Anly EP4-1 User manual

EP4-1
DIGITAL VOLTAGE
PROTECTIVE RELAY
User's Manual
SAFETY PRECAUTION
This manual uses the following symbols to ensure safe operation of this product.
WARNING
CAUTION
Warnings are indicated when mishandling this product might result in death or serious injury
Cautions are indicated when mishandling this product might result in minor injury to the user,
to user.
or only physical damage to the timer.
‧Note this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has
been correctly wired before turning the power ON.
‧Before wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause
electric shock.
‧Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
‧Do not disassemble the product. Doing so might cause electric shock or faulty operation.
‧Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage,
shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.
‧Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire.
WARNING
CAUTION
ANLY ELECTRONICS CO., LTD.
http://www.anly.com.tw
When using this product in applications
that require particular safety or when
using this product in important facilities,
please pay attention to the safety of the
overall system and equipment. Install fail-
safe mechanisms, perform redundancy
checks and periodic inspections and
adopt other appropriate safety measures
when it is necessary. This product is rated
at Class Ⅱ .
RESTRICTIONS ON USE
V
S
L1
L2
L3
L1
L2
L3
V
S
L1
L2
L3
V
S
L1
L2
L3
V
S
NO INPUT
UNBALANCE VOLTAGE
REVERSE PHASE
PHASE LOSS
UNDER VOLTAGE
OVER VOLTAGE
V
S
L1
L2
L3
V
S
L1
L2
L3
V
S
L1
L2
L3
V
S
L1
L2
L3
V
S
L1
L2
L3
V
S
L1
L2
L3
V
S
V
S
V
S
L1
L2
L3
L1
L2
L3
L1
L2
L3
1. 3-phase voltages display 2. Fault indications
Phase-to-phase voltages
are displayed in sequence.
Set the desired value for over voltage.
The display will show existing 3-phase
voltages after 10 seconds.
Set the desired value for under voltage.
The display will show existing 3-phase
voltages after 10 seconds.
Set the tripping delay for under voltage.
The display will show existing 3-phase
voltages after 10 seconds.
Set the tripping delay for over voltage.
The display will show existing 3-phase
voltages after 10 seconds.
3. Over voltage tripping delay setting1. Over voltage setting
4. Under voltage tripping delay setting2. Under voltage setting
Operating voltage
Life
Mechanical : 5,000,000 times / Electrical : 100,000 times
voltage range
Allowable operating
85 ~ 110% of rated operating voltage
Rated frequency
50 / 60 Hz
Display error ±1%(at 550V)
Contact rating 250VAC 5A (Resistive load)
Power consumption Approx. 3.3VA
Ambient temperature -10 ~ +50 ºC (without condensation & freezing)
Ambient humidity MAX 85% RH (without condensation)
Altitude MAX 2000m
Weight Approx. 130g
AC/DC : 100 - 240V, DC : 8 - 60V(for EP4-11060- only)
REV. ON
OFF
ON
OFF
ON
OFF
ON
OFF
UNBAL.
AUTO
5S/1S
Auto reset
Auto reset delay 5 sec
Auto reset delay 1 sec
Manual reset
Phase reversal protection ON
Unbalance protection ON
Unbalance protection OFF
Phase reversal protection OFF
V
S
L1
L2
L3
L1
L2
L3
V
S
L1
L2
L3
L1
L2
L3
V
S
V
S
OVER VOLTAGE
SETTING VALUE
UNDER VOLTAGE
SETTING VALUE
OVER VOLTAGE DELAY
UNDER VOLTAGE DELAY
5. DIP switches setting 6. Setting display
Pressing "TEST" will cycle-through all
settings in sequence.
3-phase voltages are displayed after
10-second of idle.
Unbal. Auto
Off
5S
1S
Rev.
Over
Volt
Under
Over
Volt
Under
Under
Over
Over
Time
Time
Under
EP4-1
L2
L2
L3
L3
L1
L1
S
V
Test
OverUnbal. Auto
O
ff
5S
1S
Rev.
Voltage Time
Under Over Under
Reset
Voltage indicatior
Over voltage
tripping delay
Time indicatior
in second
Under voltage
tripping delay
Function settings
Manual reset
Display
Under voltage setting
Phase sequence
Setting values display
Over voltage setting
NAMES AND FUNCTIONS OF FACEPLATESPECIFICATIONS
SETTING PROCEDURE DISPLAY
DIMENSIONS
90.6
45
45
68.1
90.6
94.6
56.6
18
39.5 7

DC Voltage(8-60V) DC Voltage 1-Phase 2-Wire 3-Phase 3-Wire 3-Phase 4-Wire
A1 (L/+)
L1(+)L3(-)
A2(N/-)
15
16 18
25
26 28
2C
1C
Under Over
1C Inst.
A1 (L/+)
L1 L3
A2(N/-)
15
16 18
25
26 28
2C
1C
Under Over
1C Inst.
A1 (L/+)
L1 L2L3
A2(N/-)
15
16 18
25
26 28
2C
1C
Under Over
1C Inst.
A1 (L/+)
L1 L2L3
A2(N/-)
N
15
16 18
25
26 28
2C
1C
Under Over
1C Inst.
A1
(L/+)
A2
(N/-)
15
16 18
25
26 28
2C
1C
Under Over
1C Inst.
Printed in Taiwan
M-EP41-T-B
CONNECTION
TYPE SELECTION
TIMING CHART
8~60V
160~300V
N/A
EP4-12300-
Single Phase
EP4-11060-
EP4-11300-
DC Type
N/A
EP4-14300-
3 Phase 4 Wire
N/A
50~200V
N/AEP4-11200- N/AN/A
70~150V EP4-12150-EP4-11150- N/AEP4-13150-
EP4-13300-
EP4-12----EP4-11---- EP4-14----EP4-13----
270~550V EP4-12550-N/A EP4-14550-EP4-13550-
3 Phase 3 Wire
Voltage type
EP4-1----1
1C No-Fault
EP4-1----2
1C Fault
EP4-1----3
2C Over & Under Fault
EP4-1----4
2C Inst. & No-Fault
EP4-1----5 EP4-1----6
2C No-Fault
Output contact 2C Over & Under No-Fault
Under Voltage
Over Voltage
Line Normal
Under Voltage
Phase Loss
Over Voltage
Over TimeReset TimeReset Time Reset Time
Reset Time
Reset Time Reverse Time
Reset Time
Unbalance Time
Under Time Phase-Loss Time
L1L2L3 L2L1 L1L2L3 >±5%
L3
A1-A2
N.C. (15-16, 25-26)
N.O. (25-28)
N.C. (25-26)
N.O. (25-28)
N.C. (25-26)
(25-28)
(25-26)
No-Fault
N.O. (15-18)
N.C. (15-16)
Under
Fault
N.O. (15-18)
N.C. (15-16)
N.O. (15-18)
N.C. (15-16)
Under
No-Fault
N.O.
N.C.
Over
No-Fault
Over
Fault
Inst.
Fault
N.O. (15-18, 25-28)
Voltage
detect range