TECHNICAL DATA & SERVICE MANUAL
Outdoor Unit Dual System Kit
AER522QC DKR-5555C
MULTI-SPLIT SYSTEM AIR CONDITIONER
Outdoor Unit Dual System Kit
AER522QC DKR-5555C
0.8180.130.0 02/2001
®

i
Important!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person,
it is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
●Carefully read this instruction booklet before
beginning.
●Follow each installation or repair step exactly as
shown.
●Observe all local, state, and national electrical codes.
●Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or
death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help
for a special problem, contact our sales/service outlet
or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR
DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIAN SHOULD
ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and
tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections
and inadequate grounding can cause accidental
injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your
knees when lifting to reduce strain on your back. Sharp
edges or thin aluminum fins on the air conditioner can
cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to
prevent “sweating” that can cause dripping and water
damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to
provide a solid, level foundation for the outdoor unit.
This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces
of the flare and union tubes before connecting them,
then tighten the nut with a torque wrench for a leak-
free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any
moving parts.
• Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or
testing the refrigeration system. Escaped refrigerant
gas, on contact with fire or heat, can produce
dangerously toxic gas.
• Confirm upon completing installation that no
refrigerant gas is leaking. If escaped gas comes in
contact with a stove, gas water heater, electric room
heater or other heat source, it can produce
dangerously toxic gas.
CAUTION

Table of Contents
Page
UNIT COMBINATION iiii
1OPERATING RANGE 1
2SPECIFICATIONS
2-1Unit Specification 2
2-2Major Component Specifications 4
2-3Other Component Specifications 5
3DIMENSIONAL DATA 7
4REFRIGERANT FLOW DIAGRAM 9
5ELECTRICAL DATA
5-1Electrical Characteristic 115-2Electric Wiring Diagrams 12
6INSTALLATION INSTRUCTION
6-1Installation Site Selection 166-2Place and Space for Installation 17
6-3Installation with Dual System Kit 18
6-4Wiring Instruction 19
7FUNCTION 21
8TROUBLESHOOTING
8-1Check before and after troubleshooting 22
8-2Air Conditioner Does not operate 23
8-3Some Parts of Air Conditioner does not operate 24
8-4Air Conditioner operates, but abnormalities are observed 26
9SPECIAL PRECAUTIONS WHEN SERVICING THE UNIT
9-1Blue/green connector attachment for servicing 28
9-2Refrigerant recovery 29
9-3Service on outdoor unit 29
9-4Evacuation using vacuum pump 29
9-5Refrigerant charging 30
9-6Reattaching green connectors for operation 31
10 REFRIGERANT R407C:SPECIAL PRECAUTION WHEN SERVICING THE UNIT
10-1Characteristics of new refrigerant R407c 33
10-2Checklist before servicing 33
10-3Tools specifically for R407c 34
10-4For tubing installation procedures 34
10-5In case of compressor malfunction 35
10-7Charging additional refrigerant 39
10-8Retro-fitting existing systems 39
ii
10-6 In case of refrigerant leaking 37

11 ARRANGEMENT OF ELECTRICAL COMPONENTS 40
12 CHECKING ELECTRICAL COMPONENTS
12-1Measurement of insulation resistance 42
12-2Checking motor capacitor 43
iii

iii
■Unit Combination
Combine indoor and outdoor units only as listed below.
Indoor Unit
Outdoor Unit A
B
C
Fig.1
Indoor Unit
Outdoor Unit
A
B
C1
C2
Fig.2
Dual System Kit
Symbol of
Indoor Unit
Outdoor Unit Indoor Unit
Dual System Kit
(Option)
AER522QC
AWR509CL
A
B Fig.1
Refer to
NON
AWR509CL
C
AWR509CL
A
Fig.2
AWR509CL
B
DKR-5555C
AWR509CL
C1
AWR509CL
C2
AWR509CL

1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.

2. SPECIFICATIONS
2-1. Unit Specifications
2
Symbol of indoor unit A , B , C : AWR509CL
Power Source 220 – 240 V ~ 50 Hz
Cooling
Max.Capacity kW 5.5
BTU/h 20,000
Indoor unit(s) A + B C A + B + C
Capacity kW 3 2.5 5.5
BTU/h 10,900 9,000 20,000
Voltage rating V 230
Available voltage range V 198 to 264
Running amperes A 5.0 4.2 9.2
Power input W1,100 1,000 2000
Power factor %95 95 95
C.O.P. W/ W 2.7 2.5 2.8
Compressor locked rotor amperes A24 24 48
Fan speed 1
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment gR407c / A + B : 950 C : 950
Refrigerant control Capillary tube
Operation sound dB-A 54
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m A + B : 15 C : 7.5
Refrigerant tube Narrow tube mm (in.) A , B , C : 6.35 (1/4)
diameter Wide tube mm (in.) A , B , C : 9.52 (3/8)
Refrigerant tube kit Optional
Dual system kit Non
AER522QC
Unit dimensions Height mm 630
Width mm 830
Depth mm 305
Package dimensions Height mm 713
Width mm 994
Depth mm 413
Weight Net kg 61.0
Shipping kg 66.0
Shipping volume m30.29
Dimensions & Weight Features Electrical Rating Performance
Outdoor Unit AER522QC
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.

