Alphacool Eiszeit 2000 User manual

CHILLER 2000
EISZEIT

English

3
Contents
English Manual
Security advice
4
Parts Introduction
5
Installation 6-7
Parameter Adjustment 8-11
Flow Alarm 12
Fault Indication 13-14
Technical Speci cation 15
German Manual 17
French Manual 31

4
Security Advice
Please ensure the power supply and electrical outlet are securely connected and that the
grounding wire is connected.
The average operating current of the chiller is small, but the instantaneous operating current could be
up to 10 amps.
Please make sure there is a stable and normal voltage for the working chiller!
The standard operating voltage for the chiller is 220V.
Mismatched power frequency can cause damage to the chiller!
Be sure you can run a machine with 50 Hz.
To protect the pump, it is strongly advised that you do not run the chiller without having
water in the water reservoir!
The machine is packaged without water in the tank, so make sure the tank has enough water inside
before starting it otherwise the pump can be damaged.When the water level is below the green
(NORMAL) range of the water level gauge, the cooling capacity of our chiller will go down slightly,
hence please ensure the water level is within the green (NORMAL) range. Do not drain the water by
circulating the pump!
Please be sure that the air inlet and air outlet have good ventilation!
There must be at least 30 cm from obstructions to the air outlet in the back of the cooler and at Ieast
8 cm between obstructions and the side air inIet.
The fi lter screen must be regularly cleaned!
It‘s essential to unpick and clean the dust gauze, or a serious blockage could cause a breakdown to the
chiIIer.
Please pay attention to the effect of the condensate water!
When there is higher ambient humidity, and when the water temperature is lower than the ambient
temperature, condensation will appear on the surface of the water circulation pipes and the cooled
components. If this occurs, setting a higher water temperature or keeping connected pipes and cooled
parts warm is recommended.
1
2
3
4
5
6
7

5
Parts Introduction
Power Switch
Front
Back
Display
Flow Alarm
(red)
Normal Flow
(green)
Air Inlet (with
lter)
Fillport
Alarm Output
Terminal
Power Socket
(with fuse)
Water Inlet
Water Outlet
Air Outlet
Water Level
Gauge
Water Drain

6
Installation
Open the Fillport to fi ll in cooling water
Keep observing the water level gauge while adding water slowly. For the
cooling of carbon steel equipment, the water should be added an appropri-
ate amount of anti-corrosion additives.Working in cold areas, it‘s better to
use noncorrosive antifreeze fl uid.
Connect the water in- and outlet to your cooling circuit
Use two G1/4 ttings to connect the chiller with tubes.
Plug in power, turn on the power switch
Do not start up without water in the water reservoir!
1. The rst time of operating may cause more bubbles in the tube leading
to a fl ow alarm. It will go back to normal after a few minutes of operating.
2. Check whether the system leaks immediatly!
3. If the water temperature is below the set value, it is normal the fans and
other components do not work.The temperature controller will automati-
cally control the working conditiond of the compressor,magnetic valve, fans
and other parts based on the set controlling parameters.
4. According to different conditions it may take more time to start the
compressor and other single components. So do not turn off and on again
frequently to avoid damaging parts.
1
2
3

7
Installation
Check the water level
The rst startup of the new chiller empties the air in the water tubes,
leading to a small water level decline in the reservoir. Observe the water
level for a period of time and add adequate water if necessary.A rapid
water level drop may be a sign of system leakage.
Adjust parameters of the temperature controller
The machine uses an intelligent thermostat. Normally, users should not
need to adjust it. If it becomes necessary to do so, please refer to the
“Parameter adjustment” chapter.
4
5

8
Parameters Adjustment - control panel
The new intelligent temperature controller does not need to be adjusted under normal circumstances. It will self-adjust controlling parameters
according to room temperature for meeting equipment cooling requirements.
D1, D2: Indicators of thermostat working state
(1) Press to show the room temperature. Holding the button for 6 seconds to display the restore defaults
(2) keys are for adjusting the controller parameters
(3) RST: Enter button
(4) SET: Function setting key
ON: Thermostat works in intelligent control mode
OFF: Thermostat works in constant temperature control mode
FLASHES: Thermostat is working in parameter setting mode or
displaying room temperature
D1
ON: Chiller works in refridge rating state
OFF: Chiller works in the insulation working state
FLASHES: Chiller works in energy-saving state
D2

