AccuLine CNQplus 1000RT User manual

USER MANUAL
Acculine CNQplus-
Rack/Tower 1000/2000/3000VA
ONLINE UPS
2nd Edition, February 2018
UNINTERRUPTIBLE POWER SUPPLY

CONTENTS
1. Safety and EMC Instructions ................................................................. 3
1.1 Installation ............................................................................................... 3
1.2 Operation ................................................................................................ 9
1.3 Maintenance, servicing and faults ........................................................ 10
1.4 Transport ............................................................................................... 13
1.5 Storage ................................................................................................. 13
1.6 Standards .............................................................................................. 14
2. Description of Commonly Used Symbols .......................................... 15
3. Introduction ........................................................................................... 16
4. Panel Description ................................................................................. 17
5. Connection and Operation ................................................................... 19
5.1 Inspection .............................................................................................. 19
5.2 Connection ............................................................................................ 19
5.3 Battery charging .................................................................................... 20
5.4 Turn on the UPS ................................................................................... 20
5.5 Test function ......................................................................................... 21
5.6 Turn off the UPS ................................................................................... 21
5.7 Audible alarm mute function ................................................................. 21
5.8 Operation procedure of external battery connection ............................ 22
6. Operating Modes for All Models .......................................................... 24
6.1 Line mode ............................................................................................. 24
6.2 Battery mode ......................................................................................... 25
6.3 Bypass mode ........................................................................................ 25
6.4 NO output mode .................................................................................... 26
6.5 EPO (Emergency Power Off) ................................................................ 26
6.6 ECO mode (Economy mode) ................................................................ 26
6.7 Converter mode .................................................................................... 27
6.8 Abnormal mode ..................................................................................... 27
7. Setting by LCD Module ........................................................................ 28
8. Trouble Shooting .................................................................................. 31
9. Maintenance .......................................................................................... 34
9.1 Operation .............................................................................................. 34
9.2 Storage ................................................................................................. 34

9.3 Battery Replacement ............................................................................ 34
10. Technical Data ..................................................................................... 35
10.1 Electrical specifications ....................................................................... 35
10.2 Operating Environment ....................................................................... 35
10.3 Typical backup time (Typical values at 25°C in minutes:)....................... 35
10.4 Dimensions and weights ....................................................................... 36
11. Communication ................................................................................... 37
11.1 RS-232 and USB communication ports .............................................. 37
11.2 RS-232 port ......................................................................................... 37
11.3 USB port ............................................................................................. 38
11.4 Installing the Network Management Card (optional) .......................... 38
11.5 Dry Contact port .................................................................................. 38
12. Software ............................................................................................... 40
Appendix: Rear panel ............................................................................... 41

3
1. Safety and EMC Instructions
1.1 Installation
Read installation instructions before connecting to the mains.
Condensation may occur if the UPS is moved directly from a cold to a
warm environment. The UPS must be absolutely dry before being
installed. Please allow an acclimatization time of at least two hours.
Do not install the UPS near water or in a damp environment.
Do not install the UPS where it would be exposed to direct sunlight or
near heat.
Do not connect appliances or items of equipment which would overload
the UPS (e.g. laser printers, etc) to the UPS output.
Place cables in such a way that no one can step on or trip over them.
Assure that the UPS is firmbly placed on earth.
Assure that the external battery source is connected to earth.
Connect the UPS only to a ground-connected shockproof socket outlet.
The building wiring socket outlet (shockproof socket outlet) must be
easily accessible close to the UPS.
With the installation of the equipment, the sum of the leakage current of
the UPS and the connected load must not exceed 3.5mA.
Do not block ventilation openings in the UPS housing. Ensure that the
air vents on the front and rear of the UPS are not blocked. Allow at
least 25cm of space on each side.
Loads and Battery Cabinets connect to the ground through UPS input
power cord. When installing final system configuration, make sure that
all battery cabinets are ground-connected via earth terminals (earth line
ports) and that all loads are connected to the UPS outlets before
switching it on.
An appropriate disconnecting device such as short-circuit backup
protection should be provided in the building wiring installation.
1.1.1 Inspection of Unit
Inspect the UPS upon receiving. If the UPS has been apparently damaged
during shipment, please keep the box and packing material in original form
and notify the carrier and/or dealer immediately.
Please read carefully the following user manual and the safety
instructions before installing the unit or using it!

