Acorn Meridian Edge 3802 Instruction manual

A C O R N E N G I N E E R I N G C O M P A N Y
P. O . B O X 3 5 2 7 • C I T Y O F I N D U S T R Y, C A 91 7 4 4 U . S . A .
T O L L F R E E 8 0 0 - 4 8 8 - 8 9 9 9 : : L O C A L 6 2 6 - 3 3 6 - 4 5 6 1
FA X 6 2 6 - 9 6 1 - 2 2 0 0 : : w w w. a c o r n e n g . c o m
REQUIRED ITEMS FOR INSTALLATION - NOT SUPPLIED
®
MERIDIAN-EDGE
WASH BASIN
®
CORTERRA
ADA/OBC COMPLIANT
MODEL 3802
?7/16" Hex Wrench
?1/2" NPS Supply Angle Stops
?Hammer
?Chalk Line
?Carpenters Level
?Plumbers Putty
?9/16” (8 Count) Fixture Wall Anchors and
Anchoring Hardware (and Appropriate Tools)
?Teflon Tape
?9/32” (10 Count) Fixture Wall Anchors and
Anchoring Hardware (and Appropriate Tools)
INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
Part #: 6216-011-000 Date Revised: 08/02/19
Page 1 of 22
TABLE OF CONTENTS
Prior to Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessibility Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cleaning and Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 - 16
Rough-Ins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 12
Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Finished Layouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 - 14
Components & Repair Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 - 21

ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications. ®
MERIDIAN-EDGE MODEL 3802
Date Revised: 08/02/19
Page 2 of 22
Part #: 6216-011-000
Provide: 110-120 VAC/60Hz/3A (MAX) electrical receptacle for factory supplied
120VAC/9VDC, 100mA plug-in transformer when -SO and -SOS options are selected.
Provide: 110-120 VAC/60Hz/15A dedicated circuit when Dyson Air Blade Faucet
selected. Refer to Dyson installation instructions for more information.
Single Temp Valve Assembly: Recommended working water pressure is 30 PSI (2.07
bars) minimum to 100 PSI (6.89 bars) maximum. Maximum temperature is 130°F
(54.4°C). Maximum outlet temperature is recommended is 105°F (40.6°C). Valve
assembly must be drained prior to being subjected to freezing temperatures. A
checkstop is provided with this valve assembly.
Important: Some options may slightly alter installation. To ensure proper installation
review the manual thoroughly and verify rough-ins before beginning any work. File this
manual with the owner or maintenance personnel upon completion of installation.
Prior to installation, supply lines must be flushed of all foreign material such as pipe
dope, chips, or solder. Debris or foreign material in water supply may damage valve.
Teflon tape is recommended on all threaded waste and supply connections to reduce the
possibility of leaks.
ANSI, UFAS or ADA compliance is subject to the interpretation and requirements of the
local code authority and is the responsibility of the installer for verification.
Industry standard wall backing, for wall hung fixtures, is required. Installer provided wall
anchors and wall anchoring hardware must be appropriate for wall construction, and
have a minimum pull-out rating of 1000 lbs. (453.6 kg).
NOTE: Receptacle(s) must be wired to a GFCI protected circuit. Fixture must be earth
grounded per N.E.C. (National Electrical Code).
T/P Mixing Valve Assembly: Recommended working water pressure is 30 PSI (2.07
bars) minimum to 100 PSI (6.89 bars) maximum. Maximum hot water temperature is
180°F (82°C). Temperature adjustment range is 95°F-110°F (43°C-48°C). Valve
assembly must be drained prior to being subjected to freezing temperatures. The valve
assembly has a check integral to the inlet however, angle stop is to be provided by the
installer.

ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications. ®
MERIDIAN-EDGE MODEL 3802
ACCESSIBILITY COMPARISONS
ADA ages
6 thru 12
ADA
Adult
OBC
(Ontario Building Code)
131
8"
22"
33
4"
34" RIM
MAX
27"
17"
9"
131
8"
22"
33
4"
31" RIM
MAX 27"
17"
9"
131
8"
22"
33
4"
17"
9"
OBC
PROFILE
33" RIM
MAX
131
8"
22"
33
4"
34" RIM
MAX
17"
9"
BCBC
(British Colombia Building Code)
ADA ages
6 thru 12
Date Revised: 08/02/19
Page 3 of 22
Part #: 6216-011-000

ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
DIMENSIONAL DATA
®
MERIDIAN-EDGE MODEL 3802
56"
22"
17"
Date Revised: 08/02/19
Page 4 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ROUGH-IN DIMENSIONS
ADA (Adult)
MOUNTING PLUMBING
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
Date Revised: 08/02/19
Page 5 of 22
Part #: 6216-011-000
E - 120VAC, 60 Hz, 3A (Max.) GFCI Protected, Electrical Receptacle when -SO and -SOS options are
selected.
C - Valve Mounting Area.
F - Wall Anchoring Ø9/16” x 1” Long, Angle Bracket Mounting Slots, 8 Places.
G - Wall Anchoring Ø9/32” x 3/4” Long, Enclosure Mounting Slots, 9 Places.
H - Wall Anchoring Ø9/16” Mounting Hole, Support Bracket Mounting, 2 Places.
B - Waste Outlet for 1-1/2" O.D. P-Trap by others.
D - Supply Stub-Outs with Stops for Valve 1/2" NPT Hot & Cold Supply Inlets.
I - Wall Anchoring Ø3/8” x 3/4” Long, Trap Cover Mounting Slots, 2 Places.
A - 110-120 VAC/60Hz/15A dedicated circuit when Dyson Air Blade Faucet selected
31" [787] ADA (6-13)
34" [864] ADA ADULT
34" [864] BCBC
33" [838] OBC
21
2"
[64]
6"
[152] Typ.
6"
[152] Typ.
31" [787] ADA (6-13)
34" [864] ADA ADULT
34" [864] BCBC
33" [838] OBC
61
2"
[165]
61
2"
[165]
25
8"
[67]
G G G GGGG G G
F F
H H
10"
[254]
A
211
2"
[546]
11"
[279]
43
4"
[121]
Optional -SOS Sensor
Operated Soap Profile
(Shown For Reference)
DD
A
6"
[152]
E
51
2"
[140]
B
5"
[127]
17"
[432]
C
I I
181
2"
[470]
7"
[178]
55
16"
[135]
Typ.
F
F
F
F
F
F
7"
[178]
181
2"
[470]

