Akytec MV110-8AS User manual

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
MV110-8AS
Analog input module
8 channel
User guide
MV110-8AS_2019.08_0226_EN
© All rights reserved
Subject to technical changes and misprints

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
1
Contents
1. Description......................................................................................................................................................2
1.1 Function...................................................................................................................................................2
1.2 RS485 network ........................................................................................................................................2
1.3 Design......................................................................................................................................................2
2. Specifications.................................................................................................................................................4
2.1 Galvanic isolation.....................................................................................................................................4
2.2 Environmental conditions.........................................................................................................................4
3. Safety...............................................................................................................................................................6
3.1 Intended use............................................................................................................................................6
4. Installation.......................................................................................................................................................7
4.1 Wiring.......................................................................................................................................................7
4.1.1 Inputs ...................................................................................................................................................7
4.1.2 Different input signals ..........................................................................................................................9
5. Configuration................................................................................................................................................10
6. Operation.......................................................................................................................................................12
6.1 Signal processing ..................................................................................................................................12
6.1.1 Sampling............................................................................................................................................12
6.1.2 Signal change rate limitation..............................................................................................................12
6.1.3 Digital Filter........................................................................................................................................12
6.1.4 Linear signal.......................................................................................................................................12
6.2 Modbus communication.........................................................................................................................13
6.3 Error diagnosis.......................................................................................................................................14
7. Factory settings restoration........................................................................................................................15
8. Maintenance..................................................................................................................................................17
9. Transportation and storage.........................................................................................................................18
10. Scope of delivery..........................................................................................................................................19
Appendix A. Dimensions ..................................................................................................................................20

Description
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
2
1. Description
1.1 Function
The MV110-8AS analog input module is an extension module with 8 analog inputs for the
following standard signals:
– 4-20 mA
– 0-20 mA
– 0-5 mA
– 0-10 V
The module has the following galvanically isolated circuits:
– Power supply
– Analog inputs
– RS485 interface
Separate inputs are not galvanically isolated.
The module performs the following functions:
– Connection of peripherals with analog outputs
– Conversion of analog signals to digital values
– Sensor-based status diagnostics
– Diagnostics of RS485 network status
– Generation of appropriate error signals or alarm signals
– Slave device in Modbus protocol structure
The module supports Modbus RTU, Modbus ASCII protocols with automatic protocol
identification.
The module is to be configured using ‘M110 Configurator’ software via RS485-USB inter-
face adapter (not included).
1.2 RS485 network
The I/O modules of Mx110 series use common standard RS485 for data exchange. The
RS485 serial interface is based on two-wire technology and half-duplex mode. Protocols
Modbus RTU, Modbus ASCII and akYtec are supported. The network consists of a mas-
ter device and can contain up to 32 slave devices. The maximum length is 1200 m. The
number of slave devices and the network length can be increased with using a RS485
interface repeater.
Separate devices (slave devices) are connected according to linear (bus) topology. It
means that the line goes from the first device to the second one, from the second one to
the third one, etc. Star connections and spur lines are not allowed.
Line reflections always occur at the open bus ends (the first and the last node). The high-
er the chosen data transmission rate, the stronger they are. A terminating resistor is
needed to minimize reflections. Experience proves that the most efficient practice is to
use terminating resistors of 150 ohm.
The module can be used as slave devices only. Master device can be PLC, PC with
SCADA software or control panel.
1.3 Design
─Enclosure: plastic, grey, for DIN-rail or wall mounting
─Terminal blocks: 2 plug-in terminal blocks with 24 screw terminals
─LED „POWER“: power supply indicator
─LED „RS-485“: flashes at data exchange via RS485 interface
─LED „FAULT“: is on in case of fault status (see 6.3)

Description
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
3
Fig. 1.1 Front View
Dimensional Sketches are given in Appendix A.
Under the cover on the front panel of the module there is a 10-pole pin strip XP1 with the
jumper JP1 (see Figure 4.1, 7.3) for factory settings restoration (see 7).

Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
4
2. Specifications
Table 2.1 General Specifications
Power supply
24 (21…35) V DC
Power consumption, max
6 W
Inputs
digital
analog
8
Outputs
digital
-
analog
Sampling time for each input (1)
5±2% ms
Basic error
0.25 %
Temperature influence (2)
0.12 %
Resolution
0(4)-20 mA
4 μA
0-5 mA
1 μA
0-10 V
2 mV
Input resistance
0(4)-20 mA
130…250 ohm
0-5 mA
130…500 ohm
0-10 V
>200 ohm
Permissible input voltage
-40…+40 V
RS485 interface
Terminals
D+, D-
Protocols
Modbus RTU/ASCII, akYtec
Baud rate
2.4…115.2 kbit/s
Data bits
7, 8
Parity control
even, odd, none
Stop bits
1, 2
Dimensions
63 x 110 x 75 mm
Weight
approx. 240 g
Material
plastic
(1) Because the sampling of inputs is performed sequentially, the total sampling time is
equal to the sum of the times of all connected inputs.
(2) % FS, per 10 °C of deviation from (20 ±5) °C within the permissible limits.
2.1 Galvanic isolation
The device has three potential groups:
─Power supply 24 VDC
─Analog Inputs
─RS485
Table 2.2Galvanic isolation
Groups
Analog inputs
(3-12; 15-24) RS485 (13;14) Enclosure
Power supply (1.2)
1500 V
1500 V
3000 V
Analog inputs
(3-12; 15-24) - 1500 V 3000 V
RS485 (13;14)
-
-
3000 V
2.2 Environmental conditions
The module is designed for natural convection cooling. It should be taken into account
when choosing the installation site.
The following environment conditions must be observed:
─clean, dry and controlled environment, low dust level

Specifications
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
5
─closed non-hazardous areas, free of corrosive or flammable gases
Table 2.3Environmental conditions
Condition Permissible range
Ambient temperature
-20…+55°C
Transportation and storage
-25…+55°C
Relative humidity
up to 80% (at +25°C, non-condensing)
IP code
IP20
Altitude
up to 2000 m above sea level

Safety
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
6
3. Safety
Explanation of the symbols and keywords used:
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury.
►
NOTICE
NOTICE indicates a potentially harmful situation which, if not avoided, may result
in damage of the product itself or of adjacent objects.
3.1 Intended use
The device has been designed and built solely for the intended use described in this
guide, and may only be used accordingly. The technical specifications contained in this
guide must be observed.
The device may be operated only in properly installed condition
Improper use
Any other use is considered improper. Especially to note:
─This device should not be used for medical devices which receive, control or other-
wise affect human life or physical health.
─The device should not be used in an explosive environment.
─The device should not be used in an atmosphere with chemically active substance

Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
7
4. Installation
WARNING
Improper installation
Improper installation can cause serious or minor injuries and damage the de-
vice. Installation must be performed only by fully qualified personnel.
─The device is intended to be mounted in a cabinet on DIN-rail or on the wall.
─Install the module in a clean, dry and controlled environment. Further requirements
are described in paragraph 2.1.
─The module is designed for convective self-cooling. This should be taken into account
when selecting the installation site.
4.1 Wiring
WARNING
Dangerous voltage
Electric shock could kill or seriously injure.
All electrical connections must be performed by a fully qualified electrician.
Ensure that the mains voltage matches the voltage marked on the nameplate!
Ensure that the device is provided
with its own power supply line and electric
fuse!
►
NOTICE
Switch on the power supply only after the wiring of the device has been com-
pletely performed.
– Terminal connections are shown in Fig. 4.1, terminal assignments are given in Table
4.1.
– The inputs should be wired in accordance with Fig. 4.2 – 4.3.
– Connect the supply voltage to the terminals 24V and 0V.
– The maximum wire cross-section for power supply is1.5 mm²
►
NOTICE
EMC-safety
Signal cables should be routed separately or screened from the supply cables.
Only shielded cable may be used for data transmission and signal lines.
Shield in the control cabinet for best electromagnetic immunity recommended.
– Connect the RS485 line to the terminals D+ and D-.
– Use twisted pair cable for RS485 connection. The length of the line should not ex-
ceed 1200 m.
4.1.1 Inputs
The following must be observed:
– All the AIx terminals are internally connected.
– The total resistance of the sensor output with connection lines must not exceed 100 ohm.
– When connecting, one must ensure that the permissible input voltage (see Table 2.1)
is not exceeded. If the voltage is within the permissible limits the input current will be
limited to 35 mA automatically.

Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
8
Fig. 4.1 Electrical connections
Table 4.1 Terminal assignments
No
Designation
Description
No
Designation
Description
1
0 V
Power supply
13
D-
RS485 D-
2
24 V
Power supply
14
D+
RS485 D+
3
free
15
free
4
free
16
free
5
AI1-
common negative
17
AI5-
common negative
6
AI1+
AI1+
18
AI5+
AI5+
7
AI2-
common negative
19
AI6-
common negative
8
AI2+
AI2+
20
AI6+
AI6+
9
AI3-
common negative
21
AI7-
common negative
10
AI3+
AI3+
22
AI7+
AI7+
11
AI4-
common negative
23
AI8-
common negative
12
AI4+
AI4+
24
AI8+
AI8+
When connecting current and voltage signals take into account an external additional
voltage source
Fig. 4.2 Connection of 2-wire sensors
Fig. 4.3 Connection of 3-wire sensors

Installation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
9
4.1.2 Different input signals
Each input can be configured for any type of signal individually. The signal type (sensor
type) must be selected for in-t parameter. A full list of configuration parameters is pre-
sented in Appendix B.
If a sensor has a positive output you can use a common additional voltage source. In
case of a negative output, a separate additional voltage source should be provided for
each sensor.

Configuration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
10
5. Configuration
►
NOTICE
Before starting
Before switching on, make sure that the device has been kept at the specified
ambient temperature (-20... +55 ° C) for at least 30 minutes.
The configuration tool ‘M110 Configurator’ allows viewing, editing and saving of parame-
ters. The complete list of parameters is shown in Table 5.1.
The module must be configured in order to use it in RS485 network. Proceed as follows:
– install the configuration software ‘M110 Configurator’ on the PC
– connect the module to the USB interface of the PC over USB/RS485 adapter (not
included)
– connect a power source 24V DC to the module terminals 24V/0V
– switch the power on
– run the M110 Configurator
If the factory settings of the module have not been changed, then connection with the
module is established automatically. The module is automatically identified, the module
configuration parameters are readout and a window with an appropriate configuration
mask opens.
Otherwise, the network parameters of the configurator must be adapted.
Table 5.1 Configuration parameters
Name Parameter Valid value Meaning
Default
setting
Common parameters
dev Device up to 8 characters
MV110-
8AS
ver Firmware version up to 8 characters
Manufac-
turer
n.Err
Last error code
0…255 (at power on – 0)
–
exit Exit code
0
software reset
6
hardware reset
7
power on
8
watchdog timer
Network parameters
bPS Baud rate, kbit/s
0
2.4
9.6
1
4.8
2
9.6
3
14.4
4
19.2
5
28.8
6
38.4
7
57.6
8
115.2
PrtY Parity *
0
none
None
1
even
2
odd
Sbit Stop bits *
0
1
1
1
2
Addr
Device address
1…247
16
Rs.dL
Response delay,
ms
0…45 2
Input Parameters

Configuration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
11
Name Parameter Valid value Meaning
Default
setting
ComF Input filter for all
channels
0
off
off
1
50 Hz, first-order
2
50 Hz, second-order
3
50 Hz, fourth-order
4
200 Hz, first-order
in-t Sensor type
0
off
4-20 mA
1
4-20 mA
2
0-20 mA
3
0-5 mA
4
0-10 V
in.Fd
Filter time con-
stant, ms
10…10000 10
Ain.L
Lower limit
FLOAT32
0
Ain.H
Upper limit
FLOAT32
20000
dP
Decimal point
0…3
0
Peak
Rate of change
limit 1…200 s-1 200
OutF Output filter
0
off
0
1
Exponential filter
2
Moving average fil-
ter, L=2
…
…
16
Moving average fil-
ter, L=16
* Invalid network parameter combinations:
– prty=0; sbit=0; len=0
– prty=1; sbit=1; len=1
– prty=2; sbit=1; len=1