4
1.1.2 Unpacking the Cabinet
To unpack the system:
1. Open the outer carton and remove the accessories packaged with the
cabinet.
2. Carefully lift the cabinet out of the outer carton and set it on a flat, stable
surface.
3. Discard or recycle the packaging in a responsible manner, or store it for
future use.
1.1.3 UPS Setup
CNQplus RT series are designed for both tower and rack mount set up.
They can be installed into a 19 inches rack. Please follow the instructions for
Tower Setup and Rack-Mount Setup.
Tower setup
CNQplus RT series can be placed horizontally and vertically. As a tower
configuration, the appropriate UPS stands are provided in the package to
stabilize the UPS when it is positioned vertically. The UPS stands must be
attached to the bottom of the tower. Use the following procedure to install UPS
in UPS stands.
1. Slide down the UPS vertically and put two UPS stands at the end of the tower.
2. Place down the UPS into the two stands carefully.
3. Pull out the LCD box and rotate it in a clockwise direction to 90 degree and
then push it back in the front panel

5
Rack-mount setup
CNQplus RT series can be installed in 19 inches racks. Both the UPS and each
external battery enclosure need 2U of rack space.
Use the following procedure to install UPS in a rack.
1. Align the mounting ears with screw holes on the side of the UPS, and tighten
the screws.
2. Assemble the rack rails onto the rack-mounting.
3. Slide in the UPS into the rack rail and lock it inside the Rack-mounting.
4. Tighten the screws, and then the load can be connected.
1.1.4 EBM Installation (Optional)
UPS Acculine CNQplus series include external battery port that allows users
to connect multiple EBMs in order to provide additional backup time. Follow
the below procedure to install one or multiple EBM.
Connecting one EBM in Tower form:
1. Slide down both the UPS and the EBM vertically and place two UPS stands
with the extension parts at the end of the tower.

6
2. Tighten the screws on the metal sheet for stabilization
3. Connect the Earth line from the UPS (port A ) to EBM (port B)
4. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. Users need to remove the small gate
(C) on side of the front panel to allow the outlet wire of the EBM to pass
through the gate and then reassemble front panel.
B
A
C
B
A

7
Connecting one EBM in a rack form
1. Using the same method as assembling the UPS in a rack form, assemble
EBM into the rack-mounting on the top or bottom of the UPS.
2. Connect the earth line from UPS (port A ) to EBM (port B )
3. Take off the LCD box, and unscrew the internal screws.
4. Take off the front panel, and connect the battery terminal (A) from the UPS
to EBM terminal (B) shown as below. Users need to remove the small
gate(C) on side of the front panel to allow the outlet wire of the EBM to pass
through the gate and then reassemble front panel.
5. After installing the into the rack, the load can then be connected to the
UPS. Please make sure the load equipment is turned off before plugging all
loads into the UPS output receptacles
A
B
BA
C
Unscrew
Unscrew

8
Connecting multiple EBMs in Tower form
1. Connect Earth line between the UPS and the first EBM, then connect the
Earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from the UPS
to EBM terminal (B) shown as below. hen connect the battery terminal (D)
of the first EBM to the battery terminal (E) of the second EBM. Users need
to remove the small gate(C) on side of the front panel to allow the outlet
wire of the EBM to pass through the gate and then reassemble front panel.
Connecting Multiple EBMs in rack form
1. Connect the earth line between the UPS and the first EBM, and then
connect the earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to
EBM terminal (B) shown as below. hen connect the battery terminal (D)
from the first EBM to the battery terminal (E) from the second EBM. Users
need to remove the small gate (C) on side of the front panel to allow the
outlet wire of the EBM to pass through the gate and then reassemble front
panel.
B
C
A
E

9
Note: Three or more EBMs can be connected to the UPS in the same way as
shown above.
Note: After connecting the EBMs, please do not forget to set the number of
EBMs via the LCD menu
for setting procedure. If you are using non-standard EBMs, please call local
dealer or distributor for setting method.
1.2 Operation
Do not disconnect the mains cable from the UPS or the building wiring
socket (ground-connected shockproof socket) during operation as this
would suspend ground connection of the UPS and all connected loads
and EBMs.
The UPS features its own, internal current source (batteries). You may be
electric shocked when you touch the UPS output sockets or output
terminal block even if the UPS is not connected to the building wiring
socket.
In order to fully disconnect the UPS, first press the OFF button to turn off
the UPS, then disconnect UPS from the mains.
Ensure that no liquid or other foreign objects can enter the UPS.
Do not remove the enclosure. This system is to be serviced by qualified
service personnel only.
Remove the protective panel only after disconnecting the terminal
connections.
For CNQplus-3000SRT input wire, use 90 C copper wire 3 x 4 mm² and
0,5 N-m (4.4 lb-in) Torque force when connecting to terminal block.
E
B
A
D