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
®
MERIDIAN-EDGE MODEL 3802
Please visit www.acorneng.com
for most current specifications.
FIXTURE ANCHORING
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
Locate and mount the mounting bracket to a finished wall. Locate and install P-Trap
1enclosure anchors provide by others.
NOTE: It may be advantageous to install to the deck, faucets,
soap dispensers or other accessories prior to wall mounting.
Hang deck and P-Trap enclosure onto mounting bracket , level
3and mount to the finished wall using 1/2” mounting hardware
supplied by others.
Assemble deck to P-Trap enclosure using the 1/4”-20 hardware
2provided. (6 places)
1/4"-20 UNC X 1/2" HEX
HEAD CAP SCREW
(PROVIDED)
1/4" MOUNTING BOLTS
(PROVIDED BY OTHERS)
When P-Trap enclosure is in the
4closed position, secure P-Trap
enclosure by securing cover catch
to bottom of counter deck.
Date Revised: 08/02/19
Page 6 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
Install grid strainer and close elbow to
4basin bowl using plumber's putty.
1. Grid Strainer w/ 1-1/2" -16 UNE Threads
2. Rubber Gasket
3. Flat Fiber Washer
4. 1-1/2" -16 UNI Rough Chrome Brass
Jam Nut
5. 1-1/2"-16 x 1-1/4" UNI Close Ell
with 3/8" NPT Clean-Out Plug
WASTE PLUMBING
Assemble waste piping using teflon tape on all
5threaded connections and make up waste
connections to 1-1/2” P-Trap.
HINT: Teflon tape is recommended on all
threaded waste and supply connections.
NOTE: ADD TEFLON TAPE TO ITEM (1) BEFORE
ASSEMBLING ITEM (5)
CUT TO FIT TAILPIECE
AS NEEDED
1
2
3
4
5
71
2"
Date Revised: 08/02/19
Page 7 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
PUSH-IN FITTING INSTALLATION
NOTE: FITTINGS AND TUBE SHOULD BE KEPT
CLEAN, BAGGED AND UNDAMAGED PRIOR TO
INSTALLATION.
3. Pull on the fitted tubing to ensure it is secure. Tube
should not come free from the fitting. Water test the
connection assembly prior to leaving the site to ensure
there are no leaks.
4. To disconnect the tube from the fitting ensure that the
water supply is off. Push collet square towards the
push-in fitting body and hold. While holding the collet in,
pull on the PE tubing to remove from the push-in fitting.
1. Cut to fit length of 1/4” PE tubing and remove any burrs
or sharp edges. Ensure that the outside diameter is free
from score marks. Tube ends should be square.
2. Firmly and fully insert the tubing end into the push-in
fitting up to the tube stop located approximately 1/2”
deep.
1.
2.
3.
4.
3. Connect 1/4” O.D. PE tubing from valve.
SPOUT INSTALLATION
1. Assemble spout to deck securing it with nut.
2. Assemble hose adapter to tube adapter and connect
to spout hose using teflon tape.
HOSE ADAPTER
TUBE STOP
1/4" PE TUBING
COLLET
HOSE
COLLET
1/4" NPT x 1/4" O.D.
TUBE ADAPTER
1/4" PE O.D.
TUBING
NUT
WASHERS
1/2" HOSE x
1/4" NPT HOSE
ADAPTER
1/2" SPOUT HOSE
TUBE ADAPTER
Date Revised: 08/02/19
Page 8 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
VALVE INSTALLATION & ADJUSTMENT
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
4) Turn on hot and cold water supplies. If any
leaks are observed, hand-tighten
connections as necessary to stop leaks
before proceeding.
5) Turn on fixture and allow water to flow for 2
minutes. Measure water temperature at
outlet. If water is not at desired temperature,
adjust as necessary.
NOTE: Installation should be in accordance with
accepted plumbing practices.
1) Locate suitable place for mounting the valve
assembly. Valve assembly should be
accessible for service and adjustment and
as close to the point-of-use as possible.
Wall anchors and anchoring hardware are
by others.
2) Connect hot and cold water to supply
valve using 1/2” NPTE connections by others.
3) Connect outlet of tempering valve to
spout using 1/2” NPT connections
provided (Refer to pg.8).
1) Loosen locknut.
2) Turn on fixture and run water for at least 2
minutes. Allow supply temperature to
stabilize.
3) Turn temperature stem counter-clockwise
for hotter or clockwise for colder outlet
temperature.
5) Re-check outlet temperature.
4) Tighten locknut to prevent accidental or
unauthorized temperature adjustment.
Temperature Adjustment
Valve Assembly Installation: !IMPORTANT
Flush supply lines of all foreign material such
as pipe dope, pipe chips, solder, sand etc.
before making up supply connections.
HINT: Angle stops are recommended
and is the responsibility of the installer.
LOCKNUT
WARMER
TEMPERATURE
STEM
1
2
1
(For -MXTP Option):
