RJG Lynx OA1-M-V User manual

PRODUCT MANUAL
Training and Technology for injecTion Molding
Lynx™ Shielded AnAlog output
Module
OA1‑M‑V

PRINT DATE 02.25.2019
REVISION NO. 0

Product Manual | Lynx™ Shielded Analog Output Module OA1‑M‑V RJG, Inc. i
PRODUCT MANUAL
Lynx™ Shielded AnAlog output
Module
OA1‑M‑V
INTRODUCTION
DISCLAIMER III
PRIVACY III
ALERTS III
PRODUCT DESCRIPTION
APPLICATIONS 1
PROCESS MONITORING AND CONTROL 1
OPERATION 1
PLASTIC PRESSURE OUTPUT 1
STROKE OUTPUT 1
VELOCITY OUTPUT 1
MACHINE CONTROL, FLOW VALVE, AND PRESSURE VALVE OUTPUTS 1
DIMENSIONS 2
CABLE LENGTH 2
INSTALLATION
INSTALLATION OVERVIEW 3
OA1‑M‑V 3
eDART CONNECTION 3
INSTALLATION SPECIFICATIONS 4
REQUIREMENTS 4
MOUNTING 4
WIRING 4
CONNECTIONS 4

Lynx™ Shielded Analog Output Module OA1‑M‑V | Product Manual
ii RJG, Inc.
MAINTENANCE
CLEANING 5
REGULAR CLEANING 5
TESTING 5
OA1‑M‑V 5
WARRANTY 5
RJG, INC. STANDARD WARRANTY 5
PRODUCT DISCLAIMER 5
TROUBLESHOOTING
CUSTOMER SUPPORT 7
RELATED PRODUCTS
COMPATIBLE PRODUCTS 9
SHIELDED ANALOG OUTPUT MODULE CABLE C‑OA1‑M‑3M 9
LYNX CABLES CE‑LX5 9
eDART PROCESS CONTROLLER 9
SIMILAR PRODUCTS 10
LYNX SURFACE‑MOUNT ANALOG OUTPUT MODULE OA1‑S‑V 10
LYNX COMMUNICATIONS ADAPTER
DIN/LX‑D 10
PRODUCT MANUAL
lynx™ Shielded AnAlog output
Module
OA1‑M‑V

Product Manual | Lynx™ Shielded Analog Output Module OA1‑M‑V RJG, Inc. iii
INTRODUCTION
Read, understand, and comply with all following
instructions. This guide must be kept available
for reference at all times.
DISCLAIMER
Inasmuch as RJG, Inc. has no control over the
use to which others may put this material, it
does not guarantee that the same results as
those described herein will be obtained. Nor
does RJG, Inc. guarantee the effectiveness or
safety of any possible or suggested design for
articles of manufacture as illustrated herein by
any photographs, technical drawings, and the
like. Each user of the material or design or
both should make his own tests to determine
the suitability of the material or any material
for the design as well as the suitability of the
material, process, and/or design for his own
particular use. Statements concerning possible
or suggested uses of the material or designs
described herein are not to be construed as
constituting a license under any RJG, Inc. patent
covering such use or as recommendations
for use of such material or designs in the
infringement of any patent.
PRIVACY
Designed and developed by RJG, Inc. Manual
design, format and structure copyright 2018
RJG, Inc. content documentation copyright
2018 RJG, Inc. All rights reserved. Material
contained herein may not be copied by hand,
mechanical, or electronic means, either whole
or in part, without the express written consent
of RJG, Inc. Permission will normally be granted
for use in conjunction with inter‑company use
not in conflict with RJG’s best interests.
ALERTS
The following three alert types are used as
needed to further clarify or highlight information
presented in the manual:
Term
A definition of a term or terms used in the
text.
NOTE A note provides additional information
about a discussion topic.
CAUTION A caution is used to make the
operator aware of conditions that can cause
damage to equipment and/or injury to personnel.

