5
Alpha CombiMax 350 and 600
3.1 ELECTRICAL SUPPLY
The CombiMax requires a 230/240 V ~ 50 Hz electrical mains supply.
This appliance must be earthed.
The mains supply to the CombiMax and boiler must be directly connected to the CombiMax terminal block, i.e. not the boiler. A
supply cable from the CombiMax terminal block has been provided for connection to the boiler terminal block.
Notes: 1. If an external control is to be fitted, it must be suitable for 240 V and it must be connected to the boiler terminal block.
2. If an external DHW clock is to be fitted, it must be suitable for 240 V and it must be connected to the CombiMax
terminal block.
Theremustonlybeonecommonisolator,providingcompleteelectricalisolation,fortheCombiMax,boilerandanyexternalcontrols.
However,ifan immersion heateristo be fitted,anindependant electrical supplymustbe provided.Refertothe instructionssupplied
with the Alpha immersion heater kit.
Theapplianceshouldbeconnectedtoafusedthreepinplugandunswitchedshutteredsocketoutlet(bothcomplyingwithBS1363),
or a fused double pole switch with a contact separation of at least 3 mm in both poles using heat resisting cable (i.e. 85°C) not less
than 0.75 mm² (24 x 0.2 mm) to BS 6500 Table 9.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671).
Note:Ifanimmersionheateristobefitted,thismustbesuppliedbyAlphaThermLtd.andbeinstalledaspertheinstructionssupplied
with the kit. A standard 3 kW immersion heater must not be fitted.
DHW CLOCK - Sometimes it may be required to switch off the CombiMax and, if fitted, the secondary circulation overnight to
avoid unnecessary heat loss and operation of the appliance. This can be achieved by connecting an external clock to the 'Ext
Prog' terminals on the CombiMax terminal block, as shown in section 2.4.
Note: When the clock is in an OFF position the CombiMax will not operate, i.e. hot water will only be supplied from the water
left within the storage cyliner. Therefore the OFF periods should be set at times when hot water will not be required.
If a secondary circulation kit is to be fitted, refer to the instructions supplied with the kit.
3.2 LOCATION
The appliance is not suitable for external installation.
The CombiMax and boiler must be installed on a flat vertical wall which is capable of supporting a weight of approximately 92 kg
(350 model) or 130 kg (600 model)..
TheCombiMaxmay be installedinany roomorinternalspace, althoughparticularattention is drawntothe requirements ofthecurrent IEE
WiringRegulations,andinScotland,theelectricalprovisionsoftheBuildingRegulationsapplicableinScotland,withrespecttotheinstallation
in a room or internal space containing a bath or shower. Where it is installed in a room containing a bath or shower, it must not be possible
for a person using the bath or shower to touch any electrical switch or boiler control utilising mains electricity.
The appliance may be installed in a cupboard or compartment, provided it is correctly designed for that purpose and that the
requirements of BS 6798 are complied with.
The appliance does not require any air vents for cooling in the room in which it is installed or when installed in a cupboard or
compartment.
If required, the CombiMax (produced after February 1999, i.e. from serial No. A906) may be located remotely (up to 1 metre)
from the boiler. Refer to Appendix 1, starting on page 18.
3.3 DOMESTIC HOT WATER SYSTEM
To ensure a hot water flow rate of 18 l/min the mains water supply must be capable of delivering 22 l/min to the appliance at 2 bar.
The incoming mains water pressure is regulated to 2.5 bar within the Combimax by a pressure reducing valve. However, all taps
and mixing valves used with the hot water system must be suitable for operating at a pressure of up to 8 bar.
To ensure economic use, the pipe runs between the appliance and taps should be in 15 mm copper pipe and be as short as
possible. Where possible the pipework should be insulated to reduce heat loss.
Showers - A shower may be used with the CombiMax if required.
If a loose or flexible head type shower is used it may require the fitting of a double check valve, to comply with Water Bye Law 17.
Bidets - No anti-syphonage arrangements are necessary, provided the outlets are shrouded and it is not possible to attach a temporary
hand held spray. A supply of direct mains fed hot and cold water is permitted provided the appliance is of the over-rim flushing type.
Before the mains water supply pipe is connected, it should be thoroughly flushed out to avoid the danger of dirt or foreign
matter entering the CombiMax or boiler and the filter incorporated within the pressure reducing valve cleaned.
The stored water temperature is approximately 56°C. In hard water areas this should avoid possible scale build-up. However, if
descaling is necessary contact Alpha Therm Ltd. for guidance.
3 INSTALLATION INFORMATION