Akytec MU110-6U User manual

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Тел.: +49 (0) 511 16 59 672-0 · www.akytec.de
MU110-6U
Analog output module
6 channel
User guide
MU110-6U_2019.08_0292_EN
© All rights reserved
Subject to technical changes and misprints

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
1
Contents
1Description......................................................................................................................................................2
1.1 Functions .................................................................................................................................................2
1.2 RS485 network ........................................................................................................................................2
1.3 Design......................................................................................................................................................2
2Specifications.................................................................................................................................................3
2.1 Operating conditions................................................................................................................................3
3Safety...............................................................................................................................................................4
3.1 Intended use............................................................................................................................................4
4Installation.......................................................................................................................................................5
4.1 Wiring.......................................................................................................................................................5
4.1.1 Hardware write protection....................................................................................................................5
4.1.2 Outputs ................................................................................................................................................6
5Configuration..................................................................................................................................................7
6Operation.........................................................................................................................................................9
6.1 Output functional test...............................................................................................................................9
6.2Fault state..............................................................................................................................................10
6.3 Modbus addressing ...............................................................................................................................10
7Restore factory settings ..............................................................................................................................11
8Maintenance..................................................................................................................................................13
9Transportation and storage.........................................................................................................................14
10 Scope of delivery..........................................................................................................................................15
Appendix A Dimensions ...................................................................................................................................16

Description
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
2
1 Description
1.1 Functions
MU110-6U is an extension module with 6 analog outputs.
The module provides following functions:
─module control and parametrization via RS485 network
─RS485 Network diagnostics
─error and alarm signal generation
─Slave in the RS485 network.
The module is to be configured using ‘M110 Configurator’ software via RS485-USB
interface adapter IC4 (not included). The latest version of the configuration software is
available for download on www.akytec.de.
1.2 RS485 network
The I/O modules of Mx110 series use the common standard RS485 for data exchange.
The serial interface RS485 enables communication via two-wired line in half-duplex
mode. The module supports the Modbus RTU and Modbus ASCII protocols with automat-
ic protocol detection The network consists of a Master device and can contain up to 32
Slave devices. The maximum length is 1200 m. The number of slave devices and net-
work length can be increased using RS485 interface repeater.
Separate devices are connected to a network according to linear (bus) topology. It means
that the line goes from the first device to the second one, from the second one to the third
one, etc. Star connections and spur lines are not allowed.
Line reflections always occur at the open bus ends (the first and the last node). The high-
er the chosen data transmission rate, the stronger they are. A terminating resistor is
needed to minimize reflections. Experience proves that the most efficient practice is to
use terminating resistors of 150 ohm.
The modules can be used as slave devices only. Master device can be PLC, PC with
SCADA software or control panel.
1.3 Design
─Enclosure plastic, grey, for DIN-rail or wall mounting
─Terminal blocks 2 plug-in terminal blocks with 24 screw terminals
─LED “POWER“ power supply indicator
─LED “RS-485” flashes at data exchange via RS485 interface
─LED “FAULT” lit when data exchange via RS485 interfaces interrupted
Dimensional drawings are given in App. A.
There are three jumpers under the front cover (see Fig. 4.1):
─X2 −restore factory settings (see 7)
─X3 −service function
─X1 −DRAM write-protection (see 4.1.1)
All jumpers are in OFF position by default.

Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
3
2 Specifications
Table 2.1 General specifications
Power supply
24 (18…29) V DC
Power consumption, max.
6 W
Inputs
Digital
Analog
Outputs
Digital
Analog
6
Output signal
0-10 V
Load resistance, min
2 kohm
Auxiliary voltage
12…36 V DC
RS485 interface
Terminals
D+, D-
Protocols
Modbus RTU/ASCII, akYtec
Baud rate
2.4…115.2 kbit/s
Data bits
7, 8
Parity
none, even, odd
Stop bits
1, 2
Accuracy, max.
±0.5%
Dimensions
63 x 110 x 75 mm
Weight
approx. 500 g
Material
plastic
2.1 Operating conditions
The following environment conditions must be observed:
─clean, dry and controlled environment, low dust level
─closed non-hazardous areas, free of corrosive or flammable gases
Table 2.2Environmental conditions
Condition Permissible range
Ambient temperature
-20…+55°C
Transportation and storage
-25…+55°C
Relative humidity
up to 80%, non-condensing
IP Code
IP20
Altitude
up to 2000 m above sea level