Lynx™ Shielded Analog Output Module OA1‑M‑V | Product Manual
iv RJG, Inc.

Product Manual | Lynx™ Shielded Analog Output Module OA1‑M‑V RJG, Inc. 1
PRODUCT DESCRIPTION
The Lynx shielded analog output module
is a DIN‑rail‑mounted module the is wired
to the molding machine in order to output
a 0–10 V DC signal representing molding
parameters or as an external machine transfer.
APPLICATIONS
PROCESS MONITORING AND CONTROL
The eDART system requires various inputs
from the injection molding machine in order to
accurately calculate significant process values for
monitoring and control.
The OA1‑M‑V supplies an output from the
eDART to the molding machine to control
machine transfer.
OPERATION
The OA1‑M‑V is often used to provide outputs
to the injection molding machine controller
collected by the eDART.
PLASTIC PRESSURE OUTPUT
The OA1‑M‑V is used to provide a signal to
the injection molding machine to indicate
the machine to transfer from pressure to
hold (V→P). The shielded output module
cable C‑OA1‑M‑3M is wired to the machine
input card which accepts the signal; the
C‑OA1‑M‑3M is connected to the OA1‑M‑V,
which collects the signal for use from the
eDART. In the eDART software, the module is
configured to enable V→P.
STROKE OUTPUT
The OA1‑M‑V is used to provide the molding
machine with the stroke output collected
by the eDART. The shielded output module
cable C‑OA1‑M‑3M is wired to the machine
input card which accepts the signal; the
C‑OA1‑M‑3M is connected to the OA1‑M‑V,
which collects the signal for use from the
eDART.
VELOCITY OUTPUT
The OA1‑M‑V is used to provide the molding
machine with the velocity output collected
by the eDART. The shielded output module
cable C‑OA1‑M‑3M is wired to the machine
input card which accepts the signal; the
C‑OA1‑M‑3M is connected to the OA1‑M‑V,
which collects the signal for use from the
eDART.
MACHINE CONTROL, FLOW VALVE, AND
PRESSURE VALVE OUTPUTS
In some circumstances, the OA1‑M‑V can
be used to provide a machine control, flow
valve, or pressure valve output (from eDART
software v9.xx only). These instances are
often specialized and infrequent; refer to RJG
customer support for more information on
these uses.

Lynx™ Shielded Analog Output Module OA1‑M‑V | Product Manual
2 RJG, Inc.
DIMENSIONS
CABLE LENGTH
The C‑OA1‑M‑3M is 9.8 ft. (3 m) long.
CABLE LENGTH

Product Manual | Lynx™ Shielded Analog Output Module OA1‑M‑V RJG, Inc. 3
INSTALLATION
INSTALLATION OVERVIEW
The shielded machine interface modules are
mounted to a solid surface, such as the machine
frame, inside the molding machine on a DIN
rail.
OA1‑M‑V
The shielded analog output module cable
C‑OA1‑M‑3M is wired directly to the machine
(to an input card) on one end, and connected
to the OR2‑M on the other using the four‑pin
connector. The shielded analog output module
is connected to the ID7‑M‑SEQ (or DIN/LX‑D),
or other shielded module using the integrated
amphenol connector.
eDART CONNECTION
A Lynx cable CE‑LX5 is connected to the Lynx
port on the ID7‑M‑SEQ and a Lynx port on
the eDART to provide it with the machine’s
sequence signals for process monitoring and
control calculations, along with the other
installed machine interface module signals.