10
For battery wire for all models, use 90 C copper wire 3 x 6 mm² and
Anderson PP45 connectors for user external battery cabinet.
1.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Repairs may be carried out
only by qualified maintenance personnel.
CAUTION - risk of electric shock: Even after the unit is disconnected from
the mains power supply (building wiring socket), components inside the
UPS are still connected to the battery and are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect
the batteries. Verify that no current is present and no hazardous voltage
exists in the capacitor or BUS capacitor terminals.
CAUTION - risk of electric shock: The battery circuit is not isolated from
the input voltage. Hazardous voltages may occur between the battery
terminals and the ground. Verify that no voltage is present before
servicing!
Batteries must be replaced only by qualified personnel in compliance with
the directions given in paragraph 1.3.3.
Please replace the fuse only by a fuse of the same type and of the same
amperage in order to avoid fire hazards.
Do not dismantle the UPS, unless you are qualified maintenance
personnel.
1.3.1 UPS and Battery Care
For best preventive maintenance results, keep the area around the UPS clean
and dust-free. If the atmosphere is very dusty, clean the outside of the system
with a vacuum cleaner. For long battery life, keep the UPS in an ambient
temperature of 25°C (77°F)
1.3.2 Storing the UPS and Batteries
When the UPS is intended to be stored for a long period, recharge the battery
every 6 months by connecting the UPS to utility power. The batteries charge
to 90% capacity in approximately 4 hours. However, it is recommended that
the batteries charge for 48 hours after long-term storage.

11
1.3.3 Time to Replace Batteries
When the discharging time after full charging is less than 50% of the specified
back-up time, the batteries may need to be replaced. Please contact your
local dealer to order new battery.
WARNING:
Turn off the UPS and disconnect the utility power cord from the wall outlet.
Servicing should be performed by qualified service personnel
knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries
Batteries can present a risk of electrical shock or burn from high short
circuit current. The following precautions should be taken:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Do not lay tools or metal parts on top of batteries.
4. Wear rubber gloves and boots.
5. Disconnect the charging source prior to connecting or disconnecting
battery terminal.
When replacing batteries, replace with the same type and number of
batteries or battery packs. Contact your service representative to order new
batteries.
Do not dispose of battery in a fire. Batteries may explode when exposed to
flame.
Proper disposal of batteries is required. Refer to your local regulations for
disposal requirements.
Do not open or mutilate the battery. Released toxic electrolyte is harmful to
skin and eyes.
1.3.4 Replacing UPS Internal Batteries
Follow the steps below to replace batteries:
1. Take off the LCD box, and remove the screws.
2. Slide and pull the front panel leftwards to take it off.
3. Disconnect the cable from the UPS and battery pack.
Note: If you are not qualified service personnel do not attempt to open the
UPS or EBM to replace the battery. Please call local dealer or distributor
immediately.

12
4. Remove the inner battery bracket on the right side.
5. Pull the battery pack out onto a flat area.
6. Install the new battery pack into the UPS.
7. Screw the battery bracket back on its place and reconnect the battery cable
A and B
8. Re-install the front panel on the UPS.
1.3.5 Testing New Batteries
Before testing the Batteries, please check that:
The batteries are fully charged.
The UPS is in Normal mode with no active alarms.
The load on the UPS output is not variable.

13
To test the batteries:
1. Connect the UPS to utility power for at least 48 hours to charge the
batteries.
2. Press and hold the I button 1 second to start the battery test on line mode
or HE mode. The status display string shows TEST
1.3.6 Recycling the Used Battery:
To recycle the used battery properly, please do not discard the UPS, battery
pack and batteries with ordinary trash. Please follow your local laws and
regulations; you may contact your local recycling waste management center
for further information to dispose of the used UPS, battery pack, and batteries
properly.
1.4 Transport
Please transport the UPS only in the original packaging (to protect against
shock and impact).
1.5 Storage
The UPS must be stockpiled in a ventilated and dry environment.
Warning:
Never dispose of batteries in fire. They may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the
skins and eyes. It may be toxic.
Batteries can present a risk of electrical shock and high short circuit
current.

14
1.6 Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission..........................:IEC/EN 62040-2 Category C1
Radiated Emission.............................:IEC/EN 62040-2 Category C1
Harmonic Current...............................:IEC/EN 61000-3-2
Voltage Fluctuation and Flicker..........:IEC/EN 61000-3-3
*EMS
ESD...................................................:IEC/EN 61000-4-2 Level 3
RS.....................................................:IEC/EN 61000-4-3 Level 3
EFT....................................................:IEC/EN 61000-4-4 Level 4
SURGE.............................................:IEC/EN 61000-4-5 Level 4
...:IEC/EN 61000-4-6 Level 3
..: IEC/EN 61000-4-8 Level 3
-4-11
Low Frequency Signals.....................:IEC/EN 61000-2-2

15
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is suggested
that you familiarize yourself with them and understand their meaning:

