Argoclima AER518DC Manual

TECHNICAL DATA & SERVICE MANUAL
Outdoor Unit Indoor Unit
AER518DC AWR509CL(x2)
MULTI-SPLIT SYSTEM AIR CONDITIONER
Indoor Unit Outdoor Unit
0.8180.138.0 03/2001
AFR509CL(x2)
AWR509CL(x2)
AFR509CL(x2)
AER518DC
®

IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person, it is
an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
●Carefully read this instruction booklet before beginning.
●Follow each installation or repair step exactly as
shown.
●Observe all local, state, and national electrical codes.
●Pay close attention to all warning and caution notices
given in this manual. This symbol refers to a hazard
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or
your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and
tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections
and inadequate grounding can cause accidental
injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your
knees when lifting to reduce strain on your back. Sharp
edges or thin aluminum fins on the air conditioner can cut
your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide
a solid, level foundation for the outdoor unit. This
prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leak-
free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have been
left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously
toxic gas.
• Confirm upon completing installation that no
refrigerant gas is leaking. If escaped gas comes in
contact with a stove, gas water heater, electric room
heater or other heat source, it can produce
dangerously toxic gas.
WARNING
WARNING
CAUTION
CAUTION
ii

Table of Contents
Page
Unit combination iiii
1OPERATING RANGE 1
2SPECIFICATIONS
2-1Unit Specification 2
2-2Major Component Specifications 3
2-3Other Component Specifications 5
3DIMENSIONAL DATA 8
4COOLING CAPACITY 8
5AIR THROW DISTANCE CHART 10
6REFRIGERANT FLOW DIAGRAM 12
7ELECTRICAL DATA
7-1Electrical Characteristic 137-2Electric Wiring Diagrams 14
7-3Performance Charts 17
8INSTALLATION INSTRUCTION
8-1Installation Site Selection 18
8-2Remote Control Unit Installation Position 20
8-3Recommended Wire Length and Diameter 21
9FUNCTION
9-1Room Temperature Control 22
9-2Dry Operation 23
9-3Freeze prevention 24
10 REFRIGERANT R407C:SPECIAL PRECAUTION WHEN SERVICING UNIT
10-1Characteristics of new refrigerant R407c 25
10-2Checklist before servicing 25
10-3Tools specifically for R407c 26
10-4For tubing installation procedures 26
10-5In case of compressor malfunction 27
10-6In case refrigerant is leaking 29
10-7Charging additional refrigerant 31
10-8Retro-fitting existing systems 31
11 TROUBLESHOOTING
11-1Check before and after troubleshooting 31
11-2Air Conditioner Does not work 33
11-3Some Parts of Air Conditioner does not operate 38
11-4Air Conditioner operates, but abnormalities are observed 40
11-5If a sensor is defective 41
12 ARRANGEMENT OF ELECTRICAL COMPONENTS 42

13 CHECKING ELECTRICAL COMPONENTS
13-1Measurement of insulation Resistance 4313-2Checking Continuity of Fuse on PCB Ass’y44
13-3Checking Motor Capacitor 44
iv

v
■Unit Combination
Combine indoor and outdoor units only as listed below.
Indoor Unit
Outdoor Unit A
B
Refer toOutdoor Unit Symbol of
Indoor Unit
A
Indoor Unit
Fig.1
AER518DC
AWR509CL
Fig.1
AFR509CL
B
AFR509CL
AWR509CL

1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
1

DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
No. of indoor units. 1-unit 2-units
Power Source 220 – 240 V ~ 50 Hz
Cooling
Capacity kW 2.85 5.30
BTU/h 9,700 18,100
Air circulation (High) m3/h 470 470×2
Moisture removal (High) Liters/h 1.0 1.0×2
Voltage rating V230
Available voltage range V 198 to 264
Running amperes A4.6 9.5
Power input W 1020 2050
Power factor %96 93
C.O.P. W/W 3.0 2.7
Compressor locked rotor amperes A24 48
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours, Daily program, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Auto
Air filter Washable, Anti–Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment gR407c / 2,000 (1,000×2)
Refrigerant control Capillary tube
Operation sound Indoor – Hi / Me / Lo dB-A 38 / 33 / 31
Outdoor – Hi dB-A 53
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube Narrow tube mm (in.) 6.35 (1/4)
diameter Wide tube mm (in.) 9.52 (3/8)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 270 630
Width mm 805 830
Depth mm 177 305
Package dimensions Height mm 243 713
Width mm 855 994
Depth mm 332 413
Weight Net kg 8.0 59.0
Shipping kg 10.0 64.0
Shipping volume m30.07 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit AWR509CL
Outdoor Unit AER518DC
2
2. SPECIFICATIONS
2-1. Unit Specifications

DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
No. of indoor units. 1-unit 2-units
Power Source 220 – 240 V ~ 50 Hz
Cooling
Capacity kW 2.85 5.30
BTU/h 9,700 18,100
Air circulation (High) m3/h 380 380 x 2
Moisture removal (High) Liters/h 1.0 1.0×2
Voltage rating V230
Available voltage range V 198 to 264
Running amperes A4.6 9.5
Power input W 1020 2050
Power factor %96 93
C.O.P. W/W 3.0 2.7
Compressor locked rotor amperes A24 48
Controls / Temperature control Microprocessor / I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours, Daily program, 1-hour OFF
Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi)
Airflow direction (Indoor) Horizontal Manual
Vertical Manual
Air filter Washable, Anti–Mold
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment gR407c / 2,000 (1,000×2)
Refrigerant control Capillary tube
Operation sound Indoor – Hi / Me / Lo dB-A 37 / 32 / 31
Outdoor – Hi dB-A 53
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m 7.5
Refrigerant tube Narrow tube mm (in.) 6.35 (1/4)
diameter Wide tube mm (in.) 9.52 (3/8)
Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor Unit Outdoor Unit
Unit dimensions Height mm 700 630
Width mm 560 830
Depth mm 200 305
Package dimensions Height mm 770 713
Width mm 620 994
Depth mm 265 413
Weight Net kg 18 59.0
Shipping kg 20 64.0
Shipping volume m3
0.07 0.29
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit AFR509CL
Outdoor Unit AER518DC
3

2-2. Major Component Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW–K8E(A), POW–K8E(B)
Controls Microprocessor
Control circuit fuse 250 V 3.15 A
Remote Control Unit RCS–8PS3E
Type Cross–flow
Q'ty ... Dia. and length mm 1 ... ø95 / L617
Fan motor model ... Q'ty KFV4Q–11H5P–S ... 1
No. of poles ... rpm (230 V, High) 4 ... 1,190
Nominal output W 10
Coil resistance (Ambient temp. 20°C) ΩBRN – WHT : 561.8
VLT – WHT : 197.4
VLT – ORG : 63.4
YEL – ORG : 155.7
YEL – PNK : 115.9
Safety Type Internal fuse
devices Operating temp. Open °C 145 ± 2
Close —
Run capacitor µF 0.8
VAC 440
Type Stepping motor
Model MP24GA1
Rating DC 12 V
Coil resistance (Ambient temp. 25°C) ΩWHT – BLU (respectively 4 wires) : 380 ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.4
Face area m20.130
Heat
Exch. Coil Flap Motor Fan & Fan Motor
Controller
PCB
4
Indoor Unit AWR509CL

5
Indoor Unit AFR509CL
Controller PCB
Part No. POW-K185GS5-N
Controls Microprocessor
Control circuit fuse 250 V 3 A
Remote Control Unit RCS-5PS3E
Fan & Fan Motor
Type Cross-flow
Q'ty ... Dia. and length mm1 ... ø100 / L410
Fan motor model ... Q'ty KR35406M01527
No. of poles ... rpm (230 V, High) 4 ... 1,140
Nominal output W27
Coil resistance (Ambient temp. 20°C)ΩGRY-WHT : 545 - 630
WHT-VLT : 92 - 105
VLT-YEL : 62 - 71
BRN-YEL : 78 - 90
——
Safety devices Type Internal protector
Operating temp. Open °C150±10
Close Automatic reclosing
Run capacitor µF 0.6
VAC 400
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm1.4
Face area
m2
0.185
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Type Rotary (Hermetic)
Compressor model ... Q'ty C–RN90H5B ... 2 / 80228345 ... 2
Nominal output W 900
Compressor oil ... Amount cc DAPHNE-FV68S ... 470×2
Coil resistance (Ambient temp. 25°C) ΩC – R : 3.07
C – S :6.69
Type External protector (OLR 1, 3) External protector (OLR 2, 4)
Safety Overload relay ... Q'ty MRA38066-3229 ... 2 CS–7C115 ... 2
devices Operating temp. Open °C 145 ± 5 115 ± 3
Close °C 69 ± 11 95 ± 5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 18A —
Run capacitor ... Q'ty µF 25 ... 2
VAC 450 ... 2
Type Propeller
Q'ty ... Dia. mm 1 ... ø400
Fan motor model ... Q'ty SMEN 19TFB6047–S ... 1
No. of poles ... rpm (230 V) 6 ... 910
Nominal output W 50
Coil resistance (Ambient temp. 20°C) ΩWHT – BRN : 83.4
WHT – PNK : 218.7
Safety Type Internal protector
devices Operating temp. Open °C 130 ± 5
Close Automatic reclosing
Run capacitor µF 2.0
VAC 400
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.8
Face area m20.473
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil Compressor
Fan & Fan Motor
Outdoor Unit AER518DC
6

