aci ASA Series Installation instructions

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 1
Version: 6.0
I0000602
FIGURE 1: DIMENSIONS
ANALOG SIGNAL AMPLIFIER
SERIES
Installation & Operation Instructions
Phone: 1-888-967-5224
Website: workaci.com
GENERAL INFORMATION
The ASA is an analog signal amplier which
accepts an analog (voltage or current) signal and
outputs a voltage signal. Several preset input
ranges are jumper selectable. It is designed to give
a Building Automation System signal output the
power (wattage) to control Maxitrol™ Gas Valves
normally installed in rooftop units. The top-adjust
trimmer potentiometers can be used to make ne
adjustments of gain and oset. The output gain
can be adjusted anywhere from 1 to 20 times the
input on the ASA (gain will vary depending on
type of input). By using voltage divider
applications, the ASA can also accept a resistance
input. The oset of the output can be +/- 0 to 20
VDC. If above 30 watts, derate load current and
calculate again (P out = [(V out/Load) (V out)]
and/or (P out = (Load Current)(V out)). The ASA is
eld calibratable, however, factory calibration is
available upon request for an additional charge.
This will speed up installation time for the end
user.
MOUNTING INSTRUCTIONS
Circuit board may be mounted in any position. If
circuit board slides out of snap track, a
non-conductive “stop” may be required. Use only ngers to remove board from snap track. Slide out of
snap track or push against side of snap track and lift that side of the circuit board to remove. Do not ex
board or use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both
ends can cause a ground loop.
• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may
result in damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or
other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC
Transorb or diode, connects to the positive side of the power supply. Without these snubbers,
coils produce very large voltage spikes when de-energizing that can cause malfunction or
destruction of electronic circuits.
• All wiring must comply with all local and National Electric Codes.
2.90” (73.78mm)
3.25”
(82.55mm)
3.25”
(82.55mm)
2.70” (68.58mm)
0.70”
(17.78mm)
FACTORY CALIBRATION
The ASA is set as follows:
Voltage Input Signal
No Oset to the Output Signal
Input to Output Signal Gain (1:1)
The ASA can be ordered calibrated to your specications or you may follow the procedure below to set
your own calibration.
Be sure to check the input, output, GAIN and OFFSET specications of the ASA. It is possible that the ASA
cannot re-scale to your requirements.
CHECKOUT
Complete the following steps to change the calibration of the ASA. You will need a digital volt/current
meter, a 24 to 30 VDC or VAC power supply and a voltage input signal simulator.
EQUIVALENT CALIBRATION VOLTAGE
Use a voltage signal for your input signal during calibration: this makes both the procedure and the
explanation easier. If you will require a current input when you are nished, use the equation below to nd
the equivalent calibration voltage to use during the calibration procedure:
Equivalent Calibration Voltage = Required Input Signal Amps x 250
Example: 1 VDC is the equivalent calibration voltage for a 4 mA input signal (1= .004 x 250) or 5VDC is the
equivalent calibration voltage for a 20 mA input signal (5=.020 x 250).
Step 1) Trim Pot Presets
Set all pots as follows to start (These are 25 turn trim pots with no hard stops; they may make a slight
clicking sound at either end of their range):
Turn the GAIN pot Full Counterclockwise: = Gain of 1
Turn the OFFSET pots Fully Clockwise: = 0 volts oset
Step 2) Jumper Shunt Presets
J1 IN - INCOMING SIGNAL: Set in “E” position for voltage input.
If you require a current input, you will set this shunt in the “I” position
AFTER you are nished with the calibration procedure.
J2 - OFFSET: Set in the ‘O’ position for no oset to the output. If you will require a (+)
or (-) oset, you will set this shunt in the appropriate position in Step 6
Step 3) Wiring Connections
Make the following connections with the power OFF :
Connect a 24 to 30 VDC or VAC power supply (see power supply information on specications or
detail at bottom of page 3 instructions ) to the ASA terminals (+) and COM.
Connect the (-) input signal to the IN (-) terminal.
Connect the (-) meter lead to the OUT (-) terminal.
Connect (+) input signal lead to the IN (+) terminal.
Connect (+) meter lead to the OUT (+) terminal.
Step 4) Power Up
Turn on the power supply: the POWER indicator will light
Step 5) Set-Up- Input / Output Signal Adjustments
In this step you will gure the desired voltage/current input signal span and the desired voltage output
signal span and calibrate the ASA to these input and output signal spans.