9
Parameters Adjustment - Settings
Restore to factory settings
Before machine startup, press and keep holding buttons while turning the chiller on. Release the buttons when the conroller displays „rE“. After
6 seconds the device works in normal order with parameter settings restored to factory settings.
General settings
Press SET to enter the user-de ned state. ( Meanwhile, D1 fl ashes to indicate the controller is in parameters setup status)
(1) Under intelligent mode, the control panel displays the temperature difference value between water and air (F1)
(2) Under constant temperature mode, the control panel displays the set temperature value (F0)
Change settings with and press enter (RST) to save and exit.The new parameters take effect now. Or press SET to exit without saving
parameters.
If there is no more action within 20 seconds, the controller will automatically exit modifying status without saving.
Note:
(1) parameters setting condition: System still runs under original parameters
(2) constant temperature control mode: Water temperature is controlled by F0 parameters
(3) intelligent control mode:Water temperature depends on room temperatue and F1parameters
Advanced settings
(1) Press and hold + SET for 5 seconds until „0“ is displayed.Then press to select the password which has been set before (factory setting is
8). Press SET, if the password is correct, „F0“ is shown and you‘re entering set status. (D1 fl ashes to indicate the controller is in parameters
setup status). If you choose the wrong password the panel returns to temperature display.
(2) In setup state press or to switch between functions and select with SET.After selecting an option, the original settings are displayed. Modify
them with . Press SET to save and return to previous setup menu. Press RST to save and return to temperature display.
If no button is pressed within 20 seconds, the controller will automatically exit modifying status without saving.

10
Parameter List
Order Displayed
Code Range Factory settings Note
1F0 Temperature setting
Item
F9 ~ F8
2
3
4
5
6
7
8
9
10
F1
F2
F3
F4
F5
F6
F7
F8
F9
Temperature diffence value
Cooling hysteresis
Control mode
Alarm for too highwater
temperature
Alarm for too low water
temperature
Alarm for too high room
temperature
Password
highest allowed water
temperature
lowest allowed water
temperature
-15 ~ +5
0.1~ 3.0
0 ~ 1
1~ 20
1~ 20
40 ~ 20
00 ~ 99
F0 ~ 40
1~ F9
25
-2
0.8
1
10
15
45
8
30
20
affects temperature in constant
control mode
affects temperature in intelligent
control mode
1: intelligent
0: constant
Settings Overview

11
Settings - example of use
Switch to constant temperature mode
(1) Hold down + SET for 5 seconds, until it shows “0”. Set the value with and select the password you have set (Factory default is 8).
Press SET; if the password is correct the display will show „F0“ and you will be in the settings menu. (Display D1 will blink to show parameter
mode) If the password is incorrect, you will be returned to the temperature display.
(2) In the settings menu, press to reach menu point “F3”. Press SET to apply settings.The display will read “1”(Intelligent mode).With , change the
value to “0” (constant temperature mode).
(3) Confirm your selection with SET to save your selection and return to the settings menu
Or
Use RST to save your settings and return to the home screen.
If you do not press any keys within 20 seconds, you will automatically leave settings mode without saving.
Set water temperature - in constant temperature mode
(1) The heat exchanger is running in constant temperature mode.
(2) Press SET; the display will now read “F3”. Change the value with to “F0” and con rm your selection with SET.
(3) The set temperature value will be displayed. Using , set this value to your liking.
(4) Confirm your selection with SET to save your selection and return to the settings menu.
Or
Use RST to save your settings and return to the home screen.
If you do not press any keys within 20 seconds, you will automatically leave settings mode without saving.