Operation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
12
6. Operation
The module is controlled by the master device in Modbus network.
Following Modbus function s are available: 03, 04 for reading and 15, 16 for writing.
6.1 Signal processing
Inputs are sampled cyclically. The measured values are converted into digital values,
analyzed and processed in accordance with the set parameters. The results are saved in
data registers (Table 6.1).
6.1.1 Sampling
An input is included into the sampling list if the signal type is selected. If the parameter int
is set to OFF, then the input is excluded from the list.
6.1.2 Signal change rate limitation
Signal change rate limitation allows reducing impulse noise efficiently. This limitation can
be adjusted using Peak parameter so that the noise suppression does not affect a meas-
uring signal.
The parameter can be changed within the range from 1 to 200 s-1 in increments of 1 s-1.
Unit 1 s-1 corresponds to 1/200 of the measurement range.
For example, for 4-20 mA signal:
1 s-1 corresponds to 1*16/200 = 0.08 mA - maximum noise suppression
200 s-1 correspond to 200*16/200 = 16 mA - noise suppression is off
If the maximum signal change rate does not exceed 50 mA/s, then
50 mA s
⁄
16 mA =3.125 Measuring range s
⁄
In this case, Peak = 4 guarantees the best noise suppression and the minimum measur-
ing signal impact at the same time.
The Peak factory setting is 200.
6.1.3 Digital Filter
The digital filter consists of two stages.
– At the first stage, a common filter affecting all 8 channels is used. The filter type must
be set in comf. parameter. The filter provides noise suppression with frequencies the
values of which are a multiply of 50 Hz. The filter factory setting is “off”.
– At the second stage, a channel filter is used and must be adjusted in outf. parameter.
– If outf = 1, the exponential filter is on. The filter time constant must be set in in.fd
parameter in ms. The higher the value, the higher the noise resistance and the slower
the input response.
6.1.4 Linear signal
To scale the linear signal (current or voltage) the measurement limits must be set. Pa-
rameters Ain.L ‘Lower limit’ and Ain.H ‘Upper limit’ are set in physical.
If Ain.L<Ain.H, then
Measured value =Ain.L+ (Ain.H-Ain.L)*(Si-Smin)
Smax-Smin
If Ain.L>Ain.H, then
Measured value =Ain.L- (Ain.L-Ain.H)*(Si-Smin)
Smax-Smin
where Smax – is the upper signal limit (for example, 20 for 4-20 mA signal)

Operation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
13
Smin – is the lower signal limit (for example, 4 for 4-20 mA signal)
Si – is the actual signal value
6.2 Modbus communication
Modbus-RTU and Modbus-ASCII protocols are supported.
Modbus functions 03 and 04 for the following parameters are available:
– Measured value
– Time mark
– Error code (see 6.3)
The measured value is in two formats available:
– Integer (16 bits)
– Integer with a time mark (16 bits + 16 bits)
– Floating-point with a time mark (32 bits + 16 bits)
The integer is calculated by multiplication of the measured value by 10dP. The parameter
dP is used for a decimal point and can be set within the range 0…3.
When a floating-point number value is transmitted, the most significant byte of 32-bit data
is stored in the first register (big-endian).
The time mark is cyclic time within the range from 0 to 655.36 seconds with the increment
of 0.01 second saved as a 2 byte integer. It determines the exact time of measurement
within the cycle. When the module is powered on, the cycle starts from 0 and returns to
the initial state in 655.36 seconds.
Table 6.1 Modbus registers
Parameter Description Data type
Input
number
Register
Access
hex
exit
Cause of reset
INT16
0x88
r
n.Err
Last network error
BYTE
0x90
r
bPS
Baud rate
INT16
0x30
r/w
PrtY
Parity
INT16
0x38
r/w
Sbit
Stop bits
INT16
0x40
r/w
Addr
Device address
INT16
0x48
r/w
Rs.dL
Response delay
INT16
0x50
r/w
ComF
Common filters
INT16
0x28
r/w
in-t Sensor type INT16
1
0x00
r/w
…
…
…
8
0x07
r/w
in.Fd Filter time constant INT16
1
0x18
r/w
…
…
…
8
0x1F
r/w
Ain.L Measuring range /
lower limit FLOAT32
1
0x58, 0x59
r/w
…
…
…
8
0x66, 0x67
r/w
Ain.H Measuring range /
upper limit FLOAT32
1
0x68, 0x69
r/w
…
…
…
8
0x76, 0x77
r/w
dP Decimal point INT16
1
0x20
r/w
…
…
…
8
0x27
r/w
Peak Change rate limit INT16
1
0x08
r/w
…
…
…

Operation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
14
Parameter Description Data type Input
number Register Access
hex
8
0x0F
r/w
OutF Channel filter INT16
1
0x10
r/w
…
…
…
8
0x17
r/w
ird Measured value
(INT) INT16
1
0x100
r/w
…
…
…
8
0x107
r/w
irdt Measured value
(INT) with a time
mark
INT16
+INT16
1
0x108,
0x109 r/w
…
…
…
8
0x116,
0x117
r/w
srd Error code INT16
1
0x118
r/w
…
…
…
8
0x11F
r/w
read Measured value
(FLOAT) with a time
mark
FLOAT32
+INT16
1
0x120…0x
122
r/w
…
…
…
8
0x135…0x
137 r/w
6.3 Error diagnosis
When polling inputs, the module controls the status of the connected sensors, the cor-
rectness of communication and the measurement. The detected errors are transmitted
with the response as an error code (see Table 6.2).
If there is a measurement error, the last correctly saved value is transmitted.
Table 6.2 Error Codes
Error Comment Code
Measurement correct
Transmission in progress
0x0000
Measured value error
Measured value incorrect
0xF000
Measurement not ready
Just upon restart
0xF006
Sensor switched off
in-t parameter set to OFF
0xF007
Measurement value too
high
Exceeded the measuring range of the
selected sensor type
0xF00A
Measurement value too
low
Below measuring range of the selected
sensor type
0xF00B
Wire break
Live zero linear signal
0xF00D
Calibration error
Calibration incorrect
0xF00F