Safety
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
4
3 Safety
Explanation of the symbols and keywords used:
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury.
►
NOTICE
NOTICE indicates a potentially harmful situation which, if not avoided, may result in
damage of the product itself or of adjacent objects.
3.1 Intended use
The device has been designed and built solely for the intended use described in this
guide, and may only be used accordingly. The technical specifications contained in this
guide must be observed.
The device may be operated only in properly installed condition.
Improper use
Any other use is considered improper. Especially to note:
─This device should not be used for medical devices which receive, control or other-
wise affect human life or physical health.
─The device should not be used in an explosive environment.
─The device should not be used in an atmosphere with chemically active substance.

Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
5
4 Installation
CAUTION
Improper installation
Improper installation can cause serious or minor injuries and damage the module.
Installation must be performed only by fully qualified personnel.
─The module is intended to be mounted on a DIN-rail or on a wall. For the dimen-
sion drawings see Appendix A.
─Install the module in a cabinet with clean, dry and controlled environment. For fur-
ther details see 2.1.
─The module is designed for natural convection cooling. It should be taken into ac-
count when choosing the installation site.
4.1 Wiring
DANGER
Dangerous voltage
Electric shock could kill or seriously injure.
All electrical connections must be performed by a fully qualified electrician.
Ensure that the mains voltage matches the voltage marked on the nameplate!
Ensure that the device is provided with its own power supply line and electric fuse!
CAUTION
Switch on the power supply only after the wiring of the device has been completely
performed.
─The electrical connections are shown in Fig. 4.1 and 4.2, the terminal assign-
ments in Table 4.1.
─Connect the power supply to the terminals 24V / 0V.
─The maximum conductor cross-section is 1.5 mm².
►
NOTICE Signal cables should be routed separately or screened from the supply cables.
►
NOTICE Only a shielded cable may be used for signal lines.
─Connect the RS485 lines to the terminals D+ / D-
─Twisted pair cable should be used for the connection to the RS485 interface
─Maximal cable length is 1200 m
4.1.1 Hardware write protection
Data stored in permanent memory can be lost because of strong electromagnetic inter-
ference.
Use the jumper X1 (Hardware write-protection) to avoid data loss.
Proceed as follows:
─Turn off the device
─Open the front cover (see Fig. 4.1)
─Set the jumper X1.
Notice:
─to change the configuration parameters, the jumper X1 must be removed again.

Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
6
4.1.2 Outputs
MU110-6U has 6 analog outputs 0-10 V which can be controlled via RS485 network.
Fig. 4.1 Electrical connections
Table 4.1 Terminal assignments
No Indication Description No Indication Description
1
0V
Power supply
13
D-
RS485 D-
2
24V
Power supply
14
D+
RS485 D+
3
not connected
NC
15
not connected
NC
4
AO1A
Output 1 / 0-10 V
16
AO4A
Output 4 / 0-10 V
5
AO1B
Output 1-
17
AO4B
Output 4-
6
AO1C
Output 1+
18
AO4C
Output 4+
7
AO2A
Output 2 / 0-10 V
19
AO5A
Output 5 / 0-10 V
8
AO2B
Output 2-
20
AO5B
Output 5-
9
AO2C
Output 2+
21
AO5C
Output 5+
10
AO3A
Output 3 / 0-10 V
22
AO6A
Output 6 / 0-10 V
11
AO3B
Output 3-
23
AO6B
Output 6-
12
AO3C
Output 3+
24
AO6C
Output 6+
Fig. 4.2Output wiring
►
NOTICE
The voltage of an external auxiliary voltage source may not exceed 36 V.
The output is designed for minimal load resistance of 2 kohm.
D-
D+

