
13
Check the loop is not open circuit, short circuit, or connected to earth
(see instability or high frequency noise section of Troubleshooting)
The unit could be overheating (loop current is not delivered if the
internal heatsink reaches a predetermined level). To establish if this is
the case turn the unit off and allow to cool down before turning on.
Ensure that the unit is installed in a location with sufficient ventilation.
Low magnetic field strength
Due to insufficient current or excessive metal loss.
May require a special loop design to achieve acceptable performance,
contact Ampetronic for advice.
Instability or high frequency noise
1. It is possible for the loop cable to be grounded under fault conditions,
resulting in instability which may sound like high frequency noise,
buzz or whistling.
This fault is easy to determine. Simply disconnect the loop cable
from the amplifier and test with a resistance meter between either of
the loop wires and a good earth point such as a metal radiator. There
should be an infinitely high reading i.e. no connection at all. Any
reading indicates a failure of the loop cable insulation and you will
need to either repair or replace the loop cable.
2. Instability can be caused by using poor quality signal cables, long
unbalanced (2-wire) signal runs to the inputs, or by running input
cables in close proximity with the loop wire over an appreciable
distance. Loop amplifiers are capable of delivering high currents at
audio frequencies. If the loop cable is run close to sensitive signal
cables it may be possible to induce a signal back into the input of the
amplifier causing feedback. Cable runs and loop wires should be
kept well apart from each other. To avoid interference maintain a
separation of at least 300mm.
3. Instability can cause the amplifier to run hot and may result in an
overheat condition (see CURRENT LED not illuminating section).
Interference
1. Background magnetic field signals or interference may be present in
any location and may not be anything to do with the loop system.
Monitor this with a loop receiver (such as an ILR3, ILR3+ or Field
strength meter). If the interference is still present with the loop
system switched off, then you need to locate and eliminate the
source of the interference before switching the loop system back on
2. Magnetic fields can induce currents into any low impedance