Date Revised: 08/02/19
Page 9 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
SENSOR OPERATION & CONNECTIONS
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
-SO Sensor Operation Range Adjustment
NOTE: SENSOR IS FACTORY SET. IF ADJUSTMENT IS
DESIRED SEE BELOW:
5. Hold hand at desired sensing distance until red light
stops flashing and solenoid activates.
See DETAIL C.
1. Make sure power supply is disconnected from
sensor and make short circuit on red wires.
See DETAIL A.
4. Move hand to desired sensing distance.
See DETAIL B.
2. Connect power supply to sensor. Red light should
be flashing.
3. Move hand in front of sensor to distance of 2” to 4”
within 5 seconds and wait until red light flashes
quickly.
DETAIL A
DETAIL B
DETAIL C
Transformer must
be plugged into a
GFI protected
circuit. Fixture must
be earth grounded
per N.E.C. or
applicable codes.
Jumper
By Others
-SO Sensor Operation -SO-BAT Sensor Operation
(Battery Operated)
Red Power
Plug-in
White Valve
Plug-ins
Date Revised: 08/02/19
Page 10 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
Ferrule Nut
1/4"
Min.
Ferrule
Nut
-H Hand Operated
1/8" O.D. AIR TUBE
1/4" O.D. WATER LINE
Leave a minimum 1/4” of polyethylene tubing
through the Ferrule Nut on the pushbutton
assembly. This is necessary to ensure proper
tubing connection.
turn timing screw.
Timing Screw
To adjust timing,
HAND OPERATION & CONNECTIONS
Turn timing screw clockwise to
increase timing.
Do not over tighten
ferrule nuts.
Date Revised: 08/02/19
Page 11 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
OPTIONAL ACCESSORY INSTALLATION & ASSEMBLY
Some soaps contain corrosive additives that can cause rust in
soap dispensers. Acorn Engineering Company recommends
user/ maintenance personnel review MSDS reports of soap and
possible corrosive additives noted.
!WARNING
Rubber
Gasket
Washer
Black end of
Check Valve
Direction
of Flow
3/8" Nut
3/8" O.D.
Tube
Install soap reservoir to wall inside P-Trap
enclosure using mounting brackets provided as
shown. Wall anchors and anchoring hardware
provided by installer.
A.
Install soap filler assembly to deck as shown.
B.
Attach 1-1/4" O.D. refill tube to soap filler
assembly and soap reservoir with provided hose
clamps.
C.
Install soap dispenser(s) onto deck. NOTE:
Gasket and Washer are located beneath the
deck.
D.
Attach 3/8" O.D. Tubing to the dispenser(s) and
reservoir. NOTE: Check Valve must be field
spliced into tubing and installed with respect to
direction of flow.
E.
HINT: For best results install soap
reservoir fill hole directly below soap filler
on deck with refill tube as short and
straight as possible to facilitate refill of
soap without backup or overflow.
Soap Filler Adapter
Ø3/8" OD Tube
Ø1/4" OD Vent Tube
Soap Reservior
Mounting
Bracket
1-1/4"
Date Revised: 08/02/19
Page 12 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications. ®
MERIDIAN-EDGE MODEL 3802
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
MODEL #3802-WD04-SOS
MODEL #3802-WD04-PDM
FINISHED LAYOUTS
(SHOWN FOR REFERENCE)
Date Revised: 08/02/19
Page 13 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications. ®
MERIDIAN-EDGE MODEL 3802
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
FINISHED LAYOUTS
(SHOWN FOR REFERENCE)
MODEL #3802-H-PDM
MODEL #3802-SO-SOS
Date Revised: 08/02/19
Page 14 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
TROUBLE SHOOTING FOR 9 VOLT DC SENSOR OPERATED VALVES
Normal Valve Function: 9 Volt DC sensor operated valve has flow time of 90 seconds maximum.
To reactivate, the user must move out of and return to the sensing area.
CONDITION: WATER DOES NOT FLOW
Indicators Probable Cause
Solution
Sensor flashes continuously
every 2 seconds when
hands are within range.
Low battery warning Replace battery
Circuit breaker tripped. Reset circuit breaker
Replace battery
Defective 9V DC transformer
Transformer polarity crossed Replace transformer (sensor may be
damaged and need replacement).
Unit is in “Security Mode” after
90 seconds of constant detection.
Remove sources of detection and
wait 30 seconds before checking.
Range is too short. Increase range.
Range is too long. Decrease range and wait 30 seconds.
Sensor is picking up a highly
reflective surface. Eliminate cause of reflection and wait
30 seconds before checking.
Sensor does not flash
when the user’s hands
are within range.
Defective sensor. Replace sensor.
Stops or water main closed.
Bad sensor to solenoid connection.