To calculate the voltage/current input signal span, subtract the minimum voltage/current input signal from
the maximum input signal (i.e. a 0 to 5 volt input signal will give you a 5 volt input signal span: 5-0=5).
To calculate the voltage output signal span, subtract the minimum voltage output signal from the
maximum voltage output signal (i.e. a 3 to 15 volt output signal will give you a 12 volt output signal span:
15-3=12).
Take the number for the voltage input signal span and apply this voltage to the “IN” (+) and (-) terminals.
Compare the output voltage reading on your meter with the voltage output signal span you calculated
about. If the meter is higher or lower, adjust the “GAIN” potentiometer until the meter reads the calculated
output signal span.
Step 6) Oset Adjustments
The oset adjustments simply shift the output signal range up or down from a “no oset” setting. For
example, an output signal range with “no oset” is 3 to 15 volts. The maximum oset range is +/- 0 to 20
VDC.
Adding an oset of 2 volts would make the output signal range 5 to 17 volts. Subtracting an oset of 2 volts
would make the output signal range 1 to 13 volts.
Apply the minimum voltage input signal and read the minimum output signal on the meter. With the
“OFFSET” jumper shunt “J2” in the “0” position, no oset will be added or subtracted from the output signal
range.
If you need to shift the output signal range up, set the “OFFSET” jumper shunt “J2” in the “+” position and
adjust the “OFFSET” potentiometer until you increase the voltage reading on the meter to match the
desired minimum output voltage.
(Remember, this also increases the maximum output by the same amount.)
If you need to shift the output signal range down, set the “OFFSET” jumper shunt “J2” in the “-” position and
adjust the “OFFSET” potentiometer until you decrease the voltage reading on the meter to match the
desired minimum output voltage.
(Remember, this also decreases the maximum output by the same amount.)
Step 7) Final Adjustments
If you require a current input, set the “J1” IN jumper shunt in the “I” position. Check operation of the ASA for
desired signal rescaling and operation.

FIGURE 2: WIRING
GENERAL INFORMATION
The ASA is an analog signal amplier which
accepts an analog (voltage or current) signal and
outputs a voltage signal. Several preset input
ranges are jumper selectable. It is designed to give
a Building Automation System signal output the
power (wattage) to control Maxitrol™ Gas Valves
normally installed in rooftop units. The top-adjust
trimmer potentiometers can be used to make ne
adjustments of gain and oset. The output gain
can be adjusted anywhere from 1 to 20 times the
input on the ASA (gain will vary depending on
type of input). By using voltage divider
applications, the ASA can also accept a resistance
input. The oset of the output can be +/- 0 to 20
VDC. If above 30 watts, derate load current and
calculate again (P out = [(V out/Load) (V out)]
and/or (P out = (Load Current)(V out)). The ASA is
eld calibratable, however, factory calibration is
available upon request for an additional charge.
This will speed up installation time for the end
user.
MOUNTING INSTRUCTIONS
Circuit board may be mounted in any position. If
circuit board slides out of snap track, a
non-conductive “stop” may be required. Use only ngers to remove board from snap track. Slide out of
snap track or push against side of snap track and lift that side of the circuit board to remove. Do not ex
board or use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both
ends can cause a ground loop.
• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may
result in damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or
other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC
Transorb or diode, connects to the positive side of the power supply. Without these snubbers,
coils produce very large voltage spikes when de-energizing that can cause malfunction or
destruction of electronic circuits.
• All wiring must comply with all local and National Electric Codes.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
Version: 6.0
I0000602
FACTORY CALIBRATION
The ASA is set as follows:
Voltage Input Signal
No Oset to the Output Signal
Input to Output Signal Gain (1:1)
The ASA can be ordered calibrated to your specications or you may follow the procedure below to set
your own calibration.
Be sure to check the input, output, GAIN and OFFSET specications of the ASA. It is possible that the ASA
cannot re-scale to your requirements.
CHECKOUT
Complete the following steps to change the calibration of the ASA. You will need a digital volt/current
meter, a 24 to 30 VDC or VAC power supply and a voltage input signal simulator.
EQUIVALENT CALIBRATION VOLTAGE
Use a voltage signal for your input signal during calibration: this makes both the procedure and the
explanation easier. If you will require a current input when you are nished, use the equation below to nd
the equivalent calibration voltage to use during the calibration procedure:
Equivalent Calibration Voltage = Required Input Signal Amps x 250
Example: 1 VDC is the equivalent calibration voltage for a 4 mA input signal (1= .004 x 250) or 5VDC is the
equivalent calibration voltage for a 20 mA input signal (5=.020 x 250).