7
2-3. Other Component Specifications
Indoor Unit AWR509CL
Transformer (TR) ATR-J105
Rating Primary AC 230V, 50/60Hz
Secondary 19V, 0.526A
Capacity 10VA
Coil resistance Ω(at 21°C) Primary (WHT – WHT): 205 ± 10%
Secondary (BRN – BRN): 2.0 ± 10%
Thermal cut-off temp. 150°C
Thermistor (Coil sensor) DTN-TKS131B
Resistance kΩ0°C 15.0 ± 2%
Thermistor (Room sensor) DTN-TKS134B
Resistance kΩ25°C 5.0 ± 3%
Outdoor Unit AER518DC
Power Relay (RA, RB) G7L-2A-TUB
Coil rating AC 200–240V, 50
Coil resistance Ω(at 23°C) 21 ± 15%
Contact ratingAC 240V, 14A
Transformer (TR) ATR-H85
Rating Primary AC 235V, 50Hz
Secondary 11V, 0.727A
Capacity 8VA
Coil resistance Ω(at 21°C) Primary (WHT – WHT): 214 ± 10%
Secondary (BRN – BRN): 1.58 ± 10%
Thermal cut-off temp. 145°C, 2A, 250V
Thermistor (Coil sensor TH1) DHPBC-41ES-14N
Resistance kΩ–20°C40.1 ±5%
–10°C24.4 ±5%
0°C15.3 ±5%
-10°C9.9 ±5%
Thermistor (Room sensor TH2) DHKTEC-35-S6N
Resistance kΩ-20°C10 ±5%
-10°7.9 ±5%
-20°C6.3 ±5%
-10°C5.0 ±5%
Indoor Unit AFR509CL

8
3. DIMENSIONAL DATA
Indoor Unit AWR509CL
58.599.5
805 177
41.0
41.0 270
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8")
Center of tubing
hole (2 places)
Drain hose ø18
Remote control unit
18.5
61
172.5
Unit : mm

9
Outdoor Unit AER518DC
5858
95 58
337
307
630
19
Narrow tube service valve
ø6.35(1/4")
1
Wide tube service valve
ø9.52(3/8")
2
305
830
4 – ø12 holes
Air discharge
Air intake
538 146
2
Magnified illustration
1
To Indoor Unit B
To Indoor Unit A
Unit : mm

