CAUTION!
Do not exceed the operating pressures
specied on the rating plate. If necessary,
install a pressure reducer.
NOTE
Close off any connections not required with
appropriate plugs.
For position of the connections, please refer to
the dimensioned drawing for the respective model.
CAUTION!
Always integrate the tank in the system
according to the connection instructions.
Connection instructions from page 20.
Use the safety valve according to the respective current
standards, guidelines and directives and according to the
maximum allowae operating pressures of the storage
tank and components.
The safety discharge of the safety valve must be dischar-
ged into the drain via a funnel-shaped odour trap accor-
ding to the respective current standards, guidelines and
directives!
The discharge pipe connected to the safety valve must
be installed with continuous downward gradient in a
frost-free environment.
Water can drip from the safety valve
NOTE
The function of the pressure relief device must
be checked at regular intervals.
INSTALLATION OF THE SENSOR FOR THE HEATING AND
HEAT PUMP REGULATOR
Depending on the unit model, you must install the sensor
included in the scope of supply for the heating and
heat pump controller on site in of the sensor pockets
provided for this purpose. (In some models this sensor is
installed in the factory).
For item, see dimensioned drawing for
respective model.
Sensor connection:
see heat pump operating manual.
Domestic hot water temperature setting: s e e
controller operating manual
NOTE
In case of installation of the solar circuit with si-
multaneously installed electric heating element the
maximum storage tank temperature must be set
so that the safety temperature limiter (overheat
cut-off device) does not trip. To this end, follow
the separate operating instructions of the heating
element and solar controller.
Commissioning
Check whether the water supply is open and the
tank is full…
Check the safety valve is working properly (and if
applicable the pressure reducer)
Test the safety valve (and if applicable the pressure
reducer) for full functionality.
Storage tanks enamelled to DIN 4753 are suitable for
normal drinking water
Insulation of the connections
and the storage tank
NOTE
Insulate in accordance with applicable local
standards and guidelines/directives.
Check all hydraulic connections for leaks. Perform
leak test…
Insulate all connections and pipes.
NOTE
The function of the pressure relief device must
be checked at regular intervals.
Draining
The storage tank is drained via the drain valve (see page
18 - 19). Shut-off valves must remain closed during drain-
ing. The connection at the hot water outlet should be
open to the atmosphere.