Configuration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
7
►
NOTICE
5 Configuration
Before starting
Before switching on, make sure that the device was stored at the specified ambi-
ent temperature (-20 ... +55 °C) for at least 30 minutes.
Parameters of the module can be read, edited and saved with “M110 Configurator”
software .The full list of parameters is shown in the Table 5.1.
To control the module via Modbus network refer section 6.3 “Modbus addressing”
The module should be configured first before operating in RS485 network.
Proceed as follows:
─install the configuration software “M110 Configurator” on the PC
─connect the module to the USB interface of the PC over RS485-USB interface
adapter IC4 (not included)
─connect the power supply to the terminals 24V / 0V
─turn on the device
─start the M110 Configurator
If the factory settings of the module have not been changed, the connection to the mod-
ule is automatically established, the module automatically recognized, its configuration
parameters read out and an appropriate configuration mask open.
If it does not happen, parameters of the configurator should be changed.
Table 5.1 Configuration parameters
Name Parameter Valid value Meaning Default
Basic parameters
dev Device up to 8 characters MU110-6U
ver Firmware version up to 8 characters manufacturer
Network parameters
bPS Baud rate, kbit/s
0 2.4
9.6
1 4.8
2 9.6
3 14.4
4 19.2
5 28.8
6 38.4
7 57.6
8 115.2
LEn Data bits * 0 7 8
1 8
PrtY Parity *
0 none
none
1 even
2 odd
Sbit Stop bits * 0 1 1
1 2

Configuration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
8
Name Parameter Valid value Meaning Default
A.Len Address bits 0 8 8
1 11
Addr Device address 1…247 16
Prot Protocol
0 akYtec
akYtec
1 Modbus-RTU
2 Modbus-ASCII
t.out Time-out, s 0…600 0
Rs.dL Response delay, ms 0…45 2
Output parameters
O.ALrSafe output status, % 0…100 0
*Invalid network parameter combinations:
─prty=0; sbit=0; len=0
─prty=1; sbit=1; len=1
─prty=2; sbit=1; len=1

Operation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
9
6 Operation
The module is controlled by the Master device in a RS485 network. The addresses from 1
to 247 can be used. The address 0 is reserved for broadcasting.
The following Modbus functions are supported:
─03 (0x03) Read Holding Registers
─04 (0x04) Read Input Registers
─16 (0x10) Preset Multiple Registers
The register addresses is given in Table 6.2.
The output status according to the output value is given in Table 6.1.
Table 6.1 Output status
Output value *
Output Status
Configuration
Modbus command
0
0
0 V
1
1000
10 V
0…1
0…1000
0…10 V
* Note:
The configuration program uses internal communication protocol instead of Modbus pro-
tocol. For this reason the ranges of output value during configuration and in Modbus
command can differ. For example, in order to activate output AO1 during the functional
test, the output value should be set to 1, but in Modbus command the output value 1000
should be recorded in the register 0000.
6.1 Output functional test
In order to check the functioning of the device outputs procced as follows:
─Connect the module to the computer USB-port via USB/RS485 adapter
─Connect a voltmeter and a resistor box as shown in Fig. 6.1
─Start the configuration program "M110 Configurator"
─If connection with the module has not been established automatically, network
parameters of the configuration program should be changed
─Select the menu path "Device -> I/O Status…" to open "Output status" window
─Set individual outputs to 0 or 1 to check their functionality
─The functional test is successful, if the voltage is within the range between 0±0.05
V at 0 and 10±0.05 V at 1.
─Contact the Technical Support of akYtec GmbH in case of any deviations.
Fig. 6.1 Functional test

Operation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
10
6.2 Fault state
If data exchange via RS485 is interrupted, i.e. the command is not received from the net-
work Master within the time specified in t.out parameter, then all outputs with the pa-
rameter Log=0 will be set to the safe state. The safe state is the output value specified in
the parameter O.ALr(Safe output status) for each output. In this case:
─LED FAULT is on
─LED FAULT is off with a new query received from the Master
─The outputs remain in the safe state until the command from the Master about
status change is received
─If t.out parameter is set to 0, the fault state doesn’t occur.
Parameters t.out and O.ALrcan be set during configuration or operation and are saved
in the non-volatile memory.
►
NOTICE
Non-volatile memory
Since the non-volatile memory is not unlimited rewritable (~ 1 million), it is not
recommended to change the Safe output status (O.ALr) by a Modbus command so
often as the output value.
6.3 Modbus addressing
All variables and parameters in the Table 6.2 are of the type INT16
R – read access
W – write access
Table 6.2 Modbus register
Parameter
Valid value
Access
Address
Configura-
tion
Modbus
command hex dec
Output value AO1
0…1
0…1000
RW
0000
0000
Output value AO2
0…1
0…1000
RW
0001
0001
Output value AO…
0…1
0…1000
RW
…
…
Output value AO6
0…1
0…1000
RW
0005
0005
Safe output status (O.ALr) AO1
0…100
0…1000
RW
0010
0016
Safe output status (O.ALr) AO2
0…100
0…1000
RW
0011
0017
Safe output status (O.ALr) AO…
0…100
0…1000
RW
…
…
Safe output status (O.ALr) AO6
0…100
0…1000
RW
0015
0021
Time-out (t.out), s.
0…600
0…600
RW
0030
0048