Step 1) Trim Pot Presets
Set all pots as follows to start (These are 25 turn trim pots with no hard stops; they may make a slight
clicking sound at either end of their range):
Turn the GAIN pot Full Counterclockwise: = Gain of 1
Turn the OFFSET pots Fully Clockwise: = 0 volts oset
Step 2) Jumper Shunt Presets
J1 IN - INCOMING SIGNAL: Set in “E” position for voltage input.
If you require a current input, you will set this shunt in the “I” position
AFTER you are nished with the calibration procedure.
J2 - OFFSET: Set in the ‘O’ position for no oset to the output. If you will require a (+)
or (-) oset, you will set this shunt in the appropriate position in Step 6
Step 3) Wiring Connections
Make the following connections with the power OFF :
Connect a 24 to 30 VDC or VAC power supply (see power supply information on specications or
detail at bottom of page 3 instructions ) to the ASA terminals (+) and COM.
Connect the (-) input signal to the IN (-) terminal.
Connect the (-) meter lead to the OUT (-) terminal.
Connect (+) input signal lead to the IN (+) terminal.
Connect (+) meter lead to the OUT (+) terminal.
Step 4) Power Up
Turn on the power supply: the POWER indicator will light
Step 5) Set-Up- Input / Output Signal Adjustments
In this step you will gure the desired voltage/current input signal span and the desired voltage output
signal span and calibrate the ASA to these input and output signal spans.
To calculate the voltage/current input signal span, subtract the minimum voltage/current input signal from
the maximum input signal (i.e. a 0 to 5 volt input signal will give you a 5 volt input signal span: 5-0=5).
To calculate the voltage output signal span, subtract the minimum voltage output signal from the
maximum voltage output signal (i.e. a 3 to 15 volt output signal will give you a 12 volt output signal span:
15-3=12).
Take the number for the voltage input signal span and apply this voltage to the “IN” (+) and (-) terminals.
Compare the output voltage reading on your meter with the voltage output signal span you calculated
about. If the meter is higher or lower, adjust the “GAIN” potentiometer until the meter reads the calculated
output signal span.
Step 6) Oset Adjustments
The oset adjustments simply shift the output signal range up or down from a “no oset” setting. For
example, an output signal range with “no oset” is 3 to 15 volts. The maximum oset range is +/- 0 to 20
VDC.
Adding an oset of 2 volts would make the output signal range 5 to 17 volts. Subtracting an oset of 2 volts
would make the output signal range 1 to 13 volts.
Apply the minimum voltage input signal and read the minimum output signal on the meter. With the
“OFFSET” jumper shunt “J2” in the “0” position, no oset will be added or subtracted from the output signal
range.
If you need to shift the output signal range up, set the “OFFSET” jumper shunt “J2” in the “+” position and
adjust the “OFFSET” potentiometer until you increase the voltage reading on the meter to match the
desired minimum output voltage.
(Remember, this also increases the maximum output by the same amount.)
If you need to shift the output signal range down, set the “OFFSET” jumper shunt “J2” in the “-” position and
adjust the “OFFSET” potentiometer until you decrease the voltage reading on the meter to match the
desired minimum output voltage.
J1
IVI
J1
V
Voltage
Signal
Input
Current
Signal
Input
+
-
J2
No Oset Positive
Oset
Negative
Oset
(+)
(-)
(+)
(-)
(-)
(+)
0
+
-
J2
0
+
-
J2
0
Analog Input Signal Analog Output Signal (up to 2 Amps, or 30 watts power)
24 VAC/VDC
Power Supply
(Remember, this also decreases the maximum output by the same amount.)
Step 7) Final Adjustments
If you require a current input, set the “J1” IN jumper shunt in the “I” position. Check operation of the ASA for
desired signal rescaling and operation.

