manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Assa Abloy
  6. •
  7. Relay
  8. •
  9. Assa Abloy Securitron R8 User manual

Assa Abloy Securitron R8 User manual

Securitron®R8
Power Relay Module
Quick Start Guide
Overview
1 FlexIO Connectors – These connectors pass the
FAI signal to the R8 board and pass the FlexIO buss
on to other accessory boards in the system.
2 B1, B2, and BR Connectors – These connectors are the voltage
inputs for the R8 board. BR is the DC Common buss in the system.
B1 is the positive voltage input for the first power supply. In dual
voltage systems, B2 is the input for the second power supply.
3 Zone Inputs (IN1 – IN8) – These are the zone input
terminal strips. These terminal strips are removable and
accept wire sizes from AWG 14 – AWG 22. The terminals
are labeled on the PC board near the terminal strip.
•When using a normally open relay contact input, the
contact is connected across the IN and GND terminals.
•When using an open collector (transistor) input,
the open collector it connected to the IN terminal.
Note that the input source must be common
grounded with the R8 board’s power source.
4 Voltage Selection Jumpers (YELLOW) – These jumpers select the
power input to be used for each output. For single voltage systems,
this jumper should stay in the B1 position. This jumper should be
removed on any zones where a dry contact output is needed.
5 Relay State LEDs (RED) – These LEDs indicate the state
of the output relay. The LED will be lit when the relay is
active and extinguished when the relay is not active.
6 Output Voltage LEDs (Dual Color – BLUE/GREEN) – These
LEDs indicate the voltage of the zone’s output.
•Blue The output is set to 24 V
•Green The output is set to 12 V
•Off Fuse open or dry contact output selected
7 Zone Outputs (01 – 08) – These are the zone output terminal
strips. These terminal strips are removable and accept wire sizes
from AWG 14 – AWG 22. The terminals are labeled on the PC board
near the terminal strip. See the Output Wiring section for more
information. C, NC, and NO are the relay output. Details next page.
8 Dry Output Selection (BLACK)
– When a dry contact output is
needed, this jumper must be removed
in addition to the yellow jumper
for the zone. The output diodes
must also be cut for the zone.
9 Output Fuses (F1 – F8) – These are
the fuses for each zone output.
Fuse numbers correspond with
the zone number (e.g. F1 is the
fuse for OUTPUT1). Fuses are not in
the circuit when the zone is being
used as a relay contact output.
10 FAI LED (RED) – These LED indicates
that the R8 has received an FAI signal from the Securitron
AQL power supply through the FlexIO connector. When
lit, any zones selected to respond to FAI will unlock.
11 FAI Selection Switches (SW1) – These switches select FAI for
each output. Switch 1 is for zone 1, switch 2 for zone 2, etc. When
the switch is ON, the zone will unlock when an FAI is received.
NOTE When a dry
contact output is
needed, the Yellow
and Black jumpers
must be removed
and the output
diodes must be cut
CAUTION When
powering magnetic
loads such as
maglocks, door strikes,
solenoids, etc, each of
these loads must have
a reverse protection
diode either built-in or
external to the device.
Specifications and more details
found in the full manual here.
(Downloadable pdf)
GND GND GND GND
1234 GND GND GND GND
5678
INPUT 1– 4 INPUT 5 – 8
FAI
1
8
GND GND GND GND
1234 GND GND GND GND
5678
NC C N0 COM NC C N0 COM
OUTPUT 1 OUTPUT 2
NC C N0 COM NC C N0 COM
OUTPUT 3 OUTPUT 4
NC C N0 COM NC C N0 COM
OUTPUT 5 OUTPUT 6
NC C N0 COM NC C N0 COM
OUTPUT 7 OUTPUT 8
B2
BR
B1 B2 B1 B2 B1 B2 B1 B2 B1 B2 B1 B2 B1 B2 B1 B2
B1
2
8
10
11
6
5
4
7
9
1
3
techsupport.esh@assaabloy.com | assaabloyesh.com
800 626 7590 | 10027 S. 51st Street Phoenix, AZ 85044 USA
Patent pending and/or patent www.assaabloydss.com/patents
Copyright © 2020, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company.
All rights reserved. Reproduction in whole or in part without the express written
permission of Hanchett Entry Systems, Inc. is prohibited. M001-014_1
Input Wiring
Each input on the R8 has an “IN”
terminal and a “GND” terminal.
•When using a NO relay contact to activate the
input, the contact is placed across these terminals.
•To use a DC ground or an open collector (transistor)
as an input, connect the ground/open collector
to the “IN” terminal to activate the input.
Note that the input source must be common
grounded with the R8 board’s power source.
Output Wiring
•Each output on the R8 has “NC”, “C”,
“NO”, and “COM” terminals.
•When set for a dry contact output, the C, NC,
and NO terminals may be used as any relay
would. C to NC will have a connection when
the red LED for the zone is not lit. C to NO will
have a connection when the red LED is lit.
NOTE: To set the output as a dry contact, the
yellow and black jumpers for the zone must be
removed and the output diodes must be cut.
•When set for a voltage output, the
terminal use is as follows:
› COM – This is the negative DC Common
for the device being powered
› C – This terminal always has positive voltage, regardless
of the relay state. This terminal may be used to
power auxiliary devices such as REX or readers.
› NC – This output has positive voltage
when the relay is NOT ACTIVE. This
terminal is used for FAIL SAFE locks
› NO – This output has positive voltage when the relay
is ACTIVE. This terminal is used for FAIL SECURE locks
NOTE: Other Securitron Power Boards (not part of
AQL series) use C as a negative DC common.
Power Control Dry
Contact Output
The outputs of the R8 have built-in reverse protection
diodes. If a delay in lock release is present or if the zone is
being used as a dry contact output, the diode from that
zone may be removed from the circuit as shown below.
NOTE: Only remove the diodes from
outputs requiring their removal
Diode Removal
The diodes on the R8 are on the top side of the board
between the output terminals and the edge of the
board. To remove the diode from the output circuit,
simply cut the exposed diode lead for the desired
output zone - leave the diode body soldered to the pcb.
GND GND GND GND
1234 GND GND GND GND
5678
INPUT 1– 4 INPUT 5 –8
GND GND GND GND GND GND GND GND
B2
BR
B1
IN1 IN2 IN3 IN4 IN8IN7IN6IN5
NC C N0 COM NC C N0 COM
OUTPUT - 1 OUTPUT - 2
NC C N0 COM NC C N0 COM
OUTPUT - 1 OUTPUT - 2
NC C N0 COM NC C N0 COM
OUTPUT - 1 OUTPUT - 2
NC C N0 COM NC C N0 COM
OUTPUT - 1 OUTPUT - 2
INPUT 1 – 2 INPUT 3 – 4 INPUT 5 – 6 INPUT 7 – 8