12
Flow Alarm
In order to guarantee the equipment will not be damaged while cooling water circulation is out of control, the chiller has a low-fl ow alarm security
feature. The fl ow alarm is connected to the normally open and normally closed relay contacts, requiring operating current less than 5 A, working voltage
less than 300V.
Wiring diagram - output ports
Flow alarm causes
Display
Condition NORMAL LED ALARM LED Buzzer OUT
H1, H2
OUT
H1, H3
pump works properly
Blocked water circulation loop
Water shortage alarm
Faulted pump
Power interruption
ON
OFF
OFF
OFF
OFF OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
no sound
sounds
sounds
sounds

13
Alarm - Fault Indication
Display
Meaning
E1E2
water temperature
too high
room temperature
too high
When alarm occurs, the error code will be displayed.
The alarm sound will be suspended by pressing any button, but the alarm code remains on display until the alarming condition is eliminated.
Error messages
E3 E4 E5
water temperature
too low
Room temperature
sensor failure Water temperature
sensor failure
Troubleshooting
Failure Fault Cause Approach
Machine turned on but not receiving power Power cord is not plugged in place
Check and ensure the power interface and the
power plug is plugged in place and in good
contact.
Fuse burnt-out
PuII out the fuse box from the power supply
interface of the chiIler, check the fuse, replace with
spare fuse, if necessary and check whether the
power supply voltage is stable. Check and ensure
the power interface and the power plug is plugged
in place and in good contact.
Flow AIarm (red LED on) -
no water fl ow despite everything being
connected properly
Water IeveI is too low
Check the water level gauge, add water
until the level is in the green area.Also check
whether water circulation tube leaks
Water circulation tubes are blocked
or tubes are deformed by bending
Check water circuIation tubes.They should not
be bent or twisted.

14
Alarm - Fault Indication
Failure Fault Cause
UItra-high temperature aIarm Blocked dust gauze, bad thermolysis
Poor ventilatIon for air outlet and inlet
Voltage is extremely low or unstable
Improper parameter settings on thermostat
Power is switched on frequently
Excessive heat load
Alarm for uItra-high room temperature The working ambient temperature is too high
for the chiller
Serious probIems with condensate water Water temperature is much lower than
ambient temperature, with high humidity
Water drains slowly from drain during water
changing Fillport is not open
Approach
Unpick and wash the dust gauze regularly.
Ensure a smooth ventilation
for air outlet and inIet.
Improve the power supply circuit
or use a voltage regulator.
Reset controlIing parameters or
restore factory settings.
Ensure there is suf cient time
for refrigeration (more than 5 minutes).
Reduce the heat load or use other
model with larger cooling capacity.
Improve the ventilation to guarantee the
machine is running under 40°C.
Increase water temperature or preserve heat
for pipeline.
Open the Fillport.

15
Technical Speci cation
Model Chiller 2000
Voltage 220V
Frequency 50 Hz
Current 2.4 ~ 3.3 A
Compressor Power 0.49 / 0.57 KW (0.66 / 0.77 HP)
Refrigeration Capacity 1.41 / 1.70 KW
Refrigerant R-134a
Refrigerant Charge 380 g
Noise level 65 db(A)
Precision ± 0.3 °C
Reducer Capillary
Protection Over current protection for compressor, fl ow alarm, over temperature alarm
Pump Power 0.03 KW
Reservoir Capacity 9 L
Inlet / Outlet G 1/4 Inner threads
max. Lift 10 m
max. Flow 10 L/min
Netto Gewicht 29 kg
Dimension 56 x 28 x 47 cm (L x W x H)

Deutsch

17
Inhaltsverzeichnis
Englische Anleitung 3
Deutsche Anleitung
Sicherheitshinweise 18
Teilebezeichnung 19
Installation 20-21
Einstellungsmöglichkeiten 22-25
Durchfl ussalarm 26
Fehlermeldungen & -behebung 27-28
Technische Spezi kationen 29
Französische Anleitung 31

