ATE series Wireless Temperature Sensor
Installation Instruction V1.7
Acrel Co., Ltd.

安科瑞电气股份有限公司
2
1 Installation Guide
1.1 Product Introduction
ATE series wireless temperature measuring sensor has been developed in compliance with
Specification for Wireless Temperature Measuring equipment, NB/T 42086-2016. It is suitable for 3-35kV
indoor switchgears, including built-in switchgears, handcart switchgears, fixed switchgears and loop-net
switchgears. It is also suitable for 0.4kV low-voltage switchgears such as fixed switchgears and drawer
switchgears. The wireless temperature sensors can be installed at any heating point in switchgears, the
device utilizes the wireless data transmission technology for real-time transmission of monitored
temperature data. In addition, it can be transmitted to display device or remote intelligent monitoring
system.
1.2 Type Introduction
ATE
Wireless temperature measuring sensor
XXX
Type:
100 is bolted, 100M is magnetic,200 is belt,
400 is tied with cable tie, 100P is outdoor
bolted, 200P is outdoor belt
1.3 Technical Features
Items Features
Environment
Temperature -40℃~125℃
Humidity ≤95%
atmospheric pressure 86kPa~106kPa
ATE100M/100/200
Active wireless
temperature sensor
Wireless frequency 470MHz
Communication distance 150m in open area
Sampling frequency 25s
Transmitting frequency 25s-5min

安科瑞电气股份有限公司
3
1.4 Product Installation
There are several types of wireless temperature sensors and mounting methods correspondingly, i.e.
Magnetic , bolted , belt and alloy chip fixing.
1.4.1 Shape Size
Power source Battery
Installation Magnetic / bolted /Belt
Range of temperature -50℃~+125℃
Precision ±1℃
Application Joints in high or low voltage switchgears
Battery life ≥5 years
400 Passive
wireless
temperature sensor
Wireless frequency 470MHz
Communication distance 150m in open area
Sampling frequency 15s
Transmission frequency 15s
Power source CT-powered, starting current≥5A
Installation alloy chip fixing
Sensor probe alloy bottom
Range of temperature -50℃~125℃
Precision ±1℃
Application Joints in high or low voltage switchgears
ATE100P/200P
Outdoor wireless
temperature sensor
Wireless frequency 470MHz
Communication distance 150m in open area
Sampling frequency 25s
Transmitting frequency 25s-5min
Power source Battery
Installation bolted /Belt
Range of temperature -50℃~+150℃
Precision ±0.5℃
Application Voltage switchgears
Battery life ≥5 years
Protection level IP68

安科瑞电气股份有限公司
4
ATE100M
ATE100/ATE100P
ATE200/ATE200P
ATE400
1.4.2 Label Instructions
1.4.2.1 ATE sensor with ASD/ARTM-Pn device

安科瑞电气股份有限公司
5
ASD320 ARTM-Pn
ATE400
ATE100ATE100M ATE200
ATE200PATE100P
If the sensor is ATE100M/ATE100/ATE200/ATE400/ATE100P/ATE200P, the number behind “组号:
”
should be same as number underlined in “*51809190240001*”, the sequence of installation is base on the
label, “编码:1A” is first one on the phase A, “编码:1B” is first one on the phase B,and so on.
Notice: wireless temperature sensors and display device in the package have been matched
before delivery. Do not use them with other display device or other wireless temperature sensors
together. Please installing them with label on the sensor.
1.4.2.2 ATE sensor with ATC600/ATC450-C coordinator
ATC450-C
ATC600