GENERAL INFORMATION
The ASA is an analog signal amplier which
accepts an analog (voltage or current) signal and
outputs a voltage signal. Several preset input
ranges are jumper selectable. It is designed to give
a Building Automation System signal output the
power (wattage) to control Maxitrol™ Gas Valves
normally installed in rooftop units. The top-adjust
trimmer potentiometers can be used to make ne
adjustments of gain and oset. The output gain
can be adjusted anywhere from 1 to 20 times the
input on the ASA (gain will vary depending on
type of input). By using voltage divider
applications, the ASA can also accept a resistance
input. The oset of the output can be +/- 0 to 20
VDC. If above 30 watts, derate load current and
calculate again (P out = [(V out/Load) (V out)]
and/or (P out = (Load Current)(V out)). The ASA is
eld calibratable, however, factory calibration is
available upon request for an additional charge.
This will speed up installation time for the end
user.
MOUNTING INSTRUCTIONS
Circuit board may be mounted in any position. If
circuit board slides out of snap track, a
non-conductive “stop” may be required. Use only ngers to remove board from snap track. Slide out of
snap track or push against side of snap track and lift that side of the circuit board to remove. Do not ex
board or use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both
ends can cause a ground loop.
• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may
result in damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or
other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC
Transorb or diode, connects to the positive side of the power supply. Without these snubbers,
coils produce very large voltage spikes when de-energizing that can cause malfunction or
destruction of electronic circuits.
• All wiring must comply with all local and National Electric Codes.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 3
Version: 6.0
I0000602
FACTORY CALIBRATION
The ASA is set as follows:
Voltage Input Signal
No Oset to the Output Signal
Input to Output Signal Gain (1:1)
The ASA can be ordered calibrated to your specications or you may follow the procedure below to set
your own calibration.
Be sure to check the input, output, GAIN and OFFSET specications of the ASA. It is possible that the ASA
cannot re-scale to your requirements.
CHECKOUT
Complete the following steps to change the calibration of the ASA. You will need a digital volt/current
meter, a 24 to 30 VDC or VAC power supply and a voltage input signal simulator.
EQUIVALENT CALIBRATION VOLTAGE
Use a voltage signal for your input signal during calibration: this makes both the procedure and the
explanation easier. If you will require a current input when you are nished, use the equation below to nd
the equivalent calibration voltage to use during the calibration procedure:
Equivalent Calibration Voltage = Required Input Signal Amps x 250
Example: 1 VDC is the equivalent calibration voltage for a 4 mA input signal (1= .004 x 250) or 5VDC is the
equivalent calibration voltage for a 20 mA input signal (5=.020 x 250).
Step 1) Trim Pot Presets
Set all pots as follows to start (These are 25 turn trim pots with no hard stops; they may make a slight
clicking sound at either end of their range):
Turn the GAIN pot Full Counterclockwise: = Gain of 1
Turn the OFFSET pots Fully Clockwise: = 0 volts oset
Step 2) Jumper Shunt Presets
J1 IN - INCOMING SIGNAL: Set in “E” position for voltage input.
If you require a current input, you will set this shunt in the “I” position
AFTER you are nished with the calibration procedure.
J2 - OFFSET: Set in the ‘O’ position for no oset to the output. If you will require a (+)
or (-) oset, you will set this shunt in the appropriate position in Step 6
Step 3) Wiring Connections
Make the following connections with the power OFF :
Connect a 24 to 30 VDC or VAC power supply (see power supply information on specications or
detail at bottom of page 3 instructions ) to the ASA terminals (+) and COM.
Connect the (-) input signal to the IN (-) terminal.
Connect the (-) meter lead to the OUT (-) terminal.
Connect (+) input signal lead to the IN (+) terminal.
Connect (+) meter lead to the OUT (+) terminal.
Step 4) Power Up
Turn on the power supply: the POWER indicator will light
Step 5) Set-Up- Input / Output Signal Adjustments
In this step you will gure the desired voltage/current input signal span and the desired voltage output
signal span and calibrate the ASA to these input and output signal spans.
To calculate the voltage/current input signal span, subtract the minimum voltage/current input signal from
the maximum input signal (i.e. a 0 to 5 volt input signal will give you a 5 volt input signal span: 5-0=5).
To calculate the voltage output signal span, subtract the minimum voltage output signal from the
maximum voltage output signal (i.e. a 3 to 15 volt output signal will give you a 12 volt output signal span:
15-3=12).
Take the number for the voltage input signal span and apply this voltage to the “IN” (+) and (-) terminals.
Compare the output voltage reading on your meter with the voltage output signal span you calculated
about. If the meter is higher or lower, adjust the “GAIN” potentiometer until the meter reads the calculated
output signal span.
