Servicing
7
TheHRV1500SFDandHRV1500SFDEaredesignedtobe
serviceable from either side. If access to the unit will only
be available from one side, the unit must be set up accord-
ingly. The unit is factory shipped to be serviced from the
front. (Blowers on the right when facing the unit. If servic-
ing is only accessible from the other side follow the proce-
dure below.
1. The Ebox must be removed from the front brackets and
mounted on the rear brackets provided on the other side
of the unit.
2. The filter divider panels must be removed and placed in
the unit so they can be removed from the opposite side.
3. The lower blower divider panel must be removed and
mounted in the unit from the other side.
Each panel on the unit can be removed by removing the
two bolts on the bottom.
Servicing is easiest by removing the side panels on both
sides to gain access to either side of the unit.
Servicing Filters
1.Remove filter servicepanel(oneorboth sides).
2. Remove first set of filters.
3.Remove filter dividerpanels(ifonlyaccessing from
oneside).
4.Removefiltersfrom behind filterdividerpanel.
5. Replace all filters. Ensure that filter divider panels are
reinserted into unit.
Servicing Cores
1.Remove core servicepanel(oneor both sides).
2. Slide cores out (regular core maintenance).
3. When placing the cores back into the unit, ensure that
there are no gaps between any of the cores.
Ensure all H channels are flush with the ends of the
coresbefore the coreservicepanelis re-attached.
Servicing Blowers
1. Remove blower service panel (one or both sides)
2.Unscrew the 2boltsthat connecttheblowerto theblower
rails of the unit.
3. Remove all wiring to the motors.
4. Slide blower back and lift to remove blower assembly.
5. If access to the unit is not available from both sides,
remove the blower divider panel by removing the 8 bolts
holding this panel in place.
6. Repeat steps 2-4 with the other blower.