安科瑞电气股份有限公司
6
ATE400
ATE100ATE100M ATE200
ATE200PATE100P
According to the above pictures, If the sensor is ATE100M/100/200/400/100P/200P, the group
number of ATE must be same with the group number of ATC450-C/ATC600 and the installation order is
base on the label. The code of each sensor is used to distingguish each sensor from same group. “code:
001”is recommended to be installed on the first temperature measuring point of the first cabinet, and then
installed other sensors in this order.
In case of any special situation, please contact the relevant engineers for communication.
1.4.3 Installation Method
1.4.3.1 ATE100M Installation Method
The magnetic wireless sensor ATE100M is suitable for iron electrical nodes or equipment surfaces.
Structure introduction of ATE100M:
1 —— The core of wireless temperature sensor ATE100M
2—— Thermo-sensitive part
3 —— battery switch
2
1
1
3
1
Adsorbed directly at the iron temperature measuring point, open the battery switch before installation,
the power indicator flashes twice. The installation examples see images below.
1.4.3.2 ATE100 Installation Method
The bolted type wireless sensor ATE100 is suitable for use at joints between cable and bus bar and

安科瑞电气股份有限公司
7
joints between cable and disconnector.
ATE100 structure introduction:
1 —— The core of wireless temperature sensor ATE100
2 —— Thermo-sensitive part
3 —— battery switch
3
1
2
1
Remove the screw from the joints, and fixing the sensor on the position with the hole on the alloy
baseplate, then tighten the screw, open the battery switch before installation, the power indicator flashes
twice. The installation examples see images below.
1.4.3.3 ATE200 Installation Method
The strap-secured type called ATE200 is suitable for use at moving contacts and fixed contacts of
breaker, cable joints and bus bar.
ATE200 structure introduction:
1 —— The core of wireless temperature sensor ATE200, temperature measuring probe is on the other
side
2 —— strap and hasp
3 ——battery switch

安科瑞电气股份有限公司
8
1
3
1
2
Fixing the body of sensor on the position, then strapping it on the bus bar or breaker contact and
frapping it through the hole on the strap, fixing the strap by hasp. Clipping the strap if it is too long when
finished, if it is too short, contacting us for strap parts before installation. Open the battery switch before
installation, the power indicator flashes twice.The installation examples see images below.
1.4.3.4 ATE400 Installation Method
The mini type called ATE400 is suitable for using at moving contacts, bus bars, cables and joints
between bus bar and cable.
Mini type passive temperature sensor structure introduction:
1 —— The core of wireless temperature sensor ATE400
2 —— alloy bottom, touched with temperature probe
3 —— metal hasp, for fixing alloy chip
4 —— alloy chip, for CT-powered
5 ——silicone gasket, used to support the alloy chip
6 ——alloy chip hole, used to install the alloy chip
2
1
6
5
1
3
1
4
1
1

安科瑞电气股份有限公司
9
Firstly, take 2 pieces of alloy chips through the mounting hole of metal hasp, meanwhile fold the alloy
chips and fix the metal hasp in the middle of alloy chips. Secondly, take the folded alloy chips through one
silicone gasket, the core of ATE400 and another silicone gasket in turn.Thirdly, circle the whole alloy chips
around the mounting position and tension the alloy chips, then tighten the screw on the metal hasp. Finally,
subtract the excess alloy chips. The complete installation process is shown in Figures 1 to 4.
The wireless temperature sensor called ATE400 installation examples, see images below.
1.4.4 Wireless Temperature Coordinator
The wireless temperature coordinator connected with ATE series wireless temperature sensor
ATC450-C which can be mounted on rail (DIN35mm) or bolted directly.

安科瑞电气股份有限公司
10
The wireless temperature coordinator connected with ATE series wireless temperature sensor
ATC600 which can be mounted on rail (DIN35mm).

安科瑞电气股份有限公司
11
Appendix
Precautions
1)Please select the most suitable wireless temperature measurement product according to the
installation location and requirements.
2)For the installation of all sensors, please strictly follow the instructions in the manual. If there is
insufficient accessories due to installation errors, the customer shall bear the responsibility.
3)Before placing an order for wireless temperature measurement products, you need to have a
detailed configuration plan, and fill in the Acrel Wireless Temperature Measurement
Confirmation Form ! Then submit the plan and form to the back office.
Other manuals for ATE Series
1
This manual suits for next models
6
Table of contents
Other Acrel Temperature Controllers manuals