18
Sicherheitshinweise
Stellen Sie sicher, dass Ihr Gerät sicher mit einer Stromquelle verbunden und der
Erdungsdraht angeschlossen ist.
Die durchschnittliche Stromstärke während des Betriebs ist zwar gering, kann aber Stromspitzen von
bis zu 10 Ampere erreichen.
Die angelegte Spannung sollte für den Wärmetauscher ausgelegt und stabil sein.
Die Standartspannung für das Gerät liegt bei 220V.
Nicht abgestimmte Frequenzen können das Gerät beschädigen!
Achten Sie darauf, ob Sie ein Gerät mit 50 Hz betreiben können.
Schalten Sie den Wärmetauscher niemals ohne Kühlfl üssigkeit an, dies kann die Pumpe
zerstören!
Das Gerät wird ohne Kühlfl üssigkeit im Tank ausgleifert. Füllen Sie also vor der Inbetriebnahme
genügend Wasser ein, sodass der Wasserstand im grünen Bereich liegt. Liegt der Wasserpegel darunter,
wird die Kühlstärke leicht abnehmen. Auch das Ablassen der Kühlfl üssigkeit ist bei laufender Pumpe
untersagt.
Stellen Sie sicher, dass die Lüfter genug Freiraum haben, um heiße Luft abzuführen und
Frischluft anzusaugen.
Lassen Sie hinter dem Gerät etwa 30cm Platz und zu den Seiten mindestens 8cm.
Reinigen Sie regelmäßig die Staubfi lter!
Je nach Arbeitsumfeld des Wärmetauschers, ist es notwendig den Filter häu g zu reinigen. Bei starker
Verschmutzung kann das Gerät sehr heiß werden und wird ich selbst abschalten.
Achten Sie auf entstehendes Kondenswasser!
Bei hoher Luftfeuchtigkeit und geringerer Wassertemperatur als Umgebungstemperatur entsteht
Kondenswasser an den Schläuchen und den zu kühlenden Bauteilen. Tritt dieser Fall ein, emp ehlt es
sich eine höhereWassertemperatur einzustellen oder die Schläuche und Bauteile künstlich zu
erwärmen.
1
2
3
4
5
6
7

19
Teilebezeichnung
Netzschalter
Vorne
Hinten
Display / Anzeige
Durchfl ussalarm
(rot)
Normaler Durchfl uss
(grün)
Lufteinlass mit
Staub lter
Einfüllöffnung
Alarmsignal Ausgang
Eingang Netzstecker
Wassereinlass
Wasserauslass
Luftauslass
Wasserstand
Anzeige
Wasserauslass

20
Installation
Oberen Einlass öffnen und Kühlfl üssigkeit einfüllen
Behalten Sie dabei den Füllstand im Auge, der Pegel sollte im grünen
Bereich liegen. Für die Kühlung von Karbon-Stahl-Anlagen, sollte der
Kühlfl üssigkeit eine entsprechende Menge Anti-Korrosion Zusatz zugefügt
werden. Bei Einsatz in sehr kalten Gebieten ist es ratsam, nicht
korrodierendes Frostschutzmittel hinzuzufügen.
Kühlkreislauf mit demWasserein- und auslass des
Wärmetauschers verbinden
ZumVerschlauchen benötigen Sie 2 G1/4 Schlauchanschlüsse.
Mit Stromquelle verbinden und Gerät einschalten
Starten Sie das Gerät nicht ohne Kühlfl üssigkeit im Tank!
1. Bei der ersten Inbetriebnahme kann es vorkommen, dass sich vermehrt
Luftblasen bilden und der Durchfl ussalarm ausgelöst wird. Dieser löst sich
normalerweise nach wenigen Minuten wieder auf.
2. Prüfen Sie Ihren Kreislauf sofort auf Dichtigkeit.
3. Ist die Wassertemperatur unter den werkseitigen Einstellungsparame-
tern, ist es normal, dass Lüfter oder andere Komponenten nicht sofort
anlaufen. Die interne Temperaturkontrolle passt die Laufl eistung der Kom-
ponenten automatisch an.
4.Abhängig von den Umgebungszuständen, benötigen die Komponenten
unterschiedlich lang zum anlaufen. Häu ges An- und Ausschlaten, in kurzen
Abständen, kann zu Schäden an den Bauteilen führen.
1
2
3
Table of contents
Languages:
Popular Chiller manuals by other brands

Daikin
Daikin WCT Series operating & maintenance manual

Dunham-Bush
Dunham-Bush HRSC - D Operating & maintenance instructions

Schreiber Engineering
Schreiber Engineering 30AC Installation operation & maintenance

VDH
VDH MC 785 CHILLER-2 user manual

Carrier
Carrier AquaEdge 19XRV series Start-up and service instructions

Viessmann
Viessmann Vitoclima 200-C Service instructions

AERMEC
AERMEC AN R407C Technical and Installation Booklet

Carrier
Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR installation instructions

MCED systems
MCED systems BEF-02 Service manual

SMC Networks
SMC Networks HRSH090-A Operation manual

York
York MILLENNIUM YK Wiring diagram

Trane
Trane RTAA installation instructions