Step 6) Oset Adjustments
The oset adjustments simply shift the output signal range up or down from a “no oset” setting. For
example, an output signal range with “no oset” is 3 to 15 volts. The maximum oset range is +/- 0 to 20
VDC.
Adding an oset of 2 volts would make the output signal range 5 to 17 volts. Subtracting an oset of 2 volts
would make the output signal range 1 to 13 volts.
Apply the minimum voltage input signal and read the minimum output signal on the meter. With the
“OFFSET” jumper shunt “J2” in the “0” position, no oset will be added or subtracted from the output signal
range.
If you need to shift the output signal range up, set the “OFFSET” jumper shunt “J2” in the “+” position and
adjust the “OFFSET” potentiometer until you increase the voltage reading on the meter to match the
desired minimum output voltage.
(Remember, this also increases the maximum output by the same amount.)
If you need to shift the output signal range down, set the “OFFSET” jumper shunt “J2” in the “-” position and
adjust the “OFFSET” potentiometer until you decrease the voltage reading on the meter to match the
desired minimum output voltage.
(Remember, this also decreases the maximum output by the same amount.)
Step 7) Final Adjustments
If you require a current input, set the “J1” IN jumper shunt in the “I” position. Check operation of the ASA for
desired signal rescaling and operation.

PRODUCT SPECIFICATIONS
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 6.0
I0000602
GENERAL INFORMATION
The ASA is an analog signal amplier which
accepts an analog (voltage or current) signal and
outputs a voltage signal. Several preset input
ranges are jumper selectable. It is designed to give
a Building Automation System signal output the
power (wattage) to control Maxitrol™ Gas Valves
normally installed in rooftop units. The top-adjust
trimmer potentiometers can be used to make ne
adjustments of gain and oset. The output gain
can be adjusted anywhere from 1 to 20 times the
input on the ASA (gain will vary depending on
type of input). By using voltage divider
applications, the ASA can also accept a resistance
input. The oset of the output can be +/- 0 to 20
VDC. If above 30 watts, derate load current and
calculate again (P out = [(V out/Load) (V out)]
and/or (P out = (Load Current)(V out)). The ASA is
eld calibratable, however, factory calibration is
available upon request for an additional charge.
This will speed up installation time for the end
user.
MOUNTING INSTRUCTIONS
Circuit board may be mounted in any position. If
circuit board slides out of snap track, a
non-conductive “stop” may be required. Use only ngers to remove board from snap track. Slide out of
snap track or push against side of snap track and lift that side of the circuit board to remove. Do not ex
board or use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both
ends can cause a ground loop.
• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may
result in damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or
other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC
Transorb or diode, connects to the positive side of the power supply. Without these snubbers,
coils produce very large voltage spikes when de-energizing that can cause malfunction or
destruction of electronic circuits.
• All wiring must comply with all local and National Electric Codes.
WARRANTY
The ASA Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S SENSORS &
TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.
24 VAC +10%/-5% (0-20 VDC out), 24 VDC +/- 10% (0-18 VDC out) 25-30 VDC (0-20 VDC out)
50A nominal with no load, 2.05A maximum (Dependent on Load Impedance)
0 to 20 VDC @ 200,000
0 to 44 mA @ 250
0 to 500,000
0 to 20 VDC
+/- 0 to 20 VDC
1-20 times (output can’t exceed 20 VDC)
10 minimum
Zero Oset, Positive Oset, Negative Oset
+/- 2% Full Scale Output
2A or 30 Watts maximum
45° Captive screw Terminal Blocks
12 (3.31 mm) to 22 AWG (0.33 mm)
0.5 Nm (Minimum); 0.6 Nm (Maximum)
-40 to 150°F (-40 to 65°C)
5 to 95% non-condensing
-40 to 150°F (-28.9 to 65.5°C)
NON-SPECIFIC INFORMATION
Supply Voltage:
Supply Current:
Input Voltage Signal Range (@
Impedance):
Input Current Signal Range (@
Impedance):
Input Resistance Signal Range:
Output Voltage Signal Range:
Output Voltage Signal Oset:
Output Voltage Signal Gain:
Output Load Impedance:
Output Signal Oset (Jumper
Selectable):
Input-Output Tracking Accuracy:
Power Range:
Connections:
Wire Size:
Terminal Block Torque Rating:
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature:
FACTORY CALIBRATION
The ASA is set as follows:
Voltage Input Signal
No Oset to the Output Signal
Input to Output Signal Gain (1:1)
The ASA can be ordered calibrated to your specications or you may follow the procedure below to set
your own calibration.
