1

Quick Start Guide
AFM5000AirFlowMonitorforAVC5000ControllerCoversModels:AFM5000‐xxx&AFM5001‐xxx
This Quick Start Guide provides the basic steps required
for the installation, wiring and start-up of the AFM5000
and the AFM5001 Air Flow Monitors, when used with the
AccuValve AVC5000 controller. For details, refer to the
individual product Submittal Drawings, User Manuals and
Job-Specific Requirements.
APPLICATION
The AFM5000 connects directly to the
AccuValve AVC5000 control module and
gives the user a local Airflow Volume
Display and Alarm Indication. The
AFM5000 also gives the user the ability
to “plug in” to the AVC5000 controller
remotely to monitor and adjust the
AVC5000 using Accutrol’s Insight User
Interface from a convenient location.
The AFM5000 can also be provided with
a set point adjustment dial to change the
airflow set point in the AVC controller.
WIRING
Route the Monitor Cable from the back of the electrical box to
the location of the AVC5000 control enclosure and insert the
Monitor Cable into the Monitor Cable receptacle. Anchor the
cable to the strain relief with a cable tie.
For applications using the AFM5001, the yellow pig tail on the
Monitor Cable is connected to AI-1 (+). The jumper for AI-1 is
set to “R” to configure the input.
INSTALLATION
The AFM5000 is designed to be installed into a single-gang
electrical box, with the minimum internal dimensions of 3.825”H
x 2.35”W to accommodate the set point adjustment knob on the
AFM5001 and the additional wires.
Once the properly sized box is
installed, route the Monitor Cable
into the electrical box and use a
strain relief to prevent the cable
from being damaged. In the case
where an AFM5001 is installed,
connect the yellow pigtail on the
end of the cable with a wire nut
to the yellow wire that extends
from the back of the display
module.
Secure the AFC5000 to the
electrical box using the two
screws provided.
Connections to the AVC5000 Control Module will vary
depending on the application requirements. The diagram
below is provided as a general reference only. For detailed
wiring requirements, refer to the job specific submittal wiring
diagrams and AVC5000 Manual.
START UP
Before proceeding with start-up, verify the following
items have been completed:
 All installation has been completed and verified.
 All wiring has been completed and verified.
 Power is present at the AVC5000 and verified to spec.
 System is operating with static pressure control.
 The configuration PC has Insight loaded and operational.
AFMQUICKSTARTGUIDE—NOVEMBER2015
www.accutrolllc.com
WIRINGDETAILforAFM5001‐XXX
2

Connect PC to AFM5000
Verify the
Mode of
Operation is SETPOINT
MODE
(Jumper position)
In the MODE OF
OPERATION window above:
 Select whether the set point is
coming from AI-1, Dry Contact, or BACnet Communications.
 If ANALOG (AI-1), Select Analog signal (be sure to
configure input at AVC5000 by moving JP-3 as described).
 For AFM5001, ANALOG AI-1 is set up for Resistor (R)
 Select the range of the set point signal in the bottom
window.
In the CONTROL OUTPUT window
above:
 With the OVERRIDE
button, Select
MANUAL and a value
in % to force the
actuator to a specific
position, (the gage
face will go red).
 Go to OVERRIDE and select AUTO to release control, (the
gage face will go back to normal).
In the TUNING window above:
 Adjust the Deadband%, Gain (P) and the
Integral (I) to address tuning.
 Adjust the OFFSET or differential in a
tracking valve application
In the ALARM window above:
 Enable and Disable Alarms
 Select Airflow Volume Alarm or Set Point Deviation
Alarm
 Enter values and delays
In the A0-1 and AO-2 Window on the right:
 Configure the AO Signals to Voltage or Current
 Set either for Volume or Output position
 Manually operate the Outputs to a value for trouble shooting
Remove the rubber port plug
to access the AFM5000 USB
Port.
Plug USB Mini Cable from PC into
the AFM5000 USB Port.
Open the AVC Insight
UI Program.

Other manuals for AVC5000

1

This manual suits for next models

1

Other Accutrol Monitor manuals

Accutrol Apex Premier Instruction manual

Accutrol

Accutrol Apex Premier Instruction manual

Popular Monitor manuals by other brands

Eizo FlexScan L465 Brochure & specs

Eizo

Eizo FlexScan L465 Brochure & specs

Daewoo 901D Service manual

Daewoo

Daewoo 901D Service manual

Samsung SyncMaster 710T user manual

Samsung

Samsung SyncMaster 710T user manual

Roland CS-10 owner's manual

Roland

Roland CS-10 owner's manual

JVC BM-H1900SU - Color Production Monitor instructions

JVC

JVC BM-H1900SU - Color Production Monitor instructions

LUMAHAWK LMM-CON300 Instructions for setup

LUMAHAWK

LUMAHAWK LMM-CON300 Instructions for setup

Ikan D5 quick start guide

Ikan

Ikan D5 quick start guide

Interlogix TVM-2700 user manual

Interlogix

Interlogix TVM-2700 user manual

TIME MARK 24 quick start guide

TIME MARK

TIME MARK 24 quick start guide

Samsung SyncMaster 2043BW user manual

Samsung

Samsung SyncMaster 2043BW user manual

Sony Trinitron CPD-G200 Service manual

Sony

Sony Trinitron CPD-G200 Service manual

Acer ET322QK user guide

Acer

Acer ET322QK user guide

Commodore AMIGA 1081 manual

Commodore

Commodore AMIGA 1081 manual

Sanyo PDP-42H1EN owner's manual

Sanyo

Sanyo PDP-42H1EN owner's manual

Acer ET430K user guide

Acer

Acer ET430K user guide

NEC MultiSync PA322UHD user manual

NEC

NEC MultiSync PA322UHD user manual

Barco OverView EVD­4621 Features

Barco

Barco OverView EVD­4621 Features

ST AN3311 Instruction

ST

ST AN3311 Instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.