Debris or scale in
solenoid assembly.
Remove solenoid, pull out plunger
and spring, and clean with scale
remover solution or pressurized air.
Debris or scale in diaphragm. Remove diaphragm and clean
Sensor flashes once
when user’s hands are
within range.
Remove strainer and clean.
CONDITION: FALSE TRIGGERING;
WATER FLOWS CONTINUOUSLY
Indicators Probable Cause
Solution
Remove diaphragm and clean. Sensor flashes when user’s
hands are within range. Diaphragm is defective or torn.
Sensor is dirty or covered. Clean or uncover sensor and
wait 30 seconds.
Decrease range and wait 30 seconds.
Sensor does not flash when
users hands are within range. Range too long or highly
reflective surface, sunlight, bright
lights etc. are triggering sensor. Eliminate cause of reflection or
correct lighting problem.
CONDITION: WATER FLOWS
CONTINUOUSLY BUT STOPS
WHEN HANDS ARE WITHIN RANGE
Indicators Probable Cause
Solution
Water runs continuously when
sensor not activated. Sensor
flashes when hands are within
range and water shuts off.
Solenoid polarity crossed. Disconnect solenoid and
reverse polarity.
Battery completely used up.
Replace transformer.
Open stops or water main.
Ensure wires make proper contact.
Debris or scale in strainer.
Replace diaphragm.
Debris or scale in diaphragm
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
Date Revised: 08/02/19
Page 15 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
CONDITION: WATER DOES NOT FLOW
Probable Cause Solution
Water main closed. Open water main.
Checkstops closed. Open checkstops.
Debris or scale in checkstop strainer
. Remove checkstop strainer and clean.
Air leaks from 1/8” O.D. tubing or fittings. Replace damaged tubing or fitting.
Pushbutton air diaphragm leaks. Replace pushbutton air diaphragm.
Servomotor diaphragm center hole is blocked.
Servomotor upper diaphragm is damaged.
Low or no water pressure at supplies. Increase water pressure to 30 PSI minimum.
CONDITION: WATER DRIPS, WON'T SHUT OFF
Probable Cause Solution
Servomotor diaphragm offset hole is blocked.
Servomotor seat is damage Replace servomotor seat.
Servomotor plate or diaphragm is obstructed.
Servomotor timer assembly is damaged. Replace servomotor timer assembly.
Probable Cause Solution
Valve riser tubing is crimped. Straighten valve riser tubing.
Debris or scale in checkstop strainer
. Remove checkstop strainer and clean.
Blockage in valve flow control. Remove blockage.
Low water pressure at supplies. Increase water pressure to 30 PSI minimum.
Lime deposits in hot water pipes.
CONDITION: REDUCED WATER FLOW
Probable Cause Solution
Air leaks from 1/8" O.D. tubing or fittings. Replace damaged tubing or fitting.
Pushbutton air diaphragm leaks. Replace pushbutton air diaphragm.
Remove blockage.
Replace servomotor upper diaphragm.
Remove cause of obstruction.
Remove blockage.
TROUBLE SHOOTING FOR OPTIONAL PUSHBUTTON OPERATED VALVES
Normal Valve Function: Hand pushbutton operated valve has an adjustable flow time from
5 to 60 seconds.
Remove lime deposits with appropriate
cleaning solution.
CONDITION: PREMATURE WATER SHUT OFF
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
Date Revised: 08/02/19
Page 16 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
RECOMMENDED CLEANING SOLUTIONS
- Hand dishwashing liquid/soft water solution
- Mild soap/soft water solution
- 3M Stainless Steel Cleaner/Polish
- White vinegar/soft water solution
(for brightening, removing oil and
hard water deposits)
- CLR Brand Cleanser or baking soda/soft
water solution (for brightening, removing
hard water deposits)
- Club soda and sponge
FOR HIGH POLISH STAINLESS STEEL
Note: High polish stainless steel surfaces should never
come into contact with any abrasive cleaning brush, cloth or
cleaning agent.
To remove rust stains:
Wipe surfaces with CRES (available from Acorn) or
equivalent cleaner. Use recommended solutions. Apply
using a soft non-abrasive sponge. Rinse surfaces
immediately after application. Always follow cleaner product
directions provided. Afterwards, using a soft, non-abrasive
cloth, wipe surfaces with stainless steel cleaner/polish.
FOR TOUGH PROBLEMS
- CRES Cleaner specifically for rust stains (available from
Acorn)
- Tarn-X for general stains
- #7 chrome polish
- Silver polish
To remove stubborn spots or to treat a scratch
(Standard Satin Finish Only):
Use of synthetic, abrasive, general-purpose pads such as
Scotch Brite is recommended. Apply the stainless steel
