7ICE CFA3240A-3300A-3360A I&O Manual 10/2023 Rev.11
Model Number CFA3240 CFA3300 CFA3360
Cooling BTUH1216,600 300,000 330,000
Rated Air Flow (CFM2)7,400 11,900 10,200
ESP3@ Rated Conditions 0.40 0.45 0.55
1Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air
2CFM=Cubic Feet per Minute 3ESP=External Static Pressure
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“C” models), 460 volts for “D” models, 380 volts for “E”
models, 575 volts for “Z” models. Derate performance by 17% for ACE (380v. 3ø, 50 Hz) models
Operation of units at a different voltage from that of the rating point will affect performance and air ow.
Table 1. Cooling Performance and Air Flow Ratings
MODEL Description INCHES MILLIMETERS PART # # OF
FILTERS
MERV
RATING
CFA3180/3240 Exterior Access Return Air Filter 25 x 16 x 2 635 x 406 x 51 80137 4 8
CFA3180/3240 Interior Access Return Air Filter 24 x 18 x 2 610 x 457 x 51 81257 4 8
CFA3240 w/Economizer Fresh Air Hood Pre-lters 26 x 12 x 1 660 x 305 x 25 92526 2 N/A
CFA33240 Reverse Flow
w/Economizer Fresh Air Hood Pre-lters 16 x 32 x 1 406 x 813 x 25 93187 3 N/A
CFA3300/3360 Exterior Access Return Air Filter 30 x 30 x 2 762 x 762 x 51 80156 4 8
CFA3300/3360 Interior Access Return Air Filter 24 x 18 x 2 610 x 457 x 51 81257 4 8
Table 2. Filter Sizes/Part Numbers
MODEL Unit Weight Shipping
Weight
Shipping Dimensions
Height Width Depth
LBS KG LBS KG Inches MM Inches MM Inches MM
CFA3240 2,523 1,144 2,636 1,196 98 2,489 76 1,930 51 1,295
CFA3300 2,625 1,193 2,750 1,250 108 2,743 72 1,829 72 1,829
CFA3360 3,210 1,456 3,335 1,513 108 2,743 72 1,829 72 1,829
Table 3. Shipping Weights & Dimensions
Model CFA3240 CFA3300 CFA3360
Refrigerant Charge (Oz) 264.5143214161
1Per circuit on dual compressor models
Table 4. Refrigerant Charge (R410A, Ounces)
1.5 General Operation
Hot Gas By-Pass
Standard on all models except the, Hot Gas By-Pass is normally used in specialty applications (i.e
Magnetic Resonance Imaging (MRI) buildings) to prevent magnetic voltage disturbance caused by
cycling. This technology is applied in this product to extend the operation envelope for the compressor
to 20º F (-6.6ºC). Combined with a condenser low ambient Fan Cycle feature, compressor operation can
be extended to 0º F (-17.8ºC). During Hot Gas operation mode, system performance will be reduced. If
product operation is in mild outdoor ambient conditions, the installed shut-off ball valve may be closed,
thus disabling the Hot Gas By-Pass feature.
Refrigerant Cycle (Cooling Mode)
The air conditioners use R-410A refrigerant in a conventional vapor-compression refrigeration cycle to
transfer heat from air in an enclosed space to the outside. A motorized impeller assembly blows indoor
air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled into gas by
heat removed from the air. The warmed refrigerant gas enters the compressor where its temperature and
pressure are increased. The hot refrigerant gas condenses to liquid as heat is transferred to outdoor air