16
3. Introduction
CNQplus RT serries consist of uninterruptible power supply systems
incorporating double-converter technology. They provide perfect protection
especially for Novell, Windows NT and UNIX servers.
The double-converter principle eliminates all mains power disturbances. A
rectifier converts the alternating current from the socket outlet to direct
current. This direct current charges the batteries and powers the inverter. On
the basis of this DC voltage, the inverter generates a sinusoidal AC voltage,
which permanently supplies the loads.
Computers and peripherals are thus powered entirely by the mains voltage.
In the event of power failure, the maintenance-free batteries power the
inverter.
This manual covers the UPS listed below. Please confirm whether this is the
model you intended to purchase by performing a visual inspection of the
Model No. on the rear panel of the UPS.
Extended backup time
CNQplus Type CNQplus Type
1000RT
Standard
1000SRT Extended backup
time
2000RT 2000SRT
3000RT 3000SRT

17
4. Panel Description
The Display Panel
Switch Function
ON-Button Turns on UPS system: By pressing the ON-
system is turned on.
Deactivates acoustic alarm: By pressing this Button an acoustic
alarm can be deactivated in battery mode. Byinstantly touching
this Button all acoustic alarms can be deactivated in all modes.
By pressing this Button the UPS can perform
battery test in Line mode or ECO mode or Converter mode.
OFF-Button When mains power is normal, the UPS system switches to No
output or Bypass mode by pressing OFF-
inverter is off. At this status, if Bypass is enabled and the mains
power is available, the output sockets are supplied with voltage
via the bypass.
Deactivates acoustic alarm: By pressing this Button an acoustic
alarm can be deactivated in bypass mode.
Releases the UPS from fault mode and EPO status.
Select-Button The output voltage & frequency, Bypass disable/enable,
operating mode in No output or Bypass mode, Two Load
segments in output mode, The number of EBM in all modes, can
be selected by pressing Select-Button, and confirmed by
pressing Enter-Button.
Enter-Button
LCD Scree
n
ON Button/
Alarm Silence
OFF-Button Select-Button Enter-Button

18
The LCD Display
Display Function Display Function
Input Information Output Information
Indicates the input
voltage/frequency value,
which are displayed
alternatively.
Indicates the output
voltage/frequency value,
which are displayed
alternatively.
Indicates that the input is
connected to the mains,
and the input power is
supplied from the mains.
Indicates the Output plug.
Indicates the input
phases available. With
the mains present,
Indicates the load
when segment 2 is active,
segments are powering
the loads.
Battery Information Load Information
Indicates the battery
capacity. Every grid
represents 20% of the
total battery capacity.
Indicates the load level.
Every grid represents 20%
of the nominal UPS power.
Mode/Fault/Warning Information Else
Indicates the operating
mode or the kind of Fault
or Warning. Several
warnings could be
displayed alternatively.
Indicates that the UPS is
in setting mode.
Indicates that the UPS is
in Fault mode or that there
is a warning indication.

19
5. Connection and Operation
5.1 Inspection
Inspect the packaging carton and its contents for damage. Please inform the
transport agency or dealer immediately should you find signs of damage.
Keep the packaging in a safe place for future use.
5.2 Connection
(1) UPS Input Connection
If the UPS is connected via power cord, please use a socket with proper
protection against electric current, (refer to below table). If the UPS is
connected via wires, it is recommended to use a 3 x 4 mm2 wire, connecting
the GND terminal first.
The UPS System has no input breaker on the standard cabinet. When
installing the UPS, the user needs to connect any external breakers and
protective components in the input terminals.
(2) UPS Output Connection
The output of the UPS is IEC socket-types. Simply plug the load power cord
to the output sockets to complete connection. Use one cord for every 5A
load.
CNQplus Output Socket (pcs)
1000RT(S)/ 2000RT(S) 8 * IEC320 C13
3000RT(S) 8 * IEC320 C13 + 1 * C19
Electrical installations and wirings should be done only by qualified
electricians in accordance with applicable safety regulations!
When installing electrical wirings, pay attention to the nominal
amperage of your incoming feeder.
Caution:
Do not connect equipment which would overload the UPS system (e.g. laser
printers)
This manual suits for next models
5
Table of contents
Other AccuLine UPS manuals
Popular UPS manuals by other brands

Powerware
Powerware Uninterruptible Power Supply Installation and operation manual

INFOSEC UPS SYSTEM
INFOSEC UPS SYSTEM X1 EX Series user guide

Avaya
Avaya 9135 6000 VA Installation and operator's manual

INFOSEC UPS SYSTEM
INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series manual

Huawei
Huawei UPS5000-A series quick guide

Sanyo Denki
Sanyo Denki Sanups A11J instruction manual