3
Symbol of indoor unit A , B , C1 , C2 : AWR509CL
Power Source 220 – 240 V ~ 50 Hz
Cooling
Max.Capacity kW 5.6
BTU/h 20000
Indoor unit(s) A + B C1 + C2 A + B + C1 + C2
Capacity kW 3 2.85 5.60
BTU/h 10900 10000 20000
Voltage rating V230
Available voltage range V 198 to 264
Running amperes A 5 5 9.6
Power input W1100 1100 2100
Power factor %95 95 95
C.O.P. W/W 2.7 2.6 2.7
Compressor locked rotor amperes A24 24 48
Fan speed 1
Compressor Rotary (Hermetic)
Refrigerant / Amount charged at shipment gR407c / A + B :950 C1 + C2 :950
Refrigerant control Capillary tube
Operation sound dB-A 54
Refrigerant tubing connections Flare type
Max. allowable tubing length at shipment m A + B : 15 C1 + C2 : 15
Refrigerant tube Narrow tube mm (in.) A , B , C1 , C2 : 6.35 (1/4)
diameter Wide tube mm (in.) A , B , C1 , C2 : 9.52 (3/8)
Refrigerant tube kit Optional
Dual system kit Optional (DKR-5555C)
AER522QC DKR-5555C
Unit dimensions Height mm 630 414
Width mm 830 213
Depth mm 305 118
Package dimensions Height mm 713 170
Width mm 994 340
Depth mm 413 528
Weight Net kg 61.0 5.0
Shipping kg 66.0 6.0
Shipping volume m30.29 0.031
Dimensions & Weight Features Electrical Rating Performance
Outdoor Unit AER522QC with DKR-5555C(Option)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.

4
2-2. Major Component Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Symbol of indoor unit A, B : AWR509CL C : AWR509CL or C1, C2 : AWR509CL
Type Rotary (Hermetic)
Compressor Model name ... Q'ty C-RN80H5A ... 2 (CM1,CM2)
Code No. 80228245-G
Nominal output W800
Compressor oil cc 470 x 2
Coil resistance (Ambient temp. 25°C) ΩC – R :3.07
C – S : 7.97
Type External protector External protector
Overload relay ... Q'ty MRA38066-3229(OLR1,3) CS–7C115 (OLR2,4)
Safety Operating temp. Open °C 145 ± 5115±5
devices Close °C 69 ± 11 95 ± 10
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 16.5A —
Run capacitor ... Q'ty µF 22.5 ... 2
VAC 450 ... 2
Type Propeller
Q'ty ... Dia. mm 1 ... ø400
Fan motor model ... Q'ty 19TFB6047 ... 1
No. of poles ... rpm (230V, High) 6 ... 910
Nominal output W 50
Coil resistance (Ambient temp. 20°C) ΩWHT – BRN : 83.4
WHT – PNK : 218.7
Safety Type Internal protector
devices Operating temp. Open °C 130 ± 5
Close Automatic reclosing
Run capacitor µF 2.0
VAC 400
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.8
Face area m20.473
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil Compressor
Fan & Fan Motor
Outdoor Unit AER522QC

5
2-3. Other Component Specifications
Outdoor Unit AER522QC
Relay (R1, RR2) MCS24A2F1
Coil rating AC 240V
Coil resistance kΩ(at 20°C) 15.5 ± 15%
Contact rating AC 250V, 5A
Power Relay (PR1,PR2) G7L-2A-TUB
Coil rating AC 220/230/240V, Single Phase 50Hz
Coil resistance Ω(at 23°C) 21 ± 15%
Contact rating AC 220V, 25A
Timer (T) H3Y-2
Rating AC 220V, 50/60Hz
Operating time 3 minutes
Solenoid Valve (SV) NEV-MOAJ503B0 (Coil), NEV202DXF (Valve)
Rating AC 240V, 50/60Hz
7/6W, 45/35mA
Coil resistance kΩ(at 20°C) 1.15 ±7%
: AER522QC(R1,2)
: AER522QC(SVA,B)

6
Dual System Kit DKR-5555C
Relay (R1, R2) MY2-02-US-TS
Coil rating AC 240V
Coil resistance Ω(at 20°C) 650 ± 15%
Contact rating AC 240V, 4.4A
Solenoid Valve (SV) NEV-MOAJ503B0 (Coil), NEV202DXF (Valve)
Rating AC 240V, 50/60Hz
7/6W, 45/35mA
Coil resistance kΩ(at 20°C) 1.15 ±7%
Timer (T) H3Y-2-0
Rating AC 200–230V, 50/60Hz
Operating time 3 minutes
(SVC1,C2)