cleaner/polish to the synthetic, abrasive pads and
CAREFULLY rub out spot with cleaner/ polish. Be sure to
rub in the direction of the grain! Do not allow steel wool to
come in contact with the stainless steel. Steel particles can
embed into the stainless steel surface and create rust!
SOAP SYSTEMS
Acorn soap reservoirs and dispensers provide a dependable
operation over long term when proper maintenance is
performed and the correct soap is being used. The most
common problem with soap systems is that the wrong
viscosity (thickness) of soap is being used or high acidic pH
levels are in the ingredients. Soap thickness can be best
explained as no thicker or thinner than normal household
liquid dish soap. The pH level of the soap should be 6.5 to
8.5; more acidic soaps will corrode the metal parts and
degrade rubber or plastic components.
To remove smudges and fingerprints:
Wipe surfaces with a quality Stainless Steel Cleaner/Polish.
Apply using a soft non-abrasive cloth, wipe surfaces with
stainless steel cleaner/polish.
Stainless steel should be kept clean at all times. If
maintained, stainless steel surfaces will retain their new,
clean, polished appearance indefinitely. To remove water
spots or rust spots, stainless steel cleaner/polish on a cloth
is recommended.
ROUTINE CLEANING
Corterra should be kept clean at all times. If maintained,
®
Corterra surfaces will retain their new, clean appearance
®
indefinitely. Wash with a non-abrasive all purpose cleaner
and water, then rinse. Wipe dry. (Never use cleaners with
strong chemicals such as toilet bowl cleaners, rust
removers, ceramic cook top cleaners, laquer thinners or
oven cleaners). To remove persistent stains use a Scotch
Brite pad and an abrasive cleaner or a solution of household
bleach and water (1 part water to 1 part bleach).
REPAIRING SURFACE DAMAGE
Surface damage, such as minor chips, scratches, burn
marks and graffiti can be repaired with a fine grit abrasive
cleanser, such as a Scotch-Brite pad or fine grit sandpaper.
For more serious physical damage caused by vandals, an
Acorn Solid Surface Repair Kit is available. Contact the
factory for details. Refer to drawing #9927-160-002.
Soap reservoirs and dispensers should be maintained
periodically to clear residue. This should be done in hot
water to clean the internal components. The valve should be
pumped multiple times to thoroughly clean any residue
inside. The reservoir and tubing should also be flushed and
cleaned with hot water. In cases of extreme clogs, the
dispenser should be disassembled and the parts thoroughly
cleaned.
CARE, CLEANING, AND REPAIR
OF CORTERRA SOLID SURFACE
®
CORTERRA SOLID SURFACE
®
Acorn's densified solid surface material is composed of
recycled solid-surface polymer resin, aluminum trihydrate
and fillers. It is resistant to stains, impact and burns and
complies with ANSI Z124.3. It is attractive, durable and easy
to maintain.
WARNING: Some soap contains corrosive additives that
can cause rust on stainless steel surfaces. Acorn
recommends user/ maintenance personnel review MSDS
reports of soap and possible corrosive additives noted.
CARE AND CLEANING OF STAINLESS
STEEL SURFACE
NORMAL CLEANING
Clean weekly or more often, as needed
(especially high polishing surfaces)
RECOMMENDED CLEANING MATERIALS
- Sponge – natural or artificial
- Nylon or other soft-bristle material brush
- Soft cloth (as used on automobile finishes)
IF SPOTS ARE STUBBORN OR IF YOU WISH TO TREAT A
SCRATCH: synthetic, abrasive, general-purpose pads such
as Scotch Brite are recommended. Apply the stainless steel
cleaner/polish to the synthetic, abrasive pad and
CAREFULLY rub out spot with cleaner/polish. Be sure to
rub in the direction of the grain! Do not allow steel wool to
come in contact with stainless steel. Steel particles can
embed into the stainless steel surface and create rust.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
Date Revised: 08/02/19
Page 17 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
¼"-20 x 1/2" Long
Stainless Steel, Hex Head, Cap Screw, 0206-004-000
0332-004-000
¼"-20 x 1" Thick Fender Washer
COMPONENTS & REPAIR PARTS
Description Part No. Diagram
MOUNTING HARDWARE
0337-050-000
1/4" Stainless Steel Helical Lock Washer
Stern Easy E/B Sensor Operated Spout
9VDC
2993-400-001
SPOUTS
Stern Easy E/B Hand Operated Spout 2993-410-001
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
Date Revised: 08/02/19
Page 18 of 22
Part #: 6216-011-000

