
17
Propane Gas Piping Charts
Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or Nominal Pipe Size
Tubing Tubing Size, O.D. Type L Schedule 40
Length, 3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4"
Feet
10 730 1,700 3,200 5,300 8,300 3,200 7,500
20 500 1,100 2,200 3,700 5,800 2,200 4,200
30 400 920 2,000 2,900 4,700 1,800 4,000
40 370 850 1,700 2,700 4,100 1,600 3,700
50 330 770 1,500 2,400 3,700 1,500 3,400
60 300 700 1,300 2,200 3,300 1,300 3,100
80 260 610 1,200 1,900 2,900 1,200 2,600
100 220 540 1,000 1,700 2,600 1,000 2,300
125 200 490 900 1,400 2,300 900 2,100
150 190 430 830 1,300 2,100 830 1,900
175 170 400 780 1,200 1,900 770 1,700
200 160 380 730 1,100 1,800 720 1,500
To convertto capacities at 15 psig settings - multiply by 1.130
To convertto capacities at 5 psig settings - multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or Nominal Pipe Size
Tubing Tubing Size, O.D. Type L Schedule 40
Length, 3/8" 1/2" 5/8" 3/4" 7/8" 1-1/8" 1/2" 3/4" 1" 1-1/4" 1-1/2"
Feet
10 39 92 199 329 501 935 275 567 1,071 2,205 3,307
20 26 62 131 216 346 630 189 393 732 1,496 2,299
30 21 50 107 181 277 500 152 315 590 1,212 1,858
40 19 41 90 145 233 427 129 267 504 1,039 1,559
50 18 37 79 131 198 376 114 237 448 913 1,417
60 16 35 72 121 187 340 103 217 409 834 1,275
80 13 29 62 104 155 289 89 185 346 724 1,066
100 11 26 55 90 138 255 78 162 307 630 976
125 10 24 48 81 122 224 69 146 275 567 866
150 9 21 43 72 109 202 63 132 252 511 787
200 8 19 39 66 100 187 54 112 209 439 665
250 8 17 36 60 93 172 48 100 185 390 590
*Data in accordance with NFPA pamphlet NO. 54
WARNING
To prevent death, serious personal in-
jury or property damage due to fire or
explosion caused by a propane gas leak,
install a gas detecting warning device.
If the propane gas furnace is installed in
a basement, an excavated area or a con-
finedspace, awarning deviceis required
due to:
• Propane gas is heavier than air and
any leaking gas can settle in any low
areas or confined spaces.
• Propane gas odorant may fade, mak-
ing the gas undetectable except with
a warning device.
If the presence of gas is suspected, fol-
low the instructions on Page 2 of this
manual.
VIl. ElectricalWiring
WARNING
To prevent death or personal injury due
to electric shock, disconnect electrical
powerbeforechanginganyelectricalwir-
ing.
CAUTION
When servicing controls, label all wires
before disconnecting. Wiring errors can
cause improper and dangerous oper-
ation. After servicing is completed, al-
ways verify proper operation.
The unit wiring harness is an integral part of the furnace.
Fieldalterationtocomplywithelectricalcodesshouldnot
be required.
Power supply to the furnace must be NEC Class 1, and
mustcomplywith all applicablecodes.The furnacemust
be electrically grounded in accordance with the local
codes or, in their absence, with the latest edition of the
National Electrical Code, ANSI NFPA No. 70 and/or the
CSAC22.1Electrical Code. Afuseddisconnectmust be
providedandsizedinaccordancewiththeunitmaximum
overcurrent protection.
Figure 20
Typical Field Wiring
(24 VAC Control Circuit)
A 40 V.A. transformer and an integrated electronic con-
trol are built into the furnace to allow use with most
cooling equipment.
CAUTION
To avoid the risk of electrical shock,
wiring to the unit must be properly polar-
ized and grounded.
To provide more reliable sensing of flame, the
ground
wire
must run to the electrical panel.
Line voltage wiring
must enter into the junction box
provided with the furnace.