7
3. DIMENSIONAL DATA
Outdoor Unit AER522QC
58830
337
307
630
19
33305
5749
Air intake
Air discharge
538 146
93 4040404040
4 – ø12 Holes
Wide tube service valve : ø9.52 (3/8")
Narrow tube service valve : ø6.35 (1/4")
Wide tube service valve : ø9.52 (3/8")
Narrow tube service valve : ø6.35 (1/4")
Wide tube service valve : ø9.52 (3/8")
Narrow tube service valve : ø6.35 (1/4")
A
B
C
A
B
C
Unit : mm

8
Dual System Kit DKR-5555C
10 84
5072 50 50
118
56
34
46
32
76.5
213
393
400
414
Wide tube service valve
Unit C1 : ø9.52 (3/8")
Narrow tube service valve
Unit C1 : ø6.35 (1/4")
Wide tube service valve
Unit C2 : ø9.52 (3/8")
Narrow tube service valve
Unit C2 : ø6.35 (1/4")
Charge port
ø6.35 (1/4")
Wide tube service valve
From Unit C : ø9.52 (3/8")
Narrow tube service valve
From Unit C : ø6.35 (1/4")
Unit : mm

4. REFRIGERANT FLOW DIAGRAM
9
Evaporator
Indoor Unit C
(AWR509CL)
Wide tube
O.D.
ø9.52mm
(3/8 ")
Capi box
Narrow tube
O.D.
ø6.35mm
(1/4 ")
SAP-MC2247G5
3 Indoor Unit's Combination
Wide tube service valve
Narrow tube service valve
Capillary tube
Outdoor Unit
(AER522QC)
Wide tube
O.D.
ø9.52mm
(3/8 ")
Condenser
Compressor 2
Accumulator
B
Evaporator
Indoor Unit A
(AWR509CL)
Strainer
A
A
B
Evaporator
Indoor Unit B
(AWR509CL)
SVA
SVB
Narrow tube
O.D.
ø6.35mm
(1/4 ")
Compressor 1
Accumulator
Strainer C
C
S
S
Outdoor Unit AER522QC
3 Indoor Unit's Combination

10
SAP-MC2247G5
ATK-P244G5
4 Indoor Unit's Combination with Dual Syatem Kit
Wide tube service valve
Narrow tube service valve
Capillary tube
Outdoor Unit
(AER522QC)
Wide tube
O.D.
ø9.52mm
(3/8 ")
Condenser
Compressor 2
Accumulator
B
Evaporator
Indoor Unit A
(AWR509CL)
Strainer
A
A
B
Evaporator
Indoor Unit B
(AWR509CL)
SVA
SVB
Narrow tube
O.D.
ø6.35mm
(1/4 ")
Compressor 1
Accumulator
Strainer C
C
S
S
Wide tube
O.D.
ø9.52mm
(3/8 ")
SVC1
SVC2
S
S
Strainer
Narrow tube
O.D.
ø6.35mm
(1/4 ")
Evaporator
Indoor Unit C1
(AWR509CL)
Evaporator
Indoor Unit C2
(AWR509CL)
Dual System Kit
(DKR-5555C)
Check port
Outdoor Unit AER522QC with DKR-5555C
4 Indoor Unit's Combination with Dual System Kit

5. ELECTRICAL DATA
5-1. Electrical Characteristics
The values in the table below indicate the sum of indoor
units which are in running condition.
11
NOTE
230V Single phase 50 Hz
Outdoor Unit AER522QC
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Number of indoor unit 3 - Units 4 - Units
(A + B + C) (A + B + C1 + C2)
Rating Conditions Running amp. A9.2 9.6
Power input kW 2.00 2.10
Full Load Conditions Running amp. A10.0 11.0
Power input kW 2.33 2.35

5-2. Electric Wiring Diagram
Outdoor unit AER522QC

13
Outdoor Unit DKR-5555C

ELECTRIC WIRING SYSTEMS
AWR509CL
AWR509CL
AWR509CL
AWR509CL or AFR509CL AER522QC
AWR509CL or AFR509CL
AWR509CL or AFR509CL
AER522QC
AFR509CL
14

15
AWR509CL or AFR509CL AER522QC
AWR509CL or AFR509CL
AWR509CL or AFR509CL
AWR509CL or AFR509CL
AWR509CL
AWR509CL
AWR509CL
AWR509CL
AFR509CL
DK5555C
AER522QC
DK5555C
Table of contents
Other Argoclima Air Conditioner manuals

Argoclima
Argoclima AW22AL Manual

Argoclima
Argoclima AS52AL Manual

Argoclima
Argoclima Euro-Line AER518DH Manual

Argoclima
Argoclima Euro-Line AS28AL Manual

Argoclima
Argoclima AWR512CL Operating manual

Argoclima
Argoclima ARGO 245C Manual

Argoclima
Argoclima AE64AC Manual

Argoclima
Argoclima Euro-Line AER518SC Manual

Argoclima
Argoclima AER608SCL Manual

Argoclima
Argoclima oscar junior Manual