Specications
SPECIFICATIONS
Current Range 0.25A – 100000A
Range 50A, 200A, 500A, 2000A, 5000A rated input (eld
congurable)
Output 0-1A
Nominal Current 1A
Accuracy 1% at 1A, 5% at 20A
Accuracy Limit Factor (ALF) 20
Phase Maximum Error 1 degree
Class 5P20 (IEC 61869-2)
Continuous Thermal Current 150% (1.5A)
Short-Time Thermal Current 20A
Short-Time Thermal Current Maximum Duration 4 seconds
Setting Time to Full Scale <100μs
Operating Temperature -25°C to 70°C / -13°F to 158°C
Overload Protection Thermal
Operating Humidity Non-condensing, 0 to 95% RH
Mounting DIN TS-35/7.5 or 15 (DIN 43880) or Panel
Measurement Channels 1
Frequency Range 50/60Hz
Impedance/Burden 0.25Ω
Nominal Current 1A
Full Scale Maximum Error 1% @ 1A, 5% @ 20A
Certications UL Listed (E359521), CE Mark
Appendix

Revision Date: November 2021
MAKE ENERGY USAGE SMARTER
Accuenergy (Canada) Inc.
2 Lansing Square, Suite 700
Toronto, ON M2J 4P8
Canada
TF: 1-877-721-8908
INT: +1-416-497-4100
FAX: +1-416-497-4130
Accuenergy South Africa (PTY) LTD
Castle Walk Corporate Park,
Block B, Cnr. Nossob & Swakop Street
Erasmuskloof, Pretoria, 0181
South Africa
TF: +27 (0) 87 802 6136
Table of contents
Popular Relay manuals by other brands

Pfeiffer Vacuum
Pfeiffer Vacuum PM 061 372-T operating instructions

Moeller
Moeller ZB12 Series Hardware and engineering

F&F
F&F BIS-413M manual

Siemens
Siemens 3RB24 manual

B.E.G.
B.E.G. LUXOMATnet SA4-230/16/KNX REG Mounting instructions

Rockwell Automation
Rockwell Automation Allen-Bradley Guardmaster MSR55P installation instructions

Weidmüller
Weidmüller TERM Series operating instructions

Woodward
Woodward highprotec MRI4 user manual

Rockwell Automation
Rockwell Automation Allen-Bradley 440R-GL2S2T user manual

Pilz
Pilz PNOZ e4.1p operating manual

Interlogix
Interlogix UltraSync UM-R4 Installation sheet

Pilz
Pilz PNOZ X7P operating manual