WARNING
!
CARBON MONOXIDE, FIRE, AND/OR SMOKE
HAZARD
CARBON MONOXIDE, FIRE, OR SMOKE CAN
CAUSE SERIOUS BODILY INJURY, DEATH, AND/
OR PROPERTY DAMAGE.
FAILURE TO FOLLOW THIS WARNING COULD
RESULT IN CARBON MONOXIDE POISONING
OR DEATH.
1. Avoid an excessive number of bends.
2. Horizontal runs should pitch upward at least 1/4"
per foot. See Table 6 and Figure 14.
3. Horizontal runs should be as short as possible.
4. All vent pipe or connectors should be securely
supported and must be inserted into, but not
beyond the inside wall at the chimney vent.
5. When vent connections must pass through walls
or partitions of combustible material, a thimble
must be used and installed according to local
codes.
6. Vent pipe through the roof should be extended to
a height determined by National Fuel Gas Code
or local codes. It should be capped properly to
prevent rain water from entering the vent. Roof
exit should be waterproofed.
7. Use type “B” double wall vent when vent pipe is
routed through cool spaces (below 60° F.).
8. Apply other good venting practices as stated in
the venting section of the National Fuel Gas
Code ANSI Z223.1 “latest edition”.
9. Vent connectors serving appliance vented
by natural draft or non-positive pressure
shall not be connected into any portion of a
mechanized draft system operating under
positive pressure.
10. Horizontal pipe runs must be supported by han-
gers, straps or other suitable material in inter-
vals at a minimum of every 3 feet of pipe.
11. A boiler shall not be connected to a chimney
or flue serving a separate appliance desi-
gned to burn solid fuel.
12. The flow area of the largest section of vertical
vent or chimney shall not exceed 7 times the
smallest listed appliance categorized vent area,
flue collar area, or draft hood outlet area unless
designed in accordance with approved enginee-
ring methods.
Maximum Vent or Tile
Lined Chimney Flow Area
*Drafthood outlet diameter, flue collar diameter, or
listed appliance categorized vent diameter. Maximum
vent or tile lined chimney flow area values are for chimnies
that are not exposed to the outdoor, below the roof line. If
exposed below the roof line, then local gas utility and/or
authority having jurisdiction must be consulted.
π(D*)2
4
= X 7
TABLE 6
Gas Vent Termination
Roof Pitch Minimum Height
Flat to 7/12 1.0 Feet*
Over 7/12 to 8/12 1.5 Feet
Over 8/12 to 9/12 2.0 Feet
Over 9/12 to 10/12 2.5 Feet
Over 10/12 to 11/12 3.25 Feet
Over 11/12 to 12/12 4.0 Feet
Over 12/12 to 14/12 5.0 Feet
Over 14/12 to 16/12 6.0 Feet
Over 16/12 to 18/12 7.0 Feet
Over 18/12 to 20/12 7.5 Feet
Over 20/12 to 22/12 8.0 Feet
* This requirement covers most instal-
lations
A variety of potential sources of carbon monoxide can
be found in a building or dwelling such as gas-fired
clothes dryers, gas cooking stoves, water heaters,
boilers and fireplaces. The U.S. Consumer Product
Safety Commission recommends that users of gas-
burning appliances install carbon monoxide detectors
as well as fire and smoke detectors per the manufac-
turer’s installation instructions to help alert dwelling
occupants of the presence of fire, smoke or unsafe
levels of carbon monoxide. These devices should be
listed by Underwriters Laboratories, Inc. Standards
for Single and Multiple Station CarbonMonoxide
Alarms, UL 2034 or CSA International Standard,
Residential Carbon Monoxide Alarming Devices, CSA
6.19.
Figure 14
NOTE: The manufacturer of your boiler does NOT
test any detectors and makes no representations
regarding any brand or type of detector.