Popular Relay manuals by other brands

Pilz PNOZ X9P AC/DC operating instructions

Pilz

Pilz PNOZ X9P AC/DC operating instructions

Eaton easy800 manual

Eaton

Eaton easy800 manual

Basler BE1-59N instruction manual

Basler

Basler BE1-59N instruction manual

Dossena 9DER3/2IM quick start guide

Dossena

Dossena 9DER3/2IM quick start guide

GE D30 series instruction manual

GE

GE D30 series instruction manual

FANOX D30 manual

FANOX

FANOX D30 manual

Seg MRN3 manual

Seg

Seg MRN3 manual

Leuze electronic ML2R-SR4 manual

Leuze electronic

Leuze electronic ML2R-SR4 manual

Avantree BTTC-218 user manual

Avantree

Avantree BTTC-218 user manual

Siemens SIRIUS 3TK2821 operating instructions

Siemens

Siemens SIRIUS 3TK2821 operating instructions

GE GCX51A instructions

GE

GE GCX51A instructions

Pilz PZE X4V8 operating manual

Pilz

Pilz PZE X4V8 operating manual

Koncar konpro manual

Koncar

Koncar konpro manual

Aqara T1 quick start guide

Aqara

Aqara T1 quick start guide

Areva MCAG 19 Service manual

Areva

Areva MCAG 19 Service manual

MULTISPAN VPR 3P manual

MULTISPAN

MULTISPAN VPR 3P manual

Contec F&eIT Series First step guide

Contec

Contec F&eIT Series First step guide

Mitsubishi Electric CBV2-A01D1 instruction manual

Mitsubishi Electric

Mitsubishi Electric CBV2-A01D1 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.