Factory settings restoration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
15
7. Factory settings restoration
If communication between the PC and the module cannot be established and the network
parameters of the module are unknown, the factory settings of the network parameters
must be restored. Proceed as follows:
─power off the module
─remove the cover on the front panel of the module
─install jumper JP1 (see Figure 7.3) onto pins 9-10 (bottom row), now the module is
operated with default network parameters, the user settings are saved
─switch the power on
WARNING
Dangerous voltage
Electric shock could kill or seriously injure.
Voltage in some parts of the printed-circuit board can be dangerous! Direct con-
tact with the circuit board or penetration of a foreign body in the enclosure must
be avoided!
─start the ‘M110 Configurator’ software
─in the ‘Connection to device’ window set the parameters to default (see Table 7.1) or
click the ‘Use factory settings’ button (see Fig. 7.1)
Fig. 7.1 Start window of configuration software
– press "Connect" button. Connection is established with the default network parame-
ters
– the main window of the configurator opens
– now the saved network parameters of the module can be read out (see Fig. 7.2)
– open the ‘Network parameters’ folder in the configuration tree, read and note down
the values of the network parameters
– close the Configurator
– switch the power off

Factory settings restoration
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
16
Fig. 7.2 Main window of M110 Configurator
– remove jumper JP1 and install it onto pin 10 (do not strap!)
– close the cover
– switch the power on
– restart the Configurator
– enter the written network parameters
– press ‘Connect’ button
The module is ready for operation.
Table 7.1 Network factory settings
Parameter
Name
Deafault
Baud rate
bPS
9600
Data bits
LEn
8
Parity
PrtY
none
Stop bits
Sbit
1
Address bits
A.Len
8
Address
Addr
16
Response delay, ms
Rs.dL
2
Fig. 7.3 Jumper JP1

Maintenance
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
17
8. Maintenance
The maintenance includes:
– cleaning of the housing and terminal blocks from dust, dirt and debris
– check the device fastening
– checking the wiring (connecting leads, fastenings, mechanical damage)
The device should be cleaned with a damp cloth only. No abrasives or solvent-containing
cleaners may be used. The safety information in section 3 must be observed when carry-
ing out maintenance.

Transportation and storage
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
18
9. Transportation and storage
Pack the device in such a way as to protect it reliably against impact for storage and
transportation.
The original packaging provides optimum protection.
If the device is not taken immediately after delivery into operation, it must be carefully
stored at a protected location. The device should not be stored in an atmosphere with
chemically active substances.
Permitted storage temperature: -25…+55 °C
►
NOTICE
Transport damage, completeness
The device may have been damaged during transportation.
Check the device for transport damage and completeness!
Report the transport damage immediately to the shipper and akYtec GmbH!

Scope of delivery
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
19
10.Scope of delivery
– Module MV110-24.8AS 1
– Short guide 1
Other manuals for MV110-8AS
1
Table of contents
Other Akytec I/O System manuals

Akytec
Akytec MK210-312 User manual

Akytec
Akytec MU210-410 User manual

Akytec
Akytec MV110-8A User manual

Akytec
Akytec MU110-8I User manual

Akytec
Akytec MU110-6U User manual

Akytec
Akytec MK210-311 User manual

Akytec
Akytec MV210-101 User manual

Akytec
Akytec MV210-221 User manual

Akytec
Akytec PRM 3 Series User manual
Popular I/O System manuals by other brands

RJG
RJG Lynx OA1-M-V product manual

Keysight
Keysight VXI Bus 75000 C Series User and programming manual

ABB
ABB NEXUS-3 Series user guide

National Instruments
National Instruments PXIe-4480 CALIBRATION PROCEDURE

Helmholz
Helmholz TB20 manual

National Instruments
National Instruments FieldPoint FP-AI-100 operating instructions