Lynx™ Shielded Analog Output Module OA1‑M‑V | Product Manual
4 RJG, Inc.
INSTALLATION SPECIFICATIONS
The instructions that follow are a general guide;
actual steps necessary to install this product
will vary based on injection molding machine
manufacturer, model, and options.
A clearance height of 6” (152 mm) from the face
of the module(s) is recommended for mounting.
REQUIREMENTS
CAUTION Before beginning OA1‑M‑V
installation, disconnect and lockout/tag‑out any
and all power to the molding machine. Failure to
comply will result in personal injury or death, and
damage or destruction of equipment.
MOUNTING
Mount the OA1‑M‑V module to a solid
surface—such as the molding machine frame—
using the supplied 1.38” (35 mm) DIN rail. A
clearance height of 6” (152,4 mm) from the face
of the module is recommended.
NOTE Modules and connecting cables must
be located away from any static sources, such as
feeder tubes and material hoppers.
WIRING
The OA1‑M‑V is interfaced to a machine’s input
card. The C‑OA1‑M‑3M cable has color‑coded
wires to simplify installation. Refer to the table
at right for the correct wire/signal combinations
for installation.
OUTPUT TYPE SIGNAL COLOR
0–10 V DC Positive Signal (+) Brown
0 V DC Negative Signal (‑) Black
No Connection N/A Blue
No Connection N/A White
CONNECTIONS
Connect the OA1‑M‑V module to the shielded
sequence module ID7‑M‑SEQ—or shielded
communications module DIN/LX‑D—using the
integrated, side‑mount amphenol connector.
Connect the C‑OA1‑M‑V cable to the OA1‑M‑V
module.

Product Manual | Lynx™ Shielded Analog Output Module OA1‑M‑V RJG, Inc. 5
MAINTENANCE
The shielded analog output module requires
little to no maintenance provided that all
installation instructions are followed.
CLEANING
REGULAR CLEANING
Cables must be installed in areas free from oil,
dirt, grime, and grease.
RJG, Inc. recommends the following cleaners:
• Microcare MCC‑CCC Contact Cleaner C
• Microcare MCC‑SPR SuprClean™
• Miller‑Stephenson MS‑730L Contact Re‑Nu®
TESTING
OA1‑M‑V
Test the OA1‑M‑V outputs after assignment
using the Sensor Locations tool in version 9
software, or in Machine Setup utilities in version
10 software.
WARRANTY
RJG, INC. STANDARD WARRANTY
RJG, Inc. is confident in the quality and
robustness of the shielded analog output
module, and so are offering a one‑year
warranty. RJG’s products are guaranteed against
defects in material and workmanship for one
year from the original date of purchase. The
warranty is void if it is determined that the
adapter was subjected to abuse or neglect
beyond the normal wear and tear of field
use, or in the event the adapter box has been
opened by the customer.
PRODUCT DISCLAIMER
RJG, Inc. is not responsible for the improper
installation of this equipment, or any other
equipment RJG manufactures.
Proper RJG equipment installation does not
interfere with original equipment safety features
of the machine. Safety mechanisms on all
machines should never be removed.

Lynx™ Shielded Analog Output Module OA1‑M‑V | Product Manual
6 RJG, Inc.

Product Manual | Lynx™ Shielded Analog Output Module OA1‑M‑V RJG, Inc. 7
TROUBLESHOOTING
CUSTOMER SUPPORT
Contact RJG’s Customer Support team by
phone or email.
RJG, Inc. Customer Support
P: 800.472.0566 (Toll Free)
P: +1.231.933.8170
www.rjginc.com/support

Lynx™ Shielded Analog Output Module OA1‑M‑V | Product Manual
8 RJG, Inc.

Product Manual | Lynx™ Shielded Analog Output Module OA1‑M‑V RJG, Inc. 9
RELATED PRODUCTS
The shielded analog output module is
compatible with other RJG, Inc. products
for use with the eDART process control and
monitoring system.
COMPATIBLE PRODUCTS
SHIELDED ANALOG OUTPUT MODULE
CABLE C‑OA1‑M‑3M
The shielded analog output module cable
C‑OA1‑M‑3M ( 1at right) cable features a metal
sheathing and shielding suited for the heat and
stress found in injection molding environments.
Designed specifically for use with RJG, Inc.’s
dual‑relay output module OA1‑M‑V and the
eDART System, the C‑OA1‑M‑3M provides a
connection from molding machines’ output card
and the RJG, Inc. C‑OA1‑M‑3M.
LYNX CABLES CE‑LX5
The Lynx sensor cable ( 2at right) is a
polypropylene‑coated cable suited for the
heat and stress found in injection molding
environments. The cable is available in lengths
11.8–472.4” (0,3–12 m), and can be ordered
with straight or 90° fittings. One CE‑LX5 is
required to interface the ID7‑M‑SEQ with the
eDART system.
eDART PROCESS CONTROLLER
The eDART process controller ( 3at right) is
the base hardware unit for the eDART system.
The eDART system is the most powerful process
control system in the industry, allowing molders
to stabilize and control injection molding
processes and contain bad parts, ensuring high
quality and cost‑reduction.
1
2
3