Be sure to check the input, output, GAIN and OFFSET specications of the ASA. It is possible that the ASA
cannot re-scale to your requirements.
CHECKOUT
Complete the following steps to change the calibration of the ASA. You will need a digital volt/current
meter, a 24 to 30 VDC or VAC power supply and a voltage input signal simulator.
EQUIVALENT CALIBRATION VOLTAGE
Use a voltage signal for your input signal during calibration: this makes both the procedure and the
explanation easier. If you will require a current input when you are nished, use the equation below to nd
the equivalent calibration voltage to use during the calibration procedure:
Equivalent Calibration Voltage = Required Input Signal Amps x 250
Example: 1 VDC is the equivalent calibration voltage for a 4 mA input signal (1= .004 x 250) or 5VDC is the
equivalent calibration voltage for a 20 mA input signal (5=.020 x 250).
Step 1) Trim Pot Presets
Set all pots as follows to start (These are 25 turn trim pots with no hard stops; they may make a slight
clicking sound at either end of their range):
Turn the GAIN pot Full Counterclockwise: = Gain of 1
Turn the OFFSET pots Fully Clockwise: = 0 volts oset
Step 2) Jumper Shunt Presets
J1 IN - INCOMING SIGNAL: Set in “E” position for voltage input.
If you require a current input, you will set this shunt in the “I” position
AFTER you are nished with the calibration procedure.
J2 - OFFSET: Set in the ‘O’ position for no oset to the output. If you will require a (+)
or (-) oset, you will set this shunt in the appropriate position in Step 6
Step 3) Wiring Connections
Make the following connections with the power OFF :
Connect a 24 to 30 VDC or VAC power supply (see power supply information on specications or
detail at bottom of page 3 instructions ) to the ASA terminals (+) and COM.
Connect the (-) input signal to the IN (-) terminal.
Connect the (-) meter lead to the OUT (-) terminal.
Connect (+) input signal lead to the IN (+) terminal.
Connect (+) meter lead to the OUT (+) terminal.
Step 4) Power Up
Turn on the power supply: the POWER indicator will light
Step 5) Set-Up- Input / Output Signal Adjustments
In this step you will gure the desired voltage/current input signal span and the desired voltage output
signal span and calibrate the ASA to these input and output signal spans.
To calculate the voltage/current input signal span, subtract the minimum voltage/current input signal from
the maximum input signal (i.e. a 0 to 5 volt input signal will give you a 5 volt input signal span: 5-0=5).
To calculate the voltage output signal span, subtract the minimum voltage output signal from the
maximum voltage output signal (i.e. a 3 to 15 volt output signal will give you a 12 volt output signal span:
15-3=12).
Take the number for the voltage input signal span and apply this voltage to the “IN” (+) and (-) terminals.
Compare the output voltage reading on your meter with the voltage output signal span you calculated
about. If the meter is higher or lower, adjust the “GAIN” potentiometer until the meter reads the calculated
output signal span.
Step 6) Oset Adjustments
The oset adjustments simply shift the output signal range up or down from a “no oset” setting. For
example, an output signal range with “no oset” is 3 to 15 volts. The maximum oset range is +/- 0 to 20
VDC.
Adding an oset of 2 volts would make the output signal range 5 to 17 volts. Subtracting an oset of 2 volts
would make the output signal range 1 to 13 volts.
Apply the minimum voltage input signal and read the minimum output signal on the meter. With the
“OFFSET” jumper shunt “J2” in the “0” position, no oset will be added or subtracted from the output signal
range.
If you need to shift the output signal range up, set the “OFFSET” jumper shunt “J2” in the “+” position and
adjust the “OFFSET” potentiometer until you increase the voltage reading on the meter to match the
desired minimum output voltage.
(Remember, this also increases the maximum output by the same amount.)
If you need to shift the output signal range down, set the “OFFSET” jumper shunt “J2” in the “-” position and
adjust the “OFFSET” potentiometer until you decrease the voltage reading on the meter to match the
desired minimum output voltage.
(Remember, this also decreases the maximum output by the same amount.)
Step 7) Final Adjustments
If you require a current input, set the “J1” IN jumper shunt in the “I” position. Check operation of the ASA for
desired signal rescaling and operation.
This manual suits for next models
1
Other aci Amplifier manuals