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
COMPONENTS & REPAIR PARTS
Description Part No.
SPOUTS (cont.)
Diagram
Push Button Assembly
Dyson Airblade™ Wash + Dry
(Deck Mounted Short Faucet) 3040-091-000
2566-270-001
9 VDC Plug-In Transformer 0711-410-001
9 VDC Solenoid 2563-326-001
Stern Easy E Adapter Kit 6215-105-001
Date Revised: 08/02/19
Page 19 of 22
Part #: 6216-011-000
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
0711-412-001
0711-430-001
0711-431-001
2-Station Power Cable Assembly
Solenoid Extension, 9 Volt, 2FT, White
Solenoid Extension, 9 Volt, 2FT, Red
ELECTRONIC HARDWARE

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
Please visit www.acorneng.com
for most current specifications.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
®
MERIDIAN-EDGE MODEL 3802
COMPONENTS & REPAIR PARTS
Description Part No. Diagram
ENCLOSURES
Grid Strainer w/ Close Elbow
4926-062-001
ELECTRIC HARDWARE CONTINUED:
P-Trap Waste Assembly
4970-040-003
Mounting Bracket
Mounting Bracket 6216-204-199
WASTE ASSEMBLY
9 VDC Battery-Pak Assy
(6 AA Batteries Not Included)
Battery-Pak Mounting Bracket
0710-358-001
6155-013-199
Trap Enclosure 6216-200-002
-PDM SOAP OPTION
Soap Filler Assembly 1391-008-001
Date Revised: 08/02/19
Page 20 of 22
Part #: 6216-011-000
Table of contents
Popular Kitchen & Bath Fixture manuals by other brands

FRANZ VIEGENER
FRANZ VIEGENER Groovy FV215/F4.0 Installation and Maintenance

Transform
Transform QL036 owner's manual

Spectrum Brands
Spectrum Brands Pfister Ladera F-036-4LR Quick installation guide

VIGO
VIGO Matte Stone VG04002 manual

Moen
Moen 7165 Series installation guide

Abode
Abode Coniq-R AT2124 manual

Fantini Rubinetti
Fantini Rubinetti Young 3429000501 Care and maintenance

Sloan
Sloan G2 Optima Plus Maintenance and repair guide

METHVEN
METHVEN Aurora 14-1708 installation guide

Luxart
Luxart MODERN MO138 Installation

Bristan
Bristan QD 1/2 C Installation instructions & user guide

Central Brass
Central Brass 0127-A Series installation instructions