Restore factory settings
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
11
7 Restore factory settings
If the communication between the module and PC cannot be established and the network
parameters of the module are unknown, the default network settings should be restored.
Proceed as follows:
─power off the module
─open the front cover
─set the jumper X2
─the module will operate with the default network parameters, the user settings
remain stored
─switch the power on
DANGER
Dangerous voltage
The voltage on some components of the circuit board can be dangerous! Direct
contact with the circuit board or penetration of a foreign body in the enclosure
must be avoided!
─start the “M110 Configurator” software
─set the parameters to default (see Table 7.1) or click “Use factory settings” (see
Fig. 7.1) in the dialog window “Connection to device”
Fig. 7.1 “Connection to device” dialog window
─click “Connect” to establish the connection with factory settings
─the main window with the device mask opens
─saved user parameters can be read now (see Fig. 7.2)
─open the folder “Network parameters” and note the user network parameters
Fig. 7.2 Device mask

Restore factory settings
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
12
─close M110 Configurator
─switch the power off
─remove the jumper X2
─close the front cover
─switch the power on again
─start M110 Configurator
─enter the noted network parameters
─click “Connect”
The module is now ready for operation.
Table 7.1 Network factory settings
Parameter Name Factory setting
Baud rate, bit/s bPS 9600
Data bits LEn 8
Parity PrtY None
Stop bits Sbit 1
Address bits A.Len 8
Address Addr 16
Response delay, ms Rs.dL 2

Maintenance
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
13
8 Maintenance
The maintenance includes:
-cleaning of the housing and terminal blocks from dust, dirt and debris
-checking the fastening of the device
-checking the wiring (connecting leads, fastenings, mechanical damage).
The device should be cleaned with a damp cloth only. No abrasives or solvent-containing
cleaners may be used. The safety information in section 3 must be observed when carry-
ing out maintenance.

Transportation and storage
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
14
9 Transportation and storage
Pack the device in such a way as to protect it reliably against impact for storage and
transportation.
The original packaging provides optimum protection.
If the device is not taken immediately after delivery into operation, it must be carefully
stored at a protected location. The device should not be stored in an atmosphere with
chemically active substances.
Permitted storage temperature: -25...+55 °C
►
NOTICE
Transport damage, completeness
The device may have been damaged during transportation.
Check the device for transport damage and completeness!
Report the transport damage immediately to the shipper and akYtec GmbH!

Scope of delivery
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
15
10 Scope of delivery
1
1
–Module MU110-6U
–Short guide

Appendix A Dimensions
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
16
Appendix A Dimensions
Fig. A.1 External dimensions
Fig. A.2 Wall mounting dimensions
57
63
110
55
102

Appendix A Dimensions
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
17
Fig. A.3 Replacement of terminal blocks
This manual suits for next models
1
Table of contents
Other Akytec I/O System manuals

Akytec
Akytec MK210-312 User manual

Akytec
Akytec MV210-101 User manual

Akytec
Akytec MU110-8I User manual

Akytec
Akytec MV210-221 User manual

Akytec
Akytec MV110-8A User manual

Akytec
Akytec MK210-311 User manual

Akytec
Akytec MU210-410 User manual

Akytec
Akytec MV110-8AS User manual

Akytec
Akytec PRM 3 Series User manual
Popular I/O System manuals by other brands

RJG
RJG Lynx OA1-M-V product manual

Keysight
Keysight VXI Bus 75000 C Series User and programming manual

ABB
ABB NEXUS-3 Series user guide

National Instruments
National Instruments PXIe-4480 CALIBRATION PROCEDURE

Helmholz
Helmholz TB20 manual

National Instruments
National Instruments FieldPoint FP-AI-100 operating instructions