Lynx™ Shielded Analog Output Module OA1‑M‑V | Product Manual
10 RJG, Inc.
SIMILAR PRODUCTS
The following products, similar to the OA1‑M‑V,
are compatible for use with the eDART process
control and monitoring system.
LYNX SURFACE‑MOUNT ANALOG OUTPUT
MODULE OA1‑S‑V
The Lynx surface‑mount analog output module
OA1‑S‑V ( 1at right) is a surface‑mounted
module that interfaces the eDART and any
sensor or input that accepts a 0–10 V signal.
This module is shielded to ensure high quality
data even in rugged molding environments.
LYNX COMMUNICATIONS ADAPTER
DIN/LX‑D
The Lynx communications adapter DIN/LX‑D
(2at right)is a shielded, DIN‑rail‑mounted
module that interfaces other RJG, Inc. shielded
machine interface modules with the eDART
system when the ID7‑M‑SEQ is not used. This
module is shielded to ensure high quality data
even in rugged molding environments, and
designed to be mounted on standard 35 mm
DIN rails often found in machine panels.
1
2


LOCATIONS / OFFICES
USA RJG USA (HEADQUARTERS)
3111 Park Drive
Traverse City, MI 49686
P +01 231 947‑3111
F +01 231 947‑6403
www.rjginc.com
ITALY NEXT INNOVATION SRL
Milano, Italy
P +39 335 178 4035
it.rjginc.com
MEXICO RJG MEXICO
Chihuahua, Mexico
P +52 614 4242281
es.rjginc.com
SINGAPORE RJG (S.E.A.) PTE LTD
Singapore, Republic of
Singapore
P +65 6846 1518
sales@swg.rjginc.com
en.rjginc.com
FRANCE RJG FRANCE
Arnithod, France
P +33 384 442 992
sales@fr.rjginc.com
fr.rjginc.com
CHINA RJG CHINA
Chengdu, China
P +86 28 6201 6816
zh.rjginc.com
GERMANY RJG GERMANY
Karlstein, Germany
P +49 (0) 6188 44696 11
de.rjginc.com
KOREA CAEPRO
Seoul, Korea
P +82 02‑2113‑1870
www.caepro.co.kr
IRELAND/UK RJG TECHNOLOGIES, LTD.
Peterborough, England
P +44(0)1733‑232211
info@rjginc.co.uk
www.rjginc.co.uk
Table of contents
Popular I/O System manuals by other brands

ICP DAS USA
ICP DAS USA ET-7000/PET-7000 Series user manual

Pilz
Pilz PSSu H F PN o operating manual

Allen-Bradley
Allen-Bradley 1756-IF8I user manual

Zeta Alarm Limited
Zeta Alarm Limited SmartConnect SCM-RM instruction manual

Festo
Festo SPC200-2AI-U Brief description

SIIG
SIIG Cyber 1S1P PCIe Quick installation guide

Crestron
Crestron DMB-4K-CPU-128 Installation guides

Opal-RT
Opal-RT OP8615 user manual

Rockwell Automation
Rockwell Automation Series C installation instructions

National Instruments
National Instruments 9229 Getting started guide

DATAEAGLE
DATAEAGLE Compact 2 Series Quick reference guide

Siemens
Siemens Simatic S7-1500 Function manual