INDOOR UNIT: AWR509CL @ AFR509CL
230V 50 Hz
RATING CAPACITY 2.85 kW
AIR FLOW RATE 470 m³/h @ 380 m³/h
EVAPORATOR CONDENSER
ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 2.70 2.62 2.50 2.34 2.16
CM 0.84 0.90 0.96 1.06 1.15
21 SHC 1.85 1.82 1.75 1.68 1.59
23 SHC 2.10 2.06 2.00 1.92 1.83
15 25 SHC 2.34 2.29 2.23 2.16 2.07
27 SHC 2.59 2.53 2.47 2.34 2.16
29 SHC 2.70 2.62 2.50 2.34 2.16
31 SHC 2.70 2.62 2.50 2.34 2.16
TC 2.92 2.81 2.68 2.52 2.32
CM 0.86 0.92 0.99 1.09 1.18
21 SHC 1.62 1.57 1.51 1.44 1.34
23 SHC 1.86 1.81 1.75 1.67 1.59
17 25 SHC 2.11 2.05 1.99 1.91 1.82
27 SHC 2.35 2.29 2.22 2.15 2.06
29 SHC 2.60 2.53 2.47 2.39 2.30
31 SHC 2.84 2.76 2.68 2.52 2.32
TC 3.10 2.99 2.85 2.68 2.47
CM 0.90 0.95 1.02 1.12 1.21
21 SHC 1.36 1.31 1.25 1.18 1.09
23 SHC 1.60 1.56 1.49 1.42 1.33
19 25 SHC 1.83 1.79 1.73 1.66 1.57
27 SHC 2.06 2.03 1.97 1.90 1.81
29 SHC 2.29 2.27 2.21 2.14 2.04
31 SHC 2.53 2.51 2.45 2.37 2.29
TC 3.28 3.17 3.02 2.84 2.61
CM 0.92 0.98 1.05 1.15 1.25
23 SHC 1.34 1.29 1.23 1.16 1.07
21 25 SHC 1.57 1.53 1.47 1.40 1.31
27 SHC 1.81 1.77 1.71 1.64 1.55
29 SHC 2.04 2.01 1.95 1.88 1.79
31 SHC 2.28 2.25 2.19 2.12 2.03
TC 3.51 3.36 3.17 2.97 2.76
CM 0.94 1.00 1.08 1.18 1.28
23 25 SHC 1.32 1.26 1.19 1.12 1.04
27 SHC 1.54 1.49 1.43 1.35 1.28
29 SHC 1.77 1.73 1.67 1.59 1.52
31 SHC 2.02 1.98 1.90 1.83 1.76
TC: TOTAL COOLING CAPACITY kW
SHC: SENSIBLE HEAT CAPACITY kW
CM: COMPRESSOR INPUT kW
RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B.
INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
10
4.COOLING CAPACITY

5. AIR THROW DISTANCE CHART
11
0123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle 0°
30°
Room air temp. : 27°C
Fan speed : High
Indoor Unit AWR509CL

6. REFRIGERANT FLOW DIAGRAM
12
Indoor Unit AWR509CL (x2) AFR509CL (x2)
Outdoor Unit AER518DC
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
IMPORTANT
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
CAUTION
Outdoor Unit
Wide tube
O.D.
ø9.52mm
(3/8 ")
Narrow tube
O.D.
ø6.35 mm
(1/4")
Condenser
Wide tube
service
valve
Compressor A
Accumulator
Compressor B
B
A
A
Narrow tube
service
valve
Capillary tube
B
Accumulator
Evaporator
Indoor Unit A
Evaporator
Indoor Unit B

7. ELECTRICAL DATA
7-1. Electrical Characteristics
The values in the table below indicate the sum of indoor and
outdoor units which are in running condition.
13
NOTE
Indoor Unit AWR509CL AFR509CL
Outdoor Unit AER518DC
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
230V Single phase 50 Hz
Number of indoor unit 1 - Unit
(Either A or B) 2 - Units
(Both A and B)
Rating Conditions Running amp. A 4.6 9.5
Power input kW 1.02 2.05
Full Load Conditions Running amp. A 5.4 10.8
Power input kW 1.15 2.34

7-2 Electric Wiring Diagrams
Indoor Unit AWR509CL
WARNING
To avoid electrical shock hazard, be
sure to disconnect power before
checking, servicing and/or cleaning
any electrical parts
14

Indoor Unit AFR509CL
WARNING
To avoid electrical shock hazard, be
sure to disconnect power before
checking, servicing and/or cleaning
any electrical parts
15
This manual suits for next models
2
Table of contents
Other Argoclima Air Conditioner manuals

Argoclima
Argoclima Euro-Line AD52AL Manual

Argoclima
Argoclima AS52AL Manual

Argoclima
Argoclima Euro-Line AER518DH Manual

Argoclima
Argoclima Euro-Line AS28AL Manual

Argoclima
Argoclima AW22AL Manual

Argoclima
Argoclima oscar junior Manual

Argoclima
Argoclima AER522QC Manual

Argoclima
Argoclima AER608SCL Manual

Argoclima
Argoclima Euro-Line AER518SC Manual

Argoclima
Argoclima AE64AC Manual