Fig. 2-6
Fig. 2-7
INSTALLATIONUSERMAINTENANCE
18Alpha Intec 50CS
Note: e boiler may start-up automatically if the
anti-freeze mode is activated, (item 13 Fig. 2-1).
Also, the boiler can operate for a brief period
of time aer a demand for domestic hot water
in order to return the domestic hot water store
back to temperature.
Important: With the boiler in stand-by mode
() hot water cannot be produced and the
safety systems cannot be guaranteed, such as
pump anti-block, anti-freeze and three way
anti-block.
2.6 FAULT SIGNALS.
e Alpha InTec boiler signals any faults by the
ashing symbol (item 5 in Fig. 2-1) along with
'ERRxx' on the staus display (item 6). Where 'xx'
corresponds to the error code described in the
following table.
Fault signalled Error
code
Ignition failure 01
Safety thermostat fault
(overheating), ame control fault 02
Flue safety thermostat fault 03
Short circuit or bad connection 04
Flow sensor fault 05
Maximum number of resets reached 08
Insucient system pressure 10
Storage tank sensor fault 12
Conguration error 15
Fan fault 16
Flame sensing fault 20
Return sensor fault 23
Push button control panel fault 24
Insucient circulation 27
Loss of remote control
communication 31
Low temperature zone 2 sensor fault 32
Low temperature zone 3 sensor fault 33
Low temperature zone 2 safety
thermostat operation 34
Low temperature zone 3 safety
thermostat operation 35
IMG Bus communication loss 36
Low power supply voltage 37
Loss of ame signal 38
Ignition failure. e boiler lights automatically
with each demand for central heating or
domestic hot water. If it does not light within 10
seconds, the boiler remains in stand-by for 30
seconds, tries again and if the second attempt
fails it will go into 'ignition block' (ERR01). To
eliminate 'ignition block' the Reset button 'C'
must be pressed. e fault can be reset 5 times
•Domestic hot water priority function By
pressing button 'B' the DHW priority function
is deactivated, which is marked by the switch-
o of the symbol (item 15 in Fig. 2-1) on the
display. e disabled function keeps the water
contained in the storage tank at a temperature
of 20°C for 1 hour, giving the priority to central
heating.
•Functioning with external sensor (Fig. 2-6)
optional. In the case of a system with optional
external sensor, the boiler ow temperature
for central heating is managed by the external
sensor depending on the external temperature
measured (Par. 1.5). It is possible to modify
the ow temperature from -15°C to +15°C
with respect to the adjustment curve (Fig.
1-4 Oset value). is correction, which can
be activated using the selector switch (item
3) is kept active for any external temperature
measured. The modification of the offset
temperature is indicated on the display (item 7).
e temperature indicated on the display (item
4) is the current ow temperature and aer a
few seconds from the modication it is updated
with the new correction. 'SET' appears on the
status display (Fig. 2-6). By turning the selector
switch (item 3) in a clockwise direction the
temperature increases and in an anti-clockwise
direction it decreases.
consecutively, aer which the function disabled
for at least one hour. One attempt is allowed
every hour for a maximum of 5 attempts. By
switching the boiler on and o the 5 attempts
are re-acquired. On commissioning or after
extended inactivity it may be necessary to
eliminate the 'ignition fault'. If this phenomenon
occurs frequently, contact a qualied engineer
for assistance.
Safety thermostat fault (overheating). During
operation, if a fault causes excessive overheating
of the boiler, or a fault occurs in the ame control
section, an overheating fault is triggered in the
boiler (ERR02). To eliminate 'overheating fault'
the Reset button 'C' must be pressed. If this
phenomenon occurs frequently, call a qualied
engineer for assistance.
Flue safety thermostat fault. is occurs in
the case of partial internal obstruction (due to
the presence of lime scale) or external blockage
(combustion residues) to the combustion
chamber. To eliminate the 'ue thermostat fault'
the Reset button 'C' must be pressed. Call a
qualied engineer to remove the obstructions.
Short circuit or bad connection. is occurs
in the case of faults to the safety thermostat
(overheating) or fault in the flame sensing
control. e boiler does not start and a qualied
engineer must be called.
Flow sensor fault. If the board detects a fault
with the system NTC ow sensor, the boiler will
not start. Call a qualied egineer for assistance.
Maximum number of resets reached. The
maximum number of 5 resets has been reached.
Refer to previos paragraph - Ignition failure.
Insucient system pressure. Low water pressure
inside the central heating system is detected and
prevents the boiler operating. Check the boiler
pressure gauge (item 1, Fig. 2-1) is between 1
and 1.2 bar. Restore to the correct pressure if
necessary and check for leaks.
Storage tank sensor fault. If the board detects
a fault with the storage tank sensor, the boiler
will not produce domestic hot water. A qualied
engineer must be called.
Conguration error. If the board detects a fault
in the electric wiring, the boiler will not start. If
normal conditions are restored the boiler restarts
without having to be reset. If the fault persists,
contact a qualied engineer for assistance.
Fan fault. is occurs if the fan has a mechanical
or electrical fault. To eliminate the 'fan fault'
the Reset button 'C' must be pressed. If the
fault persists, contact a qualied engineer for
assistance.
Flame sensing fault.is occurs in case of a
leak on the detection circuit or fault in the ame
control unit. e boiler can be reset in order
to allow a new ignition attempt. If the boiler
does not start, contact a qualied engineer for
assistance.
Return sensor fault. In this condition the boiler
does not correctly control the pump if set at
'Auto'. e boiler continues functioning but to
eliminate the fault, contact a qualied engineer
for assistance.
Set central heating ow temperature with
external sensor (optional)
Winter operating mode with external
sensor (optional)
During a request for central heating 'CH ON'
appears on the status indicator (item 6) and at
the same time as burner lights the ame presence
display switches on (item 8) together with the
output scale next to it. e displays (items 7 and
9) indicate the instantaneous outlet temperature
from the primary heat exchanger. In the central
heating mode, if the temperature of the water
contained in the system is sucient to heat the
radiators, the boiler will only function with the
activation of the boiler pump.
From this moment the boiler operates
automatically. With no demand for heat (central
heating or domestic hot water) the boiler goes
into 'stand-by' mode, equivalent to the boiler
being powered without the boiler alight.
18
3
64
7
SET
ESC
°C
°C
1
2
814
4
3
69
7
18
